3.3.4 Motor Operator
The motor operator (optional) permits the ACB to be electrically closed, opened (reset) from a
remote position.
1) Connection
Remove the terminal cover (transparent) and connect the operating switch control wire and the
power supply wire to the control circuit terminals as follows:
Fig. 6
Motor Operator Connection Diagram
Caution : Be sure to replace the terminal cover (transparent) after connecting the wires.
Caution : Motor operator XMD4M is hinged type. Sag the wire so that the motor operator can
be uplifted as shown in Fig. 7. For removing the motor operator, see the
XMD Series Motor
Operator - Operating Instructions.
Fig. 7
XMD4M (hinged type)
2) Ratings
The following table shows the operating current at the maximum rated voltage.
The accessory nameplate indicates the steady-state current. For the operating switch ratings
and power capacity refer to the starting current.
Operating Current
Rated current
(at 50/60 Hz)
Operation
Steady-state current (A)/Starting current (A, peak)
XMD4M
XMD6M
XMD9M
100 - 115 VAC
Close (ON)
-/3.1
-/3.1
-/3.1
Open(OFF)/Reset
1.2/5.7
1.8/6.0
1.8/6.0
200 - 230 VAC
Close (ON)
-/1.2
-/1.2
-/1.2
Open(OFF)/Reset
0.7/3.0
1.0/3.2
1.0/3.2
Motor operator
ON switch
OFF/RESET
switch
Power
Supply
On
Off
MP1
MP2
E
XMD4M
Control circuit terminal
Hinge
ACB