TCW242-S_R1.0 – July 2021
Page 14
8.2.2.3.
Sensor setup tool
The device has also a simple but useful tool for configuration and control of MODBUS RTU
sensors. It can change the addresses and communication parameters of sensors from
different manufacturers.
8.2.3.
Input/Output
This page is used for the parameterization of relays, analog, and digital inputs.
8.2.3.1.
Analog inputs
TCW242-S has 4 analog inputs. All they are isolated from the power supply but use the same
ground. Every analog input can work in voltage (0-10V) or current loop mode (0-20mA).
For every analog input Multiplier and Offset can be set. They work as follows:
Value = (Raw_Value * Multiplier) + Offset.
If you want to see the raw value of the sensor/register set Multiplier=1 and Offset=0.
By default and after “Factory default settings” procedure: Multiplier=1.00, Offset=0.00 and
Mode=0-10V