5
441 01 2101 05
Specifications are subject to change without notice.
Step 3 — Combustion and Ventilation Air
Section 9.3 of the NFGC, NFPA 54/ ANSI Z223.1
−
2012 Air
for Combustion and Ventilation
Step 4 — Duct Systems
Air Conditioning Contractors Association (ACCA) Manual D,
Sheet Metal and Air Conditioning Contractors National
Association (SMACNA), or American Society of Heating,
Refrigeration, and Air Conditioning Engineers (ASHRAE)
2001 Fundamentals Handbook Chapter 34 or 2000 HVAC
Systems and Equipment Handbook Chapters 9 and 16.
Step 5 — Acoustical Lining and Fibrous Glass
Duct
Current edition of SMACNA and NFPA 90B as tested by UL
Standard 181 for Class I Rigid Air Ducts
Step 6 — Gas Piping and Gas Pipe Pressure
Testing
NFPA 54 / ANSI Z223.1
−
2012; chapters 5, 6, 7, and 8 and
National Plumbing Codes
Step 7 — Electrical Connections
National Electrical Code (NEC) NFPA 70
−
2011
Step 8 — Venting
NFGC; NFPA 54 / ANSI Z223.1
−
2012 chapters 12 and 13
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS PROCEDURE
1. Disconnect all power to the furnace. Multiple
disconnects may be required. DO NOT TOUCH THE
CONTROL OR ANY WIRE CONNECTED TO THE
CONTROL PRIOR TO DISCHARGING YOUR BODY’S
ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch the clean, unpainted, metal surface of the
furnace chassis which is close to the control. Tools
held in a person’s hand during grounding will be
satisfactorily discharged.
3. After touching the chassis, you may proceed to service
the control or connecting wires as long as you do
nothing to recharge your body with static electricity (for
example; DO NOT move or shuffle your feet, do not
touch ungrounded objects, etc.).
4. If you touch ungrounded objects (and recharge your
body with static electricity), firmly touch a clean,
unpainted metal surface of the furnace again before
touching control or wires.
5. Use this procedure for installed and uninstalled
(ungrounded) furnaces.
6. Before removing a new control from its container,
discharge your body’s electrostatic charge to ground to
protect the control from damage. If the control is to be
installed in a furnace, follow items 1 through 4 before
bringing the control or yourself in contact with the
furnace. Put all used and new controls into containers
before touching ungrounded objects.
7. An ESD service kit (available from commercial
sources) may also be used to prevent ESD damage.
FURNACE RELIABILITY HAZARD
Improper installation or service of furnace may cause
premature furnace component failure.
Electrostatic discharge can affect electronic
components. Follow the Electrostatic Discharge
Precautions Procedure listed below during furnace
installation and servicing to protect the furnace electronic
control. Precautions will prevent electrostatic discharges
from personnel and hand tools which are held during the
procedure. These precautions will help to avoid
exposing the control to electrostatic discharge by putting
the furnace, the control, and the person at the same
electrostatic potential.
CAUTION
!
Figure 4
−
Multipoise Orientations
THE BLOWER IS LOCATED
TO THE RIGHT OF THE
BURNER SECTION, AND
AIR CONDITIONED AIR IS
DISCHARGED TO THE LEFT.
THE BLOWER IS
LOCATED BELOW THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED UPWARD.
THE BLOWER IS
LOCATED ABOVE THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED DOWNWARD
THE BLOWER IS
LOCATED TO THE LEFT
OF THE BURNER SECTION,
AND CONDITIONED AIR IS
DISCHARGED TO THE RIGHT.
A02097