Note:
1. AHU = Air Handling Unit, LG = Length, WD = Width, Cond = Condenser, RA = Return Air, RAR = RA
Right, RAL = RA Left, SA = Supply Air
2. SU = Standard Unit, DP = Discharge Plenum, B = Bottom, L = Left
Table 35: Field piping
Field piping
25 ton to
30 ton unit
40 ton to
50 ton unit
60 ton unit
70 ton to
80 ton unit
Condensate drain
1.25 in. NPT
1.25 in. NPT
1.25 in. NPT
1.25 in. NPT
Gas heat 250 MBH
0.75 in. NPT
NA
NA
NA
Gas heat 500 MBH
1.00 in. NPT
1.00 in. NPT
1.00 in. NPT
1.00 in. NPT
Gas heat 750 MBH
1.00 in. NPT
1.00 in. NPT
NA
NA
Gas heat 1000 MBH
NA
NA
1.25 in. NPT
1.25 in. NPT
Gas heat 1250 MBH
NA
1.25 in. NPT
NA
NA
Gas heat 1500 MBH
NA
NA
1.50 in. NPT
1.50 in. NPT
Humidifier inlet
1 in. NPT
1 in. NPT
NA
NA
Humidifier drain
1.25 in. NPT
1.25 in. NPT
NA
NA
Hot water supply (high heat)
2.50 in. NPT
3.00 in. NPT
NA
NA
Hot water return (high heat)
2.50 in. NPT
3.00 in. NPT
NA
NA
Hot water supply (low heat)
1.50 in. NPT
2.00 in. NPT
NA
NA
Hot water return (low heat)
1.50 in. NPT
2.00 in. NPT
NA
NA
Steam supply
2.00 in. NPT
2.00 in. NPT
NA
NA
Steam return
1.50 in. NPT
1.50 in. NPT
NA
NA
Submittal data
Refer to the model number on the unit’s nameplate
to see what options the unit has.
Find the submittal data specific to your unit in the
Selection Navigator on the
Navigator®
customer
portal.
Note:
Alternatively download and use the
RTUToolkit application to get unit specific data.
Electrical data
The rooftop unit requires both power and control
wiring. Power and control wiring must be field
provided and installed.
Power and control wiring MUST conform to the
latest edition of the National Electrical Code® (NEC)
NFPA 70 or local codes and regulations. Power
supply to the unit must be NEC Class 1 and comply
with applicable local codes.
CAUTION
Copper conductors MUST be used for power wiring.A
disconnect switch MUST be installed (factory option
available).
Internal wiring harnesses furnished with the unit
are an integral part of the design certified unit. Field
alterations to comply with local codes should not be
needed. If any factory wiring needs to be replaced,
it must be of the same wire type and gauge as the
original factory wire.
CAUTION
Field power wiring connected to the incoming power
termination point must be copper conductor only.
Aluminum wire cannot be connected to the incoming
power termination point.
Tempmaster
®
Omni™ Premier 25 Ton to 80 Ton Rooftop Units Installation and Maintenance Guide
61