TCW122B-RR_R2.4 -March 2019
Page 5
8.3.2.
Server settings
This part can be set up if the Server mode is chosen.
•
Port
– Port on which the “Server” listens for requests from the “Client”;
•
Client ID
– by default is “00-00-00-00-00-00”. In this case, there is no device ID filtering.
If extra filtering is needed the value of “Device ID” field of “Client” should be filled in
here.
8.3.3.
Client settings
This part can be set up if the Client mode is chosen.
•
Mode
– “Single-server” or “Multi-servers”.
In Single-server mode one “Client” communicates with one “Server”. The status of
Client’s digital inputs manages corresponding relays of the “Server”.
In Multi-servers mode one “Client” communicates with up to 6 “Servers”. The status
of Client’s digital inputs manages corresponding relays of the all “Servers”. Only the
status of digital inputs of “Server1” manages corresponding relays of the “Client”.
•
Server IP : Port
– network settings of Server. It is mandatory that port here should be
the same like in field “Port” on “Server” device;
•
Connection interval
– time in seconds in which the “Client” sends a request to Server.
In case of input activation, the “Client” sends the request immediately, doesn’t matter
how many seconds are passed from the previous regular request. This guarantee
immediate response of the system. In the example the “Client” sends requests on
every 20 seconds;
•
Keep alive attempt
– a number of sequential request (on connection interval) after
which the connection is considered not alive. In the example, if no answer from server
in 100 seconds (5 attempts x 20 seconds) connection will consider broken.
8.3.4.
General settings
Descriptions and refresh interval for monitoring page can be set here.
Automatic monitoring page refresh interval can be set from 1 to 253 second. If 0 is chosen -
no automatic refresh. In the example, the monitoring page will be refreshed every second.