Applications Guide
The following table gives an overview of recommended Test Levels for several surge arresters.
Arrester Type
Arrester Unit Rating
[kV]
Test Voltage
[kV]
Silicon Carbide
3.0
2.5
4.5
4.0
6.0
5.0
7.5
7.0
9.0 / 10.0
7.5
12.0 and above
10
Metal Oxide
2.7 to 3.0
2.0
4.5 to 12.0
2.5
15.0 and higher
10.0
14.8.2
Test Procedures
Surge arresters can be equipped with leakage-current detectors or discharge counters. When testing
such units the detector or counter should be short-circuited by applying a ground directly to the base
of the arrester. The short-circuit must be removed before the arrester is returned to service.
Test Procedure on a Single-Unit Arrester
Arrester assemblies consisting of single units per phase can be tested by the grounded-specimen test
method (GST). The line connected to the arrester is first de-energized and grounded, then
disconnected from the arresters.
DUT
Test
Mode
High
Voltage
to
INPUT
A
to
INPUT
HV GND
to
GND
S1
GSTg A+B
1
-
2
2
Single-unit arrester measurement
Test Procedure on a Double-Unit Arrester Stack
Assemblies consisting of two units per phase are tested in the manner
outlined below. Again, the line is de-energized and grounded then
disconnected from the arrester stack.
DUT
Test
Mode
High
Voltage
to
INPUT
A
to
INPUT
HV GND
to
GND
S1
UST A
2
1
3
3
S2
GST gA+B
2
1
3
3
Double unit arrester stack measurement, connection for measurement of S1.