![Teracom TCW112-CM Скачать руководство пользователя страница 3](http://html1.mh-extra.com/html/teracom/tcw112-cm/tcw112-cm_user-manual_1088239003.webp)
TCW112-CM-R3.2 - March 2018
Page 2
Sampling rate: 10mS
Digital filtering time interval: 30mS
Analog input
Isolation: Non isolated
Type: Single ended
Resolution: 10 bits
Mode: Voltage
Input Range: 0 to 60 VDC
Accuracy: ±1%
Sampling Rate: 37.6mS per channel (averaged value of 64 samples)
Input Impedance: 1 mega-ohms (min.)
Supply voltage for analog sensor (+VA): 5.0 ± 0.1
Maximum output current for analog sensor (+VA): 0.1A
Relay output
Type: Form C (N.O. and N.C. contacts)
Contact current rating: 3 A @ 24 VDC/30 VAC (resistive load)
Initial insulation resistance: 100 mega-ohms (min.) @ 500 VDC
Mechanical endurance: 10 000 000 operations
Electrical endurance: 100 000 operations @ 3 A resistive load
Contact resistance: 50 milli-ohms max. (initial value)
Minimum pulse output: 1 Hz at rated load
1-Wire interface
Output voltage (+VW): 5.3 ± 0.2 VDC
Maximum output current (+VW): 0.2 A
Internal FLASH memory
Endurance: 100 000 cycles (Every relay status and settings change is a memory cycle.)