TMS-UT-0416-T01-0
Page 15
5.4.2. Access to special service menu
>10 sec
>15 sec
>20 sec
>15 sec
15
15
2
15
>5 sec
>25 sec
>30 sec
Power
ON
>5 sec
>5 sec
>5 sec
45
3
1
.
>5 sec
>5 sec
>5 sec
>5 sec
>5 sec
Press simultaneously to access service menu
Access to special service menu
To access in special service menu, press simultaneously
key (6) during switching ON main switch on boiler - RCCB
(in that moment key (7)
must
be turned off)
Limiting maximum boiler temperature
By pressing the key (6) user can limit maximum boiler
temperature.
Factory defined maximum temperature starts to blink. By
pressing up or down user can set new maximum
temperature. If the key is depressed for more than 5s,
value on the display will be memorized and becomes
active.
Radiator heating: Adjustment range 60°C-90°C, factory
default 80°C
Underfloor heating: Adjustment ran
ge 30°C-50°C,
factory default 80
°C
Setting the minimal boiler temperature
By pressing the key (6) user can set minimal boiler
temperature.
Minimal boiler temperature starts blinking.
By pressing the key user can select the desired minimal
boiler temperature. Temperature changes in st
eps of 1°C.
If the key is depressed for more than 5s, value on the
display will be memorized and becomes active.
Radiator heating: Adjustment range 20°C-45°C, factory
default 45°C
Underfloor heating: Adjustment range 15°C-30°C,
factory default 30°C
Setting the heating pump delay
By pressing key (6) user can change pump delay time
between 0 - 15 min. Factory settings is 2.
Selecting the time delay between steps for
power regulation
By pressing the key (6) user can change the time delay
between step for power regulation in the range from 5 to 60
seconds. Default value depends on the number of stages
for power regulation
– each stage will add 5 seconds. 3
stages will have 3*5=15 seconds between successive
stages turn-on. Turn of delay is fixed to 1 second.
Selecting the number of steps for power
regulation
By pressing the key (6) servicer can change the number of
steps for power regulation.
By pressing the key it is possible to select 1 to 3 steps for
power regulation. Default settings
:
3 power levels. Change
in the number of stages will cause time delay parameter to
be changed (see above) !
Selecting the number of pumps for controlling
By pressing the key (6) servicer can change the number of
pumps, one or two
–
only for option control panel
“Z“