10
A180031
Fig. 20
−
Removing Control Box Cover
3. Disconnect the blower motor white power plug and green
and wire speed tap wires, noting connection locations. (See
Fig. 21)
A180032
Fig. 21
−
Disconnect the Blower Motor
4. Loosen the conduit holding ties. (See Fig. 22)
A180033
Fig. 22
−
Loosen the Conduit Ties
5. Remove the two middle screws above/behind the blower
motor that’s attached to the top plate.
6. Remove the two outer screws that attach the blower support
plate to right evaporator coil support. (See Fig. 23)
A180034
Fig. 23
−
Remove Outer Screws from Support Plate
7. Remove the top and middle screw of the refrigerant tubing
holding bracket. (See Fig. 24)
A180035
Fig. 24
−
Remove Top and Middle Screw
8. Bend the holding bracket to release from around the tubing.
A180036
Fig. 25
−
Remove Two Outer Screws