TES TES Series Скачать руководство пользователя страница 4

4

3

.

  PROVIDE COMBUSTION AND VENTILATION 

AIR. Local code provisions may apply and should be           

referenced.

WARNING

Adequate combustion and ventilation air must be 

provided to assure proper combustion.

A.  Determine volume of space (boiler room). Rooms 

communicating directly with the space in which the 

appliances are installed, through openings not 

furnished with doors, are considered a part of the 

space.

  Volume(ft

3

) = Length(ft) x Width(ft) x Height(ft)

B.  Determine total input of all appliances in the space.
  Add inputs of all appliances in the space and round 

the result to the nearest 1000 BTU per hour.

C.  Determine type of space. Divide Volume by total 

input of all appliances in space. If the result is 

greater than  or equal to 50 ft

3

/1000 BTU per hour, 

then it is considered an unconfined space. If the 

result is less than 50 ft

3

/1000 BTU per hour then the 

space is considered a confined space. 

D.  For boiler located in an unconfined space of a 

conventionally constructed building, the fresh air 

infiltration through cracks around windows and 

doors normally provides adequate air for combus-

tion and ventilation.

E.  For boiler located in a confined space or an uncon

-

fined space in a building of unusually tight con

-

struction, provide outdoor air with the use of two 

permanent openings which communicate directly or 

by duct with the outdoors or spaces (crawl or attic) 

freely communicating with the outdoors. Locate 

one opening within 12 inches of top of space. 

Locate remaining opening within 12 inches of 

bottom of space. Minimum dimension of air 

opening is 3 inches.  Size each opening per 

following:

(1) 

Direct communication with outdoors.

 

Minimum free area of 1 square inch per 4,000 

BTU per hour input of all equipment in space.

(2) 

  Vertical ducts.

 Minimum free area of 1 square 

inch per 4,000 BTU per hour input of all 

equipment in space.  Duct cross-sectional area 

shall be same as opening free area.

(3) 

  Horizontal ducts.

 Minimum free area of 1 

square inch per 2,000 BTU per hour input of all 

equipment in space. Duct cross-sectional area 

shall be same as opening free area.

  Alternate method for boiler located within 

confined space.

 Use indoor air if two perma-

nent openings communicate directly with 

additional space(s) of sufficient volume such 

that combined volume of all spaces meet 

criteria for unconfined space. Size each 

opening for minimum free area of 1 square 

inch per 1,000 BTU per hour input of all 

equipment  in spaces, but not less than 100 

square inches.

F.  Louvers and Grilles of Ventilation Ducts

(1)   All outside openings should be screened and 

louvered. Screens used should not be smaller 

than 1/4 inch mesh. Louvers will prevent the 

entrance of rain and snow.

(2)   Free area requirements need to consider the 

blocking effect of louvers, grilles, or screens 

protecting the openings. If the free area of the 

louver or grille is not known, assume wood 

louvers have 20-25 percent free area and metal 

louvers and grilles have 60-75 percent free 

area.

(3)   Louvers and grilles must be fixed in the open 

position, or interlocked with the equipment to 

open automatically during equipment opera-

tion.

Figure 2:  Minimum Installation Clearances To 

Combustible Materials

NOTE 1:  Listed clearances comply with American 

 

 

   National Standard ANSI/NFPA 31,  

 

 

   Installation of oil burning equipment.

NOTE 2:  TES Series boilers can be installed in rooms 

 

 

   with clearances from combustible material as  

 

   listed above. Listed clearances can not be  

 

   reduced for alcove or closet installations.

NOTE 3:  For reduced clearances to combustible  

 

   material, protection must be provided as  

 

   described in the above ANSI/NFPA 31   

 

   standard.

Содержание TES Series

Страница 1: ...r t n o c g n i t a e h r u o y l l a c r e l i o b o t s r i a p e r r o e c i v r e s r o F l e b a L g n i t a R n o n w o h s s a r e b m u N l a i r e S d n a r e b m u N l e d o M r e l i o B e d i v o r p r e b m u N l e d o M r e l i o B r e b m u N l a i r e S r e l i o B e t a D n o i t a l l a t s n I r o t c a r t n o C g n i t a e H r e b m u N e n o h P s s e r d d A GASgGASAS GAS OI...

Страница 2: ...AUSE INJURY OR LOSS OF LIFE TO VENT SAFELY AND WILL CONTRIBUTE TOWARD MAINTAINING THE BOILER S EFFICIENCY 6 READ THE LITERATURE ENCLOSED BY THE MANUFACTURER WITH THE VARIOUS ACCESSORY DEVICES THESE ACCESSORY DEVICES MUST BE INSTALLED AND USED ACCORDING TO THE RECOMMENDATIONS OF THE MANUFACTURER 7 IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO SEE THAT ALL CONTROLS ARE CORRECTLY INSTALLED...

