PTK Series Polyethylene Pump Tank Station with Checkmate Control System
Page: 18
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Email: [email protected]
F.
Alarm system operation
1.
The audible / visual alarm system is an optional component. If installed, there is a
visual and audible alarm beacon mounted on the control cabinet (typical).
2.
Low pump pressure... the ‘to process’ pressure falls below the pressure switch
setting. The default is 40 PSI to open the contacts and 20 PSI to close the
contacts and trigger the alarm).
Causes of low pump pressure are: pump not operating due to tripped
overloads; impeller damaged or some internal pump obstruction; excessive
gpm.
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
Setpoints
Config 1
Delays
Communication
System Config
SEL
SYSTEM CONFIG
ADRESS
1
RATE
1
COMMUNICATION
PRESSURE
15
LEVEL
4
DELAYS
OUTPUT 1 PUMP
CONFIGURE 1
OUTPUT 2 FAN
OUTPUT 3 FAN
OUTPUT 4
OUTPUT 5
OUTPUT 6
PROCESS
84
ALT SP
40
HI ALARM
20
LO ALARM
20
SETPOINTS
PRESS
TO ENTER
SETUP ACCESS
PROCESS
STATUS
84
94
TO FROM
TOWER
94
84
PUMP 1
PROCESS PUMPS
ON
17
PUMP 2
OFF 13
1 PUMP
OUTPUTS
ON
17
2 FAN
ON
17
3 FAN
ON
17
4
ON
17
5
ON
17
6
ON
17
84
SETPOINT
84
°F
RANGE 1 to 99
TYPE
1
1 - PTS
2 - CPTS