![Teracom TCW280 Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/teracom/tcw280/tcw280_user-manual_1088221005.webp)
TCW280_R1.2 – February 2019
Page 5
Inputs and outputs locations are shown below:
Connector 1
Ethernet - RJ45
Connector 5
Pin1 – Relay1-NC
Connector 2
Power - 2.1x5.5mm connector
(central positive)
Pin2 – Relay1-COM
Pin3 – Relay1-NO
Connector 3
Pin1 – Power positive
Connector 6
Pin1 – Relay2-NC
Pin2 – Power negative (GND)
Pin2 – Relay2-COM
Connector 4
Pin1 – Open drain OUT4
Pin3 – Relay2-NO
Pin2 – SGND
Connector 7
Pin1 – IOUT1
Pin3 – Open drain OUT3
Pin2 – SGND
Pin4 – Open drain OUT2
Pin3 – VOUT1
Pin5 – SGND
Connector 8
Pin1 – IOUT2
Pin6 – Open drain OUT1
Pin2 – SGND
Pin3 – VOUT2
5.3.1.
Power supply connection
TCW280 is designed to be supplied by adapter SYS1308-2412-W2E or similar, intended for use in
the conditions of overvoltage category II. The power supply equipment shall be resistant to short
circuit and overload in a secondary circuit.
When in use, do not position the equipment so that it is difficult to disconnect the device from the
power supply.
5.3.2.
Analog outputs
TCW280 has two isolated analog channels. Every channel can be programmed to work either in
voltage or current loop mode. In the voltage mode, two ranges are supported - 0 to 5 and 0 to 10
volts. In the current loop mode, three ranges are supported – 0 to 20, 4 to 20, and 0 to 24 mA. In
the current loop mode, there is an alarm notification for open loop.
Voltage and current loop outputs are single-ended and are assigned to different connectors. Using
the selected mode requires connecting to the appropriate connector.