CL-B101D40-TCRTD Manual (d0099)
Page 3
Software Logic Tree
The
CL-B101D40-TCRTD
is an intelligent bargraph meter with a
hierarchical software structure designed for easy programming
and operation, as shown below in the software logic tree.
Software Version is Displayed on Power-up
When power is applied, all segments of the bargraph and
digital display light up for 3 seconds. The version number of
the installed software is then displayed for 2 seconds, after
which, the operational display indicates the input signal.
15 Second Program Timeout
Except for ZERO and SPAN settings in the Analog Output Range Setting and
Calibration Mode (cLo and chi), the meter has a 15 second program timeout. If
no buttons are pressed for 15 seconds in any of the other programming
sequences, the meter will exit the programming mode and return to the opera-
tional display. Any program changes that were made prior to pressing the
P
button in the preceding step will not be saved.
[orAn]
[rEd]
[H]
[L]
NOTE: Will only
appear if a tricolor
display is installed
[orAn]
[rEd]
[orAn]
[rEd]
[orAn]
[rEd]
[orAn]
[rEd]
BARGRAPH COLOR
PROGRAMMING MODE
See Page 9
Tricolor Bargraph
The tri-color bargraph is designed
like a traffic light, to display either
red, orange or green, but only one
color at a time. The color to be
displayed is selected in two ways.
The first step is to select the color to
be displayed when the bar is “below”
whichever set point is set to the
lowest position.
The second step is to select the color
to be displayed when the bar is
above each specific setpoint,
regardless of the order or position to
which the set points are set.
However, if two or more setpoints
with differently specified colors are
positioned at the same set point
value, the color specified for the set
point with the highest identifying
number will be displayed. When
setpoints are set to the same value,
the SP4 color overrides the SP3
color, the SP3 color overrides the
SP2 color, and the SP2 color
overrides the SP1 color.
Set Setpoint 1
(SP1)
Delay-on-Make
(doM)
Delay-on-Break
(dob)
0 to 9999 seconds
Relays
Activation
[rLYS] (H) High
the relay
energizes when
the setpoint is
exceeded
[rLYS] (L) Low
the relay
energizes below
the setpoint.
Setpoint 2 (SP2)
NOTE: [dom] [dob]
Functions are only
available for SP1
0 to 9999 seconds
Pump (PUM)
Hysteresis (hYSt)
Hysteresis (hYSt)
Hysteresis (hYSt)
Setpoint 3 (SP3)
Setpoint 4 (SP4)
Operational Display
MAIN MENU
BRIGHTNESS AND
SETPOINT VIEW MODE
Bargraph Center Point
Display Selection (cto)
This branch will
only appear if
the analog
output option
is installed
Back to
Operational
Display
Digital Display ON/OFF
Selection (diSP)
Sub-menu MODE
Calibration Mode
Calibration
Input
Calibration
Output
Calibrate Analog
Output Lo
Calibrate Analog
Output Hi
Select the Digital
Reading at which
the Analog Output
Hi (chi) will occur
Select the Digital
Reading at which
the Analog Output
Lo (cLo) will occur
This branch will only appear
if the analog output option
is installed
DIGITAL SPAN SELECTION
FOR ANALOG RANGE OUTPUT
See Page 6
DIGITAL DISPLAY ON/OFF
See Page 6
BARGRAPH CENTER POINT
DISPLAY MODE SELECTION
See Page 6
TWO POINT ANALOG OUTPUT
RANGE SETTING AND CALIBRATION
See Page 7
Bargraph Display
Scale Lo Range
Setting (bLo)
Bargraph Display
Scale hi Range
Setting (bhi)
Display
Brightness (br)
1 Dimmest
2 Dim
3 Bright
4 Brightest
BRIGHTNESS SELECTION
See Page 5
DIGITAL SPAN SELECTION
FOR BARGRAPH DISPLAY
See Page 5
if Analog Output is not installed,
goes directly to Input selection
+
–
4.00
+
–
20.00
1 Dimmest
2 Dim
3 Bright
4 Brightest
SETPOINT SETTING AND
RELAY CONFIGURATION MODE
See Page 8
H or L
H or L
H or L
H or L
SP1
[H]
[L]
SP2
[H]
[L]
SP3
[H]
[L]
SP4
[K]
[r]
[t]
If RTD module is installed
this menu will appear.
3 or 4 wire
RTD input
selection
RTD select type
P385 or P392
If Thermocouple module is
installed this menu will appear.
Resolution select
Thermocouple
select
Select J, K, R or T
1
°
0.1
°
Degree select
°
C
°
F
THERMOCOUPLE OR RTD TYPE,
RESOLUTION AND DEGREE C OR
°
F SELECT
See Page 4
Pump On Pump Off
When PUM is selected ON,
and SP2 is set at a value
higher than SP1, the SP1
relay will operate in
a special "pump on pump off"
Hysteresis mode. SP2 acts
as the upper limit and SP1
acts as the lower limit of the
Hysteresis Band.
For filling applications, rLYS
should be set to LhLh. SP1 will
then activate for inputs less than
the SP1 setpoint, and remain
ON until the SP2 setpoint is
reached.
For emptying applications,
rLYS should be set to hhhh.
SP1 will then activate for inputs
greater than the SP2 setpoint,
and remain ON until the SP1
setpoint is reached.
Peak
[PEAK]
Reset
PEAK
Reset
VALY
Valley
[VALY]
PEAK & VALLEY
VIEW & RESET
FL-B101D40H_LogicTree_v2.0
°
C
°
F
Displays
°
C or
°
F whichever
is the opposite of the
selected operational display