5.4.2. Access to special service menu 

 

>10 sec

>15 sec

>20 sec

>15 sec

15

15

2

15

>5 sec

>25 sec

>30 sec

Power

ON

>5 sec

>5 sec

>5 sec

45

  3

1

.

>5 sec

>5 sec

>5 sec

>5 sec

>5 sec

Press simultaneously to access service menu

 

 
 
Access to special service menu 

 

To access in special service menu, press simultaneously 
key (6) during switching ON main switch on boiler - RCCB 
(in that moment key (7) 

must

 be turned off) 

 

Limiting maximum boiler temperature

 

By  pressing  the  key  (6)  user  can  limit  maximum  boiler 
temperature. 

Factory  defined  maximum  temperature  starts  to  blink.  By 
pressing  up  or  down  user  can  set  new  maximum 
temperature.  If  the  key  is  depressed  for  more  than  5s, 
value  on  the  display  will  be  memorized  and  becomes 
active. 

Radiator heating: Adjustment range 60°C-90°C, factory 
default 80°C 

Underfloor  heating:  Adjustment  ran

ge  30°C-50°C, 

factory default 80

°C  

Setting the minimal boiler temperature 

By  pressing  the  key  (6)  user  can  set  minimal  boiler 
temperature. 

Minimal boiler temperature starts blinking. 

By  pressing  the  key  user  can  select  the  desired  minimal 
boiler  temperature.  Temperature  changes  in st

eps of 1°C. 

If  the  key  is  depressed  for  more  than  5s,  value  on  the 
display will be memorized and becomes active. 

Radiator heating: Adjustment range 20°C-45°C, factory 
default 45°C 
Underfloor  heating:  Adjustment  range  15°C-30°C, 
factory default 30°C 

Setting the heating pump delay 

By pressing key (6) user can change pump delay time 
between 0 - 15 min. Factory settings is 2. 
 

Selecting the time delay between steps for 
power regulation 

By  pressing  the  key  (6)  user  can  change  the  time  delay 
between step for power regulation in the range from 5 to 60 
seconds.  Default  value  depends  on  the  number  of  stages 
for  power  regulation 

–  each  stage  will  add  5  seconds.  3 

stages  will  have  3*5=15  seconds  between  successive 
stages turn-on. Turn of delay is fixed to 1 second. 

 

Selecting the number of steps for power 
regulation 

By pressing the key (6) servicer can change the number of 
steps for power regulation. 

By pressing the key it is possible to select  1 to 3 steps for 
power regulation. Default settings

:

 3 power levels. Change 

in the number of stages will cause time delay parameter to 
be changed (see above) !  

 

Selecting the number of pumps for controlling 

By pressing the key (6) servicer can change the number of 
pumps, one or two 

– 

only for option control panel 

“Z“

 

 

Содержание TermoMini

Страница 1: ...ELECTRIC BOILERS FOR CENTRAL HEATING TermoMini Installation manual User guide ...

Страница 2: ... 7 3 4 5 Pressure gauge 7 3 4 6 Expansion vessel 7 3 4 7 Circulating pump 7 3 4 8 Air in boiler 7 4 Boiler installation sequence 8 4 1 Transporting the appliance 8 4 2 Select position for boiler 8 4 3 Fitting the boiler hanging bracket 8 4 4 Removing fixing the front and top case 9 4 5 Power supply connection 9 4 6 Connecting temperature sensors or external electrical controls 10 4 6 1 Accessing c...

Страница 3: ...se 9 Figure 8 Power supply connection 9 Figure 9 Connection relay plate 10 Figure 10 Pump NMT PLUS 25 40 11 Figure 11 Pump characteristics 12 Figure 12 Standard electronic control panel 12 Figure 13 Control panel W OPTION 16 Figure 14 Hydraulic sketch for TermoMini with OPTION control panel type Z 16 Tables Table 1 Expansion vessel characteristics 3 Table 2 Power supply characteristics 3 Table 3 L...

Страница 4: ...ufacturer Switch off main power by MCB before opening the boiler Boiler has built in frost protection When the boiler is not in use leave the main power active that protection stay active 1 Introduction Thank you for the confidence you have shown to us by purchasing our central heating boiler In order to use the boiler to the utmost correctly and safely and above all economically read thoroughly t...

Страница 5: ...d heating smaller water quantities so that exploiting energy is already 100 TermoMini boilers are used for radiator and floor heating Temperature operation area is from 20 C to 90 C TermoMini boilers are designed in such way that in apartment contained central heating they can fit well with your furniture 1 4 Frost protection The software in control panel provides boiler frost protection When fros...

Страница 6: ...f Water in the System L 86 Table 2 Power supply characteristics Power kW 230 V N 400V 3N 50 60 Hz 3 4 5 6 9 9 12 Nominal current A 13 19 6 26 1 39 2 13 1 17 5 Fuse current A 16 25 32 50 16 25 Rated short circuit breaking capacity Icn EN 60898 kA 10 10 10 10 10 10 Rated short circuit breaking capacity Icn IEC 947 2 kA 15 15 15 15 15 15 Min conductor s cross section mm2 3x2 5 3X4 3X6 3X10 5X2 5 5x4 ...

Страница 7: ...elements 1 Primary flow 10 Expansion vessel 2 Return flow 11 Circulation pump 3 External boiler shell 12 Pressure relief valve 0 3 MPa 3 bar 4 Boiler 13 Automatic air vent 5 Heat insulation 14 Charge and discharge valve 6 Electrical heaters 16 Air indicator 7 Control panel 17 Manifold 8 Inducers for el connections 9 RCCB switch and relays ...

