71M6403
Electronic Trip Unit
SEPTEMBER 2006
Page: 62 of 75
©
2006 TERIDIAN Semiconductor Corporation
REV 1.0
CE Calibration Parameters
The table below lists the parameters that are typically entered to effect calibration of circuit breaker accuracy.
CE
Address
Name
Default
Description
0x08
CAL_I0
16384
0x09
CAL_I1
16384
0x0A
CAL_I2
16384
0x0B
CAL_I3
16384
0x0C
CAL_I4
16384
0x0D
CAL_I5
16384
These six constants control the gain of their respective channels. The nominal
value for each parameter is 2
14
= 16384. The gain of each channel is directly
proportional to its calibration parameter. Thus, if the gain of a channel is 1%
slow, CAL should be increased by 1%.