30
ENG
16.
Information on servicing
:
1. Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure
that the risk of ignition is minimized. For repair to the refrigerating system, the following precautions shall be
complied with prior to conducting work on the system.
2. Work procedure
Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or
vapour being present while the work is being performed.
3. General work area
All maintenance staff and others working in the local area shall be instructed on the nature of work being
carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off.
Ensure that the conditions within the area have been made safe by control of flammable material.
4. Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the
technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment being
used is suitable for use with flammable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe
5. Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire
extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to
the charging area.
6. No ignition sources
No person carrying out work in relation to a refrigeration system which involves exposing any pipe work shall
use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition
sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing,
removing and disposal, during which refrigerant can possibly be released to the surrounding space. Prior to
work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable
hazards or ignition risks. “No Smoking” signs shall be displayed.
7. Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or
conducting any hot work. A degree of ventilation shall continue during the period that the work is carried
out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the
atmosphere.
8. Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose and to the correct
specification. At all times the manufacturer’s maintenance and service guidelines shall be followed. If in doubt
consult the manufacturer’s technical department for assistance.
The following checks shall be applied to installations using flammable refrigerants:
- The charge size is in accordance with the room size within which the refrigerant containing parts are installed;
- The ventilation machinery and outlets are operating adequately and are not obstructed;
- If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of
refrigerant;
- Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be
corrected;
- Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any
substance which may corrode refrigerant containing components, unless the components are constructed of
materials which are inherently resistant to being corroded or are suitably protected against being so corroded.
9. Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and component inspection
procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to
the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to
continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the
equipment so all parties are advised.
Initial safety checks shall include:
-That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;
-That there no live electrical components and wiring are exposed while charging, recovering or purging the
system;
-That there is continuity of earth bonding.
17.
Repairs to sealed components
1. During repairs to sealed components, all electrical supplies shall be disconnected from the equipment
being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical
Содержание TT26EX21-0932IA
Страница 74: ...74 BG 4A 250V III 50 cm 8...
Страница 75: ...75 BG...
Страница 76: ...76 BG No 1 2 3 4 LED 5 6 7 8 9 10 11 12 No 13 14 15 16 17...
Страница 77: ...77 BG No Led 1 SLEEP SLEEP 2 1 Timer 2 3 TIMER Timer COOL 3 HEAT 5 COOL...
Страница 81: ...81 BG 1 2 3 4 1m flashing swing 1 1 2 deactivate 2 2 2 1 2 deactivate flashing 3 2 2 Fan...
Страница 82: ...82 BG fan auto COOL MODE COOL 1 2 3 HEAT MODE HEAT 1 2 3 MODE DRY FAN MODE FAN AUTO MODE AUTO AUTO 2 10...
Страница 88: ...88 BG 10Pa 5g 10g A 5 B 10 C D A B 22 R290 R161 R410A 32 Water drain pipe...
Страница 89: ...89 BG mm 250cm...
Страница 90: ...90 BG 1 65 2 1 2 3 4 PCB 1 2 32mm 3 4 5...
Страница 91: ...91 BG 3 1 3 1 2 3 4 R32 R290 1 2 3 4 1 2...
Страница 92: ...92 BG 1 2 3 4 1 25mm 2 1 2 3 4 5 6 1...
Страница 93: ...93 BG 1 2 3 1 2 3 4 10 15 10 mm Hg 5 6 1 4 10 7 8 R290 0 4 0 6Mpa 1 5 2 0Mpa R32 0 8 1 2Mpa 3 2 3 7 Mpa...
Страница 94: ...94 BG 1 2 3 4 ON OFF FAN MODE TIMER 6 1 4 7 7 1 2 8 1 8 8 t...
Страница 98: ...98 BG 6 N B LCD 1 2 3 45 C 4 5 1 2 40 3 1 2 3...
Страница 99: ...99 BG TIMER ON LIGHT...
Страница 100: ...100 BG IPM PCB EEPROM 1 2 4m2 3 4 4m2 5 6 7 8 9 10 11 12 13 14 15...
Страница 101: ...101 BG 16 1 2 3 4 5 CO2 6 7 8 9 17 1...
Страница 102: ...102 BG 2 18 19 20 21 LFL 25 OFN 22 OFN OFN OFN...
Страница 103: ...103 BG 23 a b c d e f g h 80 i j k 24 25 https tesla info wp content uploads pdf TeslaTTWiFiapp pdf...
Страница 105: ...105 24 13 12 TESLA 1 2 2 1 2 2 TESLA 2 3 2 4 2 5 2 6 2 7 2 8 2 9 2 10 2 11...
Страница 106: ...106 2 12 3 4 5 6 7 8 112 115 119 112 1 2 1 2 3 113 1 2 3 2 114 4 5 114 1 113 1 2 2 3...
Страница 107: ...107 115 4 115 1 2 1 3 1 1 10 02 9700970 02 9700971 9 30 19 00 10 00 16 00...
Страница 108: ...108...
Страница 109: ...109 GR 4A 250V H 50 cm 8...
Страница 110: ...110 GR...
Страница 111: ...111 GR 1 2 3 4 LED 5 6 7 8 9 10 11 12 13 14 15 16 17...
Страница 112: ...112 GR 1 SLEEP 2 1 2 3 3 5...
Страница 114: ...114 GR HEALTH 3 Ap 1 2 3 4 AUTO 5 COOL 6 DRY 7 FAN 8 HEAT 9 ECO ECO...