Страница 8: ...unction during wintertime there is a danger of installation freeze In this case boiler should be filled with antifreeze liquid for central heating If this is not possible water should be drained out of the system with the help of charge and discharge valve Recommended pressure of central heating installation is between 0 12 MPa 1 2 bar and 0 15 MPa 1 5 bar maximum pressure is 0 25 MPa 2 5 bar 3 3 ...

Страница 9: ...e to the fixing wiring the means for disconnection MCB must be incorporated in fixed wiring in accordance with the local wiring rules RCCB RCD switch 0 03A sensitivity is fitted inside a boiler Note In some cases additional measures must be taken subject to the requirements of the Local Authorities 3 4 System requirements 3 4 1 Pipe work Pipe work that is not a forming part of the useful heating s...

Страница 10: ... provided with the boiler This safety device is required on all sealed heating systems and is preset at 0 3 MPa 3 bar The pressure relief valve must not be used for draining purposes 3 4 5 Pressure gauge This is factory fitted to the TERMO Mini boilers and indicates the primary circuit pressure to facilitate filling and testing 3 4 6 Expansion vessel TermoMini boiler incorporate an expansion vesse...

Страница 11: ...at stable balance is achieved and lift upwards to drop into place onto bracket Ensure coordinated movements during a two person lift to ensure equal spread of weight of load it is recommended to wear suitable cut resistant gloves with good grip to protect against sharp edges and ensure good grip when handling appliance 4 2 Select position for boiler Refer to chapter 3 3 1 for information regarding...

Страница 12: ...he front and top case Figure 7 Removing front and top case Grasp the front case by its sides pull it towards the front and remove it by lifting it of the unit push top cover towards back and lift it of the unit 4 5 Power supply connection Note Before working with the appliance turn off the power supply MCB and secure against restart This device must be earthed Tightening torque for RCCB is 2 5 Nm ...

Страница 13: ...r the heating system to operate properly the indicator of manometer must be between 1 2 and 1 5 bar when the system is cold It is very important to use soft water or fluids for central heating 5 Commissioning 5 1 Heating system check Check for pressure in the system it should be from 0 12 MPa 1 2 bar to 0 15 MPa 1 5 bar when the system is cold Vent all heating elements and installation 5 2 Prelimi...

Страница 14: ...ryl Pump casing is made of grey cast iron Embodiment of the casing is single made Figure 10 Pump NMT 25 40 Table 5 Pump electric and performance information Table 6 Pump general information Max flow Qmax m3 h 2 6 Medium temperature C 5 95 Max height Hmax m 4 Ambient temperature C 0 40 Default pressure bar 10 Recommended system pressure at 50 80 110 C bar 0 05 0 4 1 1 Power W 5 25 Current A 0 05 0 ...

Страница 15: ...TMS UT 0416 T01 0 Page 12 Figure 11 Pump characteristics 5 4 Working with standard control panel Figure 12 Standard electronic control panel ...

Страница 16: ...e boiler the signalization of air in the boiler LU is shown on display 2 and the boiler stops the operation In this way the boiler is protected against burning through because of appearance of air To continue the operation the boiler should be vented If the boiler is correctly vented the operation of boiler continues automatically Voltage drop SP If the voltage in the network line drops below 180V...

Страница 17: ... can enter the boiler temperature menu The desired boiler temperature is blinking By pressing the key 6 UP or DOWN the desired boiler temperature can be set in steps of 1 C If the key is held pressed less than 5 s the value from the display becomes the desired boiler temperature Possible adjustment is from 20 C up to 90 C for radiator heating Possible adjustment is from 15 C up to 45 C for under f...

Страница 18: ... temperature Temperature changes in steps of 1 C If the key is depressed for more than 5s value on the display will be memorized and becomes active Radiator heating Adjustment range 20 C 45 C factory default 45 C Underfloor heating Adjustment range 15 C 30 C factory default 30 C Setting the heating pump delay By pressing key 6 user can change pump delay time between 0 15 min Factory settings is 2 ...

Страница 19: ...degree of heaters 1 2 3 3 Signalization of air appearance in the boiler red light 4 Signalization of under voltage protection red light 5 Signalization of boiler operation green light 6 Adjustment of temperature in boiler 7 Switch for central heating switching on and off 8 Sanitary water temperature adjustment 9 Switch for switching on and off the sanitary water preparation 10 Signalization of san...

Страница 20: ...e recommend this test once or twice in heating season Safety valve should be checked once a year before the beginning of heating season to ensure proper functioning and avoiding appearance of water calculus If the boiler is not connected to the room thermostat or if the boiler is out of function during the winter time there is a danger of installation freezing In this case the system should be fil...

Страница 21: ...g installation prevents circulation vent installation boiler does not provide enough heat one phase is missing on supply a part of heater is burned through in a three phase system the three different phases are not brought to the boiler check fuses on the main panel contact authorized service personnel to resolve the problem the switcher can be heard while operating it buzzes radio and TV interfer...

Страница 22: ...19 RCCB switch cannot be reset safety thermostat is activated pre reset safety thermostat and then the RCCB switch contact authorized service personnel to resolve the exact source of the problem Table 7 Possible malfunctions ...

Отзывы: