7
www.termoakim.com
WARNING: The values given were calculated for a
maximum length of 20 m cable to be pulled.
Power Of The
Device (kw)
Operating
Voltage (V)
Fuse Amperes
(A)
Cable Cross
Section (mm
2
)
Grounding Cross
Section (mm
2
)
6
230/400
1x32/3x10
2x4/4x2,5
2,5
8
230/400
1x40/3x16
2x6/4x2,5
4/2,5
10
230/400
1x50/3x16
2x6/4x2,5
2/2,5
12
230/400
1x63/3x20
2x10/4x4
6/4
14
230/400
1x63/3x25
2x10/4x4
6/4
ELECTRICAL CONNECTION OF THE DEVICE
• Termoakım Galaxi Pro 6-8-10-12-14 kw models are designed to
work both monophase and triphase.
• The supply cable to be pulled into the device must comply with
TSE (Turkish Standards Institute) norms.
• Electrical connections of the device should only be made by au-
thorized electricians.
• The cable to be drawn to the device must be pulled from the
main network panel. The cable to be pulled must be in one piece
with no attachment.
• The cable section to be cut into the device, the leakage current
relay ampere and the ground cable section must comply with the
standards specified in the chart.
• The tightness of the fuse and terminal connections should be
checked periodically every year.
WARNING
It is the customer’s responsibility to comply with the schedule,
to install the cable section, leakage current relay and to con-
nect the ground line to the specified standards.