16 

 
 

2.9   COMMAND  Menu Items 

You can give immediate commands to ups by using this menu. 

 

Submenu items 

Function 

SOUND : ON/OFF 

Use for turn on/off beep alert sound. 
If you press ENTER key the option will change ,one press ON ,one press 
OFF. 
If the OFF option is used sound alert is turn off but if a new different 
alarm is valid UPS changes de option to ON state. 

ENTER B.TEST>432 

If you press enter for 3 seconds battery test starts for 15 seconds. 
If battery test failes 

A6 BATT FAULT

 message is on panel and this 

message stays until you press ENTER key for 3 seconds. 
Numbers at the right shows the battery voltage. 
Starting of battery test time is recorded to log event menu if the test is 
successful you can see only 

BATTERY TEST

 message on log records.. 

ENTER <BYPASS> 

If you press ENTER key for 3 seconds UPS transfers load to bypass. 
If the load is on bypass in this submenu you see 

ENTER<INVERTER> 

message at this position if you press ENTER key for 3 seconds UPS 
transfers the load on inverter. 
In parallel modes this function disables and you see 

BYP.FUNC.DISABLE 

message on this submenu item. 

ENTER:MODEM INIT 

If you press ENTER key the connected modem of RS232 port is installed 
UPS sends AT command set to modem for installation. 
If the function is completed you must hear a beep sound. 
At the and of this function modem is ready to answer dial up connection. 

ENTER <BOOST> 

If you press ENTER key for 3 seconds boost charge starts. The given 
time for boost charge is 10 hours. At the end of this time UPS stops the 
boost charge. 
If the boost charge is active this submenu item changes to 

STOP 

BOOST> 005H 

message the 005H shows that boost charge is started 

before 5 hours. 
If the number is 10 boost charge stops. If you press ENTER key bosst 
charge stops immediately. 
Boost charge starting and boost charge end time is recorded to log event 
menu. 
If boost is active UPS beeps in each 15 seconds 

SIMULATION OFF 

The purpose of this submenu to check dry contact connections. Normally 
to check line failure contact you must turn off mains power. This is not 
necessary with this utility. 3 options are avalible. 

SIMULATION OFF 

simulaion mode is off 

SIM:LINE FAILURE

 if you press ENTER key for 3 seconds line failure 

lamp on interface board lits 

SIM:LIN.F+BT.LOW

 if you press enter key for 3 seconds line failure and 

battery low lamp on interface board lits  

SIM:BYPASS

 if you press ENTER key for 3 seconds bypass (aux) lamp 

on interface board lits. 
So you can check the connections 

ENTER EXIT 

 

 Enter 

 

(

 )

 exit from submenu 

 

Goto first submenu item 

 

 
 
 
 
 
 
 
 
 

Содержание T-3250P

Страница 1: ...USER MANUAL T 300P SERIES T 3250P 250 kVA T 3300P 300 kVA...

Страница 2: ......

Страница 3: ...n 19 3 1 1 Security 19 3 1 2 Redundancy 19 3 1 3 Power Increment 19 3 2 Parallel Operation Modes 19 3 2 1 Symetric Parallel Mode 19 3 2 2 Redundant Parallel Mode 20 3 2 3 Hot Standby Mode 21 3 3 Paral...

Страница 4: ...SERVICE 34 6 1 Maintenance 34 6 2 Troubleshooting 34 6 3 Storage 34 VII REMOTE MONITORING AND CONTROL 35 7 1 Using Serial Port 35 7 2 Serial Communication Cable 35 7 3 Modem Connection 35 7 3 1 Hardwa...

Страница 5: ...e personnel The output may be energized when the unit is not connected to a mains supply Risk of electric shock hazardous live parts inside this unit are energized from the battery supply even when th...

Страница 6: ...e technology with pure sine wave output PWM and IGBT technology 3 Microprocessors at each UPS Microprocessor controlled main controller board Microprocessor controlled rectifier board Microprocessor c...

Страница 7: ...provides this voltage and frequency being fixed STATIC TRANSFER SWITCH STATIC BY PASS Two types of bypass circuitry is available for T 300P series UPS Full static switch for parallel systems Half sta...

Страница 8: ...chanical bypass circuit breaker the load is powered by the UPS Also during the normal operation battery charges This is made by the UPS s rectifier B Battery operation During this operation Inverter p...

Страница 9: ...rter Rectifier Static By Pass Static Transfer Switch Maintenance Bypass Mechanic transfer switch 3 Phase Line Input Battery group S3 S2 S1 S5 S4 3 Phase By Pass Supply Input Figure 1 2 UPS Split exter...

Страница 10: ...el System Analog Signals Socket DB15 Female optional Dry Relay Output Contacts Battery Circuit Breaker Input Emergency Stop Line Failure Relay Battery Low Relay By Pass Relay Figure 1 3 250 300 kVA Po...

Страница 11: ...N Voltage regulation tolerance 1 Nominal Output frequency 50 Hz Output frequency tolerance line syncron 2 Output frequency tolerance free running 0 2 Efficiency 100 Load 90 Load Crest Factor 3 1 Tota...

Страница 12: ...5 function keys on front panel these are ENTER UP DOWN PLUS and MINUS UP and DOWN keys help moving on menus PLUS and MINUS keys select options ENTER key means the selected option or menu is valid NOTE...

Страница 13: ...at this power range A16 BYP INPUT BAD During transfer to bypass Voltage or frequency value of bypass source is incorrect and the UPS turn off the load power During normal inverter operation some time...

