26
5.4 Connecting The UPS Power Cables
CAUTION! Only qualified personnel should install or service UPS / batteries.
The ac input to the UPS should be supplied by a separate line from the ac distribution board.
The input/output cables can be sized to suit the modules rating according to the table below.
The connections of the electric panel should be supplied by grounded outlet. Cables enter the UPS modules via
entry panels in the base of cabinet. All control cables should be screened and run in a separate trunking to the
power cables.
The input/output cables can be sized to suit the modules’ rating according to the table below.
WARNING !!! :
This is a product for restricted sales distribution to informed partners. Installation
restrictions or additional measures may be needed to prevent disturbances.
WARNING !!! :
External battery cables must be shielded.
NOTE
:
Output cables must be shorter than 10 meters.
Fixing metal piece.
(The second piece is on the opposite side.)
There are two metal pieces mounted for fixing
the output transformer during transportation.
Please, discard those two pieces during
installation of the UPS unit. (Figure 5-1)
Figure 5-1
H
L
X
1000
P
Figure 5-2
Installation Diagram
UPS
(KVA)
250-300
L
1565
P
920
H
1880
X (min)
1000
NOTE :
All the dimensions are in mm.