Temperzone   SAT-­‐3   Installation   Setup   Guide,   Issue   2   

   

      

   

   

Page   2

   of   7   

   

   

1.

 

Quick   Start   Guide   

1.1.

 

General   

Refer   to   the   User’s   operating   instruction   booklet   for   everyday   operation   of   the   SAT-­‐3.   

The   system   may   include   only   one   SAT-­‐3.   

In   the   following   instructions,   to   navigate   the   settings   of   the   SAT-­‐3   thermostat   press   

   

or   

.   To   adjust   a   setting   press

   or

.      

1.1.1.

 

Installation   Settings   

Apply   power   to   the   system.   

The   SAT-­‐3   is   configured   by   default   to   operate   with   standard   Temperzone   air-­‐conditioners   

and   in   most   cases   no   adjustment   is   necessary.   If   required,   refer   to   section   2.1   on   page   3   for   

details   of   the   installation   settings   and   how   they   may   be   adjusted.   

1.1.2.

 

Clock   Setting   

Hold   down   the   

   or   

   key   for   3   seconds   to   start   adjusting   the   clock.   The   clock   

symbol   

   will   start   to   flash   as   well   as   the   presently   selected   day   of   the   week.   Set   the   day   

of   the   week   and   time   using   the   keys   detailed   in   section   1.1.   When   the   day   and   time   are   set   

correctly,   leave   the   SAT-­‐3   for   15   seconds   to   return   to   normal   operation.      

1.2.

 

Fan   Setup   

   Activate   fan   setup   mode   by   holding   down   

   and   

   together   for   3   seconds.   

When   fan   setup   mode   is   active   the   symbol   

   on   the   display   flashes   on   and   off.   

1.

 

Adjust   the   low   fan   control   voltage   to   a   suitable   low   level   while   monitoring   the   

airflow.   

2.

 

Adjust   the   high   fan   control   voltage   to   a   suitable   high   level   while   monitoring   the   

airflow.   

When   adjustment   is   complete   press      

   to   exit   fan   setup   mode.   

Setting   

Display   

Range   

Notes   

Low   level   fan   

control   voltage   

   

SET   

Lo

   

2.0   to   8.0   

Default   5.0   

Steps   of   0.333      

e.g.   2.0,   2.3,   2.7,   3.0,   etc.   

High   level   fan   

control   voltage   

   

SET   

Hi

   

4.0   to   10.0   

Default   8.0   

Steps   of   0.333      

e.g.   4.0,   4.3,   4.7,   5.0,   etc.   

1.3.

 

Air-­Conditioner   Commissioning   

Activate   commissioning   mode   by   holding   down   

   and   

   together   for   3   seconds.      

Test   the   cooling   cycle   and   (if   installed)   heating   cycle   operation   of   the   air-­‐conditioner.      

Refer   to   section   2.3   on   page   6   for   full   details   of   Commissioning   mode.   

Содержание SAT-3

Страница 1: ...Temperzone SAT 3 Installation Setup Guide Issue 2 SAT 3 Installation Setup Guide Date 4 February 2016 Issue 2 Applies to SAT 3 room temperature controller part number 201 000 146 ...

Страница 2: ...Temperzone SAT 3 Installation Setup Guide Issue 2 ...

Страница 3: ...uide 2 1 1 General 2 1 1 1 Installation Settings 2 1 1 2 Clock Setting 2 1 2 Fan Setup 2 1 3 Air Conditioner Commissioning 2 2 Detailed SAT 3 Configuration 3 2 1 Installation Settings 3 2 2 Fan Settings 5 2 3 Commissioning Mode 6 2 4 Return Air Sensor Option 6 3 SAT 3 Fault Indications 8 ...

Страница 4: ...nd time using the keys detailed in section 1 1 When the day and time are set correctly leave the SAT 3 for 15 seconds to return to normal operation 1 2 Fan Setup Activate fan setup mode by holding down and together for 3 seconds When fan setup mode is active the symbol on the display flashes on and off 1 Adjust the low fan control voltage to a suitable low level while monitoring the airflow 2 Adju...

Страница 5: ...i SET Ht Ct to 50 0 C Steps of 0 5 C Temperature differential i td 0 5 to 1 5 C Steps of 0 5 C Indoor fan type i Ft 1 or 3 Single or three speed fan Default 3 speed Enable disable Heating mode i On or off Default on Enable disable Cooling mode i On or off Default on Enable disable Cool Heat auto mode i On or off Default on see note 1 Enable disable Fan Only mode i On or off Default on Enable disab...

Страница 6: ...point from zone 1 set point i ZONE SP 2 0 to 10 0 C N A see note 6 Minimum number of zones that must be on i ZONE nn 0 1 or 2 N A see note 6 Zone 1 Size i 1 to 5 N A see note 6 Zone 2 Size i 0 to 5 N A see note 6 Zone 3 Size i 0 to 5 N A see note 6 Zone 4 Size i 0 to 5 N A see note 6 Zone 5 Size i 0 to 5 N A see note 6 Zone 6 Size i 0 to 5 N A see note 6 Programmable timer function i tF 1 or 2 Def...

Страница 7: ...bol on the display flashes on and off Settings in Fan Setup Mode are as follows Setting Display Range Notes Low level fan control voltage SET Lo 2 0 to 8 0 Default 5 0 High level fan control voltage SET Hi 4 0 to 10 0 Default 8 0 Steps of 0 333 e g 2 0 2 3 2 7 3 0 etc Additional zone voltage increase SET Ad 0 to 950 Default 300 Zone 1 balance bL 10 to 100 Default 100 Zone 2 balance bL 10 to 100 De...

Страница 8: ...utes 1 minute Minimum heating to cooling change over time 10 minutes 1 minute Power on delay prior to starting compressor 2 minutes 2 minutes 2 4 Return Air Sensor option To use a return air sensor with the SAT 3 the return air sensor must be connected to the SAT 3 The SAT 3 provides a socket that accepts a 2 pin JST connector of the standard type that Temperzone uses for its optional temperature ...

Страница 9: ...ith the power disconnected Code displayed Description Remedy t1 SAT 3 internal temperature sensor error The internal temperature sensor of the SAT 3 is damaged Replace the SAT 3 t2 SAT 3 external temperature sensor error Check the external temperature sensor connected to the Sat 3 t3 No communications between SAT 3 and unit controller Check the wiring between the unit controller and the SAT 3 Chec...