CHAPTER 4
OPERATION
4-4
Displays of series DN-109NN, DN-119NN, DN-129NN and DN-189NN
4.2.2.4
Parameters B, C, D, E (color option)
The color option allows auto set the display color according to the value displayed. The
possible colors are: Red, Green and Yellow.
In order to be able to manage the color, 2 internal bits are used (r1 y r2) that change
according to display value. To configure the activation levels of these bits, two parameters for
each one are used. Parameter B and C configures the bit r1, and parameter D and E configure
the bit r2.
4.2.2.4.1
Parameters to define the internal bit r1.
Parameter B is used to set up the activation condition and the delay or hysteresis
Parameter C defines the trigger level. The most significant digit allows setting up a
negative value.
Parameter B
Left Digit
Control bit
Right Digit
Set/Reset
0
ON if Value > Parameter C
0
No delay / No hysteresis
1
ON if Value < Parameter C
1
Delay 1s
2
Always OFF
2
Delay 2s
3
Delay 4s
4
Delay 6s
5
Delay 10s
6
Hysteresis = 2
7
Hysteresis = 4
8
Hysteresis = 8
9
Hysteresis = 12
4.2.2.4.2
Parameters to define the internal bit r2
Parameter D is used to set up the activation condition and the delay or hysteresis.
Parameter E is used to set up the trigger level. The most significant digit allows setting
up a negative value.
Parameter D
Left Digit
Control bit
Right Digit
Set/Reset
0
ON if Value > Parameter E
0
No Delay / hysteresis
1
ON if Value < Parameter E
1
Delay 1s
2
Always OFF
2
Delay 2s
3
Delay 4s
4
Delay 6s
5
Delay 10s
6
Hysteresis = 2
7
Hysteresis = 4
8
Hysteresis = 8
9
Hysteresis = 12