Premier Elite 5Ci-W Internal
Installation Manual
4
INS655-3
LED Indications
The
Premier Elite 5Ci-W
LED’s aid in the installation of the device and act as status indicators. The table below details the status of each
LED indicator.
T
he LED jumper has no effect on the status described below.
Leds
Status
Left LED flashing quickly
Device is attempting to communicate with receiver after power up.
Left LED flashing slowly
Device has learnt or re-connected to receiver and is waiting for the tamper to be
closed.
Both LEDs off
Device has failed to learn or failed to communicate after tamper has been
closed.
Right LED flashing quickly
Device is attempting to communicate with receiver after tamper has been
closed.
Right LED on solid (for 3 seconds)
Device has successfully connected with receiver after tamper closed.
Right LED flashing slowly
Hold-off mode has been requested from the panel but the tamper is closed. Bell
will not self-activate. Cancels after 20 minutes.
LEDs alternating quickly.
Device has successfully connected with receiver after tamper closed and self-
activation on tamper will re-activate in 2 minutes.
Both LEDs flashing
1 or 2 batteries are fitted incorrectly. Remove the batteries and reinstall correctly.
Hold-Off Mode
For safety reasons, each Texecom sounder and strobe unit incorporates a unique patented engineer Hold-Off mode. This mode prevents
the unit from self-activating during installation and maintenance, thereby allowing only bona fide engineers access to the unit without any
loss of tamper protection. The sounder can be put in hold-off mode by flashing the strobe 3 times, or by pressing the Omit key when in Bell
Test menu.
When the outer cover is replaced and the tamper circuit is closed, the LEDs will alternate rapidly, confirming that the tamper circuit is secure
and signalling that self activation on tamper will be re-enabled within 2 minutes, after which the LEDs will alternate slowly to signal normal
operation. If the tamper circuit is re-opened within the 2 minute period, then hold-off mode will be restored.
The LED's will only flash after hold off mode has stopped IF the LED jumper is in the "ON" position.
The strobe is disabled during hold-off mode. Hold-off mode is immediately cancelled when the sounder is activated from the control panel if the
tamper is closed.
.
Tamper Detection
As this unit is designed for internal applications only and may be mounted at low level and within easy reach the SAB facility has been
disabled. The unit
WILL NOT
self activate in the case of the device being tampered.
Care should be taken when installing these devices, and all possible precautions should be taken to ensure the units are not easily
accessible to unauthorised persons.
Tamper signals will still be generated and logged by the control panel. Tamper signals will also be transmitted to the ARC if signalling is
enabled.
Mounting the Unit
Select a suitable position to mount the unit, which satisfies the following criteria:
Good wireless signal
The wireless signal may be checked before final installation by depressing the tamper switch briefly. The Right LED will flash to indicate
communication and will the go solid for 3 seconds to indicate a successful connection.
Highly prominent for maximum deterrence
High enough to be out of normal reach to deter tampering. See above
In addition to the corner screw fixing points, the unit also has a central keyhole to simplify mounting and aid levelling.
Four screws and wall plugs are required for mounting the backplate to an even surface.
An additional screw is required to provide "Removal from Mounting" tamper and is required in installations complying with the requirements PD6662
and/or EN50131. In doing so, care must be taken to leave the screw head slightly proud to ensure that the microswitch remains level and closes
correctly when the outer cover is fitted.