TM-601N/603/604
EN-7
and the red lamp goes ON when it turns
counterclockwise, this suggests the
wiring of L1, L2 and L3 is normal. (In this
case, skip to step 8.) If the red lamp goes
ON when the motor turns clockwise, and
the green lamp goes ON when it turns
counterclockwise, this indicates the
wiring sequence must be corrected. Go
to step 6.
Exchange L1 and L3. If the green lamp
goes ON when the motor turns clockwise,
and the red lamp goes ON when it turns
counterclockwise, skip to step 8. If the
red lamp goes ON when the motor turns
clockwise, and the green lamp goes ON
when it turns counterclockwise, this
indicates the wiring sequence must be
corrected. Go to step 7.
Exchange L1 and L2. If the green lamp
goes ON when the motor turns clockwise,
and the red lamp goes ON when it turns
counterclockwise, this suggests the
wiring of L1, L2 and L3 is normal. (In this
case, skip to step 8.)