Страница 14: ...PS STATUS at the upper line of LCD PANEL RECTIFIER START UPS started the rectifier INVERTER START UPS started the inverter MAINT SWITCH ON Maintenance bypass switch is on MANUEL BYPASS Load is transfe...

Страница 15: ...us CANCEL SHUTDOWN Shutdown command is canceled Only operating system or a PC computer can send this commands If the shutdown command is performed during line failure UPS shutdowns and is the mains is...

Страница 16: ...er of the UPS VERSION MC1XX Version of UPS FREQUENCY PLL XTAL Frequency generation mode ENTER EXIT Exit from submenu PASSWORD MENU password required System settings ENTER EXIT Exit from submenu SETTIN...

Страница 17: ...voltages 6 IPI 022 010 030 Input currents amperes 7 BATT 430 V 22 1 A Battery voltage and charge current 8 TEMP 030 c Cabinet inside temperature 9 CHARGE LEVEL 100 BATT CAPACI 068 Battery charge level...

Страница 18: ...on is valid 2 UPS No 001 By using PLUS and MINUS keys you can change number 0 to 3 In parallel operation select different number for each UPS If you select the same number DUBL UPS NUMBER message tell...

Страница 19: ...ort is installed UPS sends AT command set to modem for installation If the function is completed you must hear a beep sound At the and of this function modem is ready to answer dial up connection 5 EN...

Страница 20: ...8 ENTER UPDATE Enter update new date and time 9 ENTER EXIT Enter exit from submenu Goto first submenu item 2 11 PASSWORD Menu Items Only service personnel can use this menu the incorrect use of this m...

Страница 21: ...s to install one more UPS to the system 3 2 Parallel Operation Modes NOTE Parallel control board and some accessories are not installed to standart T 300P series UPS but parallel operation is availabl...

Страница 22: ...d power is higher than 1 UPS power but lower than the 1UPS 2UPS total power 3 2 4 Redundant Parallel Mode At this mode if one of the UPS failes the other UPS continues to feed load Assume that UPS1 on...

Страница 23: ...ILURE 20 Parallel Controller Board Failure A28 P FAILURE 21 Parallel Controller Board Failure A29 P TEST MODE Parallel control board is in test position A30 P FAILURE 23 Parallel Controller Board Fail...

Страница 24: ...allation it needs qualified sevice personnel You have to keep 80 cm distance between two UPS for service purposes The maximum length of digital and analog cable is 2 meters Add 20 tolerant to cables f...

Страница 25: ...ns will apply power to the load equipment 1 Open the UPS doors to gain access to the main power switches 2 Make sure that S3 switch maintenance bypass is in 0 OFF position 3 Turn on the S2 static by p...

Страница 26: ...Then turn off S1 inverter input S2 static bypass S4 UPS output switches and the battery circuit breaker into 0 position WARNING Inside the UPS the following points will carry hazardous voltages By pas...

Страница 27: ...rrupted the L6 inverter led continuously lit also L3 battery and on the LCD A10 LINE FAILURE message appears And also an audible alarm sounds Your UPS continues to convert the battery voltage to AC vo...

Страница 28: ...rton and the UPS 2 Carefully open the carton and take the UPS out 3 Retain the carton and packing material for future use Unit package contents User Manual Guarantee Certificate Battery cabinet and or...

Страница 29: ...es The input output cables can be sized to suit the modules rating according to the table below WARNING This is a product for restricted sales distribution to informed partners Installation restrictio...

Страница 30: ...27 Figure 5 3 250 300 kVA UPS Power Connections Split By Pass Connections Normal Connections A B A B...

Страница 31: ...esult in electric shock hazard to personnel or the risk of fire 5 4 2 Cable Connections ATTENTION All the cable connections of the ups must be done by the authorized service personnel Once the equipme...

Страница 32: ...29 U V W N LOAD AC INPUT 3 PHASE Neutral To be supplied by the customer Neutral Figure 5 4 POWER CONNECTIONS OF TWO UPS s FOR PARALLEL OPERATION 250kVA BATTERY GROUP BATTERY GROUP...

Страница 33: ...pped via the UPS control circuitry If the batteries are cabinet mounted this circuit breaker is fitted within the cabinet however if the batteries are rack mounted or otherwise located remote to the m...

Страница 34: ...31 Figure 5 5 UPS Battery Group Connection...

Страница 35: ...nections there must be a dedicated serial port ATTENTION The communication cables of this option must be shielded and must install away from the voltage cables The RS232 port at RS330 board and DB9 fe...

Страница 36: ...eople In case of a persistent failure or problem properly turn off the unit first Then review the following check list Be prepared to answer the questions before calling the service 1 Did you follow t...

Страница 37: ...put voltage after delay WAITING SHUTDOWN Turn off UPS output voltage SHUTDOWN and turn on UPS output voltage WAITING RESTART CANCEL SHUTDOWN RENAME UPS UPS will give response to these commands if the...

Страница 38: ...umber to which this is connected The dumb modem device connected to the UPS will answer the call and convert the data coming from UPS serial on the telephone line This way all measures and controls al...

Страница 39: ...CY STOP input ATTENTION Max 42VAC or 60VDC voltage should be applied to the dry contact outputs 7 6 Remote Monitoring Panel Remote monitoring panel can be used from 400 meters away from UPS Up to 25 m...

Страница 40: ...he product has been subjected to physical abuse improper installation unauthorized service or modification 2 The sole responsibility of corporation under this warranty shall be limited to the repair o...

Страница 41: ...38...

Страница 42: ...39 AGKK6221 02 2010...

Отзывы: