Test Results
14
SLVUBC9 – December 2017
Copyright © 2017, Texas Instruments Incorporated
TPS23523EVM-863 Evaluation Module
Lin = 20 µH, scope GND = –48V_A,
Figure 42. Load Step (0 A–11 A)
Lin = 20 µH, scope GND = –48V_A
Figure 43. Load Step Into Overcurrent
Lin = 20 µH, scope GND = -48V_A
Figure 44. Start Into Short
Lin = 20 µH, scope GND = –48V_A
Figure 45. 1-ms Brown Out
The
TPS23523 EVM – Measured Voltage Monitoring Accuracy
table shows excellent voltage monitoring
accuracy was achieved.
Table 5. TPS23523 EVM – Measured Voltage Monitoring Accuracy
V
IN, ACT
(V)
V
BUS, ACT
(V)
V
IN, MEAUS
(V)
Error
38.48
1.989
38.46
–0.05%
47.98
2.481
47.97
–0.02%
58.48
3.024
58.47
–0.02%