Страница 3: ... final position before removing crate See Figure 1 A LOCATE so that smoke pipe connection to chimney will be short and direct BOILER IS SUITABLE FOR INSTALLATION ON COMBUSTIBLE FLOOR Boiler can not be installed on carpeting B FOR BASEMENT INSTALLATION provide a solid base such as concrete if floor is not level or if water may be encountered on floor around Boiler C PROVIDE SERVICE CLEARANCE of at ...

Страница 4: ...ut of all equipment in space 2 Vertical ducts Minimum free area of 1 square inch per 4 000 BTU per hour input of all equipment in space Duct cross sectional area shall be same as opening free area 3 Horizontal ducts Minimum free area of 1 square inch per 2 000 BTU per hour input of all equipment in space Duct cross sectional area shall be same as opening free area Alternate method for boiler locat...

Страница 5: ...t rear legs down on floor Tilt boiler backward pull skid forward and set front legs down on edge of skid Install close coupling tee and plug in return coupling see Step 7 and Figure 1 Point tee toward permanent return location B Tilt boiler backward and remove skid Be careful not to damage Burner and Jacket 3 CHANGE HINGE POSITION if necessary Figure 4 Recommended Water Piping for Zone Valve Zoned...

Страница 6: ... Figure 5 Recommended Water Piping for Circulator Zoned Heating Systems ...

Страница 7: ...OMBUSTION CHAMBER LINER A OPEN SWING DOOR on front of boiler Use flashlight to inspect insulation pieces secured to front and rear doors Inspect Ceramic Fiber Blanket secured to bottom of combustion chamber with water glass adhesive Replace any damaged pieces 7 CONNECT SUPPLY AND RETURN PIPING TO HEATING SYSTEM A Hot water pipes shall have clearances of at least from all combustible construction B...

Страница 8: ...he breeching are not recommended 9 INSTALL ELECTRIC WIRING A Follow the National Electrical Code and local regulations A separate electrical circuit must be run from the main electrical service with an over current device disconnect in the circuit A service switch is recommended and may be required by some local jurisdictions Wiring should conform to Figures 11A 11B and 11C B CANADA Refer to CSA s...

Страница 9: ...o not use compression fittings Open the air bleed valve and start the burner For clean bleed slip a 3 16 ID hose over the end of the bleed valve and bleed into a container Continue to bleed for 15 seconds after oil is free of air bubbles Stop burner and close valve Lift H Maximum Length of Tubing H R 3 8 OD Tubing 3 GPH 1 2 OD Tubing 3 GPH 0 84 100 1 78 100 2 73 100 3 68 100 4 63 100 5 57 100 6 52...

Страница 10: ...Wiring Diagram for TES Boiler Control Panel 10 ...

Страница 11: ...icate if oil lubricated Most motors currently used on residential type burners employ permanently lubricated bearings and thus do not require any field lubrication Water lubricated circulators do not need field lubrication Do not over lubricate This can cause as much trouble as no lubrication at all 5 ADJUST CONTROLS SETTINGS with burner service switch turned ON WARNING All boilers equipped with b...

Страница 12: ...ng sleeved loose fitting clothing 3 Gloves 4 Eye Protection Take steps to assure adequate ventilation Wash all exposed body areas gently with soap and water after contact Wash work clothes separately from other laundry and rinse washing machine after use to avoid contaminating other clothes Discard used RCF components by sealing in an airtight plastic bag RCF and crystalline silica are not classif...

Страница 13: ...rating and Service Instructions Items 1 through 8 There are various test kits available to trace air leaks such as electronic sight glasses Follow the manufacturers instructions to find air leaks The following actions can eliminate air leaks 1 Bleed pump as detailed previously 2 Replace flare fittings 3 Replace oil supply line 4 Repair oil filter leaks 5 Replace or repair tank fittings NOTICE CHEC...

Страница 14: ...OSE BOILER CAUTION Do not start burner unless burner swing door is securely closed Close door install hex nuts and tighten securely Door should be parallel to tubesheet when viewed from top and sides Reconnect two halves of Swing Door Interlock WARNING The boiler must be connected to an approved chimney in good condition Serious property damage could result if the boiler is connected to a dirty or...

Страница 15: ...6 SERVICE RECORD DATE SERVICE PERFORMED 1 ...

Отзывы: