5.2.3 Tests Using OCR Checker (type ANS1)
The ANS1 type OCR checker is used to check for instantaneous trip function.
Two or more ACB’s cannot be tested using the OCR checker at the same time.
Caution
OCR field tests must be performed by competent persons.
Never touch the live terminal parts.
Otherwise, electric shock may result.
Fig. 15
OCR Checker Connection Diagram
Before performing the tests:
Apply the rated voltage between auxiliary circuit terminals U
1
and U
2
when the ACB is equipped
with the UVT.
How to test the OCR:
①
Stop the generator and open a disconnector or the like to isolate all sources of power/voltage
from both the primary and auxiliary circuits.
②
Connect the OCR checker power terminals (
l
and
k
)
to the OCR test terminals
l
and ka for
R-phase test,
l
and kb for S-phase test, and
l
and kc for T-phase test.
③
Close the ACB.
④
Supply power (100 - 110 VAC, 50/60 Hz, 3 VA) to OCR checker terminals P
0
and P
1
and turn
on the power switch.
⑤
Wait three seconds after turning on the power switch, press the test button to check if the ACB
trips instantaneously.
⑥
After completion of the test, turn off the power switch and return the ACB to the original state.
If the tests show any problem, contact our branch office or your local agency.
OCR test terminal
ACB
(Optional)
(not supplied)
Power switch
ANS1 OCR
checker
Test button