Authentication details for WEB access to TCW112-CM can be set in the last section. Only one
user is supported.
7.4
I/O setup page
For temperature, humidity and analog voltage - MIN, MAX, and HYSTERESIS values can be set.
These values arranged windows for monitored parameter.
When the measured value goes out of range SNMP trap or e-mail (if enabled) will be sent.
Leaving range is considered when the parameter goes lower than MIN values or higher than
MAX. Coming back in the range is considered when the parameter goes higher than (MIN +
HYSTERESIS) or lower than (MAX – HYSTERESIS).