Страница 115: ...115 GR 2 LRO 3 AAA 1 5V Ap 10 TIMER 11 12 Flashing 13 14 SUPER 15 16 Flashing 17 18 19 HEALTH WIND FREE GENMODE ECO...
Страница 116: ...116 GR 1 2 3 4 1 m 1 1 2 2 2 2 1 2 2 2...
Страница 117: ...117 GR FAN MODE COOL 1 2 3 MODE HEAT 1 2 3 MODE DRY MODE FAN MODE AUTO 2 10...
Страница 123: ...123 GR 10 Pa 5 g 10 g A 5 B o 10 A B R22 R290 R161 R410A R32...
Страница 124: ...124 GR mm 250 cm...
Страница 125: ...125 GR 1 65 2 1 2 3 4 1 2 32 mm 3 4 5...
Страница 126: ...126 GR 3 1 3 1 2 3 4 R32 R290 1 2 3 4 1 2 NAI OXI NAI OXI OXI...
Страница 127: ...127 GR 1 2 3 4 1 25 mm 2 1 2 3 4 5 6 1 1...
Страница 128: ...128 GR 1 2 3 1 2 3 2 3 4 10 15 10 mm Hg 5 6 2 1 4 10 7 2 3 8 R290 0 4 0 6 MPa 1 5 2 0 MPa R32 0 8 1 2 MPa 3 2 3 7 MPa...
Страница 129: ...129 GR 1 2 3 4 MODE 3 2 3 6 1 4 7 7 1 2 8 1 8 8...
Страница 133: ...133 GR 6 LCD 1 2 3 45 oC 4 5 1 2 40 C 3 1 2 3...
Страница 134: ...134 GR...
Страница 135: ...135 GR IPM EEPROM 1 2 4 m2 3 4 4 m2 5 6 7 8 9 10 11 12 13 14 15...
Страница 136: ...136 GR 16 1 2 3 4 5 CO2 6 7 8 9...
Страница 137: ...137 GR 17 1 2 18 19 20 21 LFL 25 OFN 22 OFN...
Страница 138: ...OFN OFN 23 80 24 25...
Страница 139: ...139 GR SmartWiFi https tesla info wp content uploads pdf TeslaTTWiFiapp pdf...
Страница 141: ...141 7 service TESLA TESLA 8 9 TESLA 10 email warranty gr comtrade com...
Страница 142: ...142 1 Service 2 Service 3 Service 4 Service 5 Service 6 Service 7 Service 8 Service 9 Service...
Страница 208: ...208 MK 4A 250V III 50 cm 8...
Страница 209: ...209 MK...
Страница 210: ...210 MK 1 2 3 4 LED 5 6 7 8 9 10 11 12 13 14 15 16 17...
Страница 211: ...211 MK Led 1 SLEEP 2 1 2 3 COOL 3 HEAT 5 COOL...
Страница 215: ...215 MK 2 LRO 3 AAA 1 5 V ECO EKO 1 2 3 4 1 m...
Страница 216: ...216 MK Swing 1 FLAP 1 2 swing 2 2 2 1 2 swing 2 2 COOL MODE COOL 1 2 3...
Страница 217: ...217 MK HEAT MODE HEAT 1 2 3 DRY MODE DRY FAN MODE FAN AUTO MODE AUTO 2 10 OPTION DISPLAY DISPLAY OPTION LED LED LED...
Страница 223: ...223 MK 10 Pa 5 g 10 g 5 10 22 R290 R161 R410A 32...
Страница 224: ...224 MK mm 250...
Страница 225: ...225 MK 1 65 2 1 2 3 4 1 2 32 mm 3 4 5...
Страница 226: ...226 MK 3 1 3 1 2 3 4 R32 R290 1 2 3 4 1 2...
Страница 227: ...227 MK 1 2 3 4 1 25 mm 2 1 2 3 4 5 6 1...
Страница 228: ...228 MK 1 2 3 1 2 3 4 10 15 10 mm Hg 5 6 1 4 10 7 8 R290 0 4 0 6 Mpa 1 5 2 0 Mpa R32 0 8 1 2 Mpa 3 2 3 7 Mpa...
Страница 229: ...229 MK 1 2 3 4 ON OFF FAN MODE TIMER 6 1 4 7 7 1 2 8 1 8 8...
Страница 233: ...233 MK 6 LCD 1 2 3 45 C 4 5 1 2 40 C 3 1 2 3...
Страница 234: ...234 MK TIMER ON COOLING DEHUMIDIFYING DRY LIGHT...
Страница 235: ...235 MK IPM PCB EEPROM 1 2 4 m2 3 4 4m2 5 6 7 8 9 10 11 12 13 14 15...
Страница 236: ...236 MK 16 i 1 2 3 4 5 CO2 6 7 8 a a 9 17...
Страница 237: ...237 MK 1 2 18 19 20 21 LFL 25 oxygen free nitrogen OFN 22...
Страница 238: ...23 a 80 24 25...
Страница 239: ...239 MK WiFi https tesla info wp content uploads pdf TeslaTTWiFiapp pdf...
Страница 241: ...241 1 30 2 3 3 12 12 12...
Страница 242: ...242...
Страница 243: ...243 Customer signature m C C V 15 1 2 3 C C V C C V...
Страница 245: ...245 070 503 855 078 213 502 070 218 860 078 522 660 Te a Te 075 650 888 078 213 502 078 213 502 078 522 660...
Страница 352: ...www tesla info...