background image

Temperzone   SAT-­‐3   Installation   Setup   Guide,   Issue   2   

   

      

   

   

Page   5

   of   7   

   

   

Notes:   

1.

 

Auto   cool/heat   mode   can   only   be   enabled   if   both   cooling   and   heating   mode   are   also   

enabled.   

2.

 

Dry   mode   (de-­‐humidification)   can   only   be   enabled   if   cooling   mode   is   also   enabled.   

3.

 

Room   temperature   sensor:   1   =   internal,   2   =   external,   3   =   average   of   internal   and   

external,   4=zone   1   temperature   (from   modbus   –   do   not   use   with   un-­‐zoned   systems).   

4.

 

Zone   1   temperature   calibration   is   applied   to   the   room   temperature   from   the   

selected   source   described   above   in   note   3.   

5.

 

Programmable   timer   function:   1   =   standard,   2   =   advanced.   

6.

 

Not   applicable   to   systems   without   zone   controller.   

2.2.

 

Fan   Settings   

To   activate   fan   setup   mode   hold   down   

   and   

   together   for   3   seconds.   When   

Fan   Setup   Mode   is   active   the   symbol   

   on   the   display   flashes   on   and   off.   

Settings   in   Fan   Setup   Mode   are   as   follows:   

Setting   

Display   

Range   

Notes   

Low   level   fan   

control   voltage   

   

SET   

Lo

   

2.0   to   8.0   

Default   5.0   

High   level   fan   

control   voltage   

   

SET   

Hi

   

4.0   to   10.0   

Default   8.0   

Steps   of   0.333      

e.g.   2.0,   2.3,   2.7,   3.0,   etc.   
   

Additional   zone   
voltage   increase   

   

SET   

Ad

   

0   to   950   
Default   300   

Zone   1   balance   

   

   

bL

   

10   to   100%   

Default   100%   

Zone   2   balance   

   

   

bL

   

10   to   100%   

Default   100%   

Zone   3   balance   

   

   

bL

   

10   to   100%   

Default   100%   

Zone   4   balance   

   

   

bL

   

10   to   100%   

Default   100%   

Zone   5   balance   

   

   

bL

   

10   to   100%   
Default   100%   

Zone   6   balance   

   

   

bL

   

10   to   100%   

Default   100%   

Not   applicable   to   systems   
without   zone   controller   

   

   

   

   

   

   

As   the   settings   are   adjusted   the   unit   controller   adjusts   its   operation   to   allow   the   settings   to   

be   evaluated:   

Setting   

Unit   controller   operation   

Low   level   

control   voltage   

The   indoor   fan   operates   at   the   low   voltage   level   selected   

High   level   
control   voltage   

The   indoor   fan   operates   at   the   high   voltage   level   selected   

Содержание SAT-3

Страница 1: ...Temperzone SAT 3 Installation Setup Guide Issue 2 SAT 3 Installation Setup Guide Date 4 February 2016 Issue 2 Applies to SAT 3 room temperature controller part number 201 000 146 ...

Страница 2: ...Temperzone SAT 3 Installation Setup Guide Issue 2 ...

Страница 3: ...uide 2 1 1 General 2 1 1 1 Installation Settings 2 1 1 2 Clock Setting 2 1 2 Fan Setup 2 1 3 Air Conditioner Commissioning 2 2 Detailed SAT 3 Configuration 3 2 1 Installation Settings 3 2 2 Fan Settings 5 2 3 Commissioning Mode 6 2 4 Return Air Sensor Option 6 3 SAT 3 Fault Indications 8 ...

Страница 4: ...nd time using the keys detailed in section 1 1 When the day and time are set correctly leave the SAT 3 for 15 seconds to return to normal operation 1 2 Fan Setup Activate fan setup mode by holding down and together for 3 seconds When fan setup mode is active the symbol on the display flashes on and off 1 Adjust the low fan control voltage to a suitable low level while monitoring the airflow 2 Adju...

Страница 5: ...i SET Ht Ct to 50 0 C Steps of 0 5 C Temperature differential i td 0 5 to 1 5 C Steps of 0 5 C Indoor fan type i Ft 1 or 3 Single or three speed fan Default 3 speed Enable disable Heating mode i On or off Default on Enable disable Cooling mode i On or off Default on Enable disable Cool Heat auto mode i On or off Default on see note 1 Enable disable Fan Only mode i On or off Default on Enable disab...

Страница 6: ...point from zone 1 set point i ZONE SP 2 0 to 10 0 C N A see note 6 Minimum number of zones that must be on i ZONE nn 0 1 or 2 N A see note 6 Zone 1 Size i 1 to 5 N A see note 6 Zone 2 Size i 0 to 5 N A see note 6 Zone 3 Size i 0 to 5 N A see note 6 Zone 4 Size i 0 to 5 N A see note 6 Zone 5 Size i 0 to 5 N A see note 6 Zone 6 Size i 0 to 5 N A see note 6 Programmable timer function i tF 1 or 2 Def...

Страница 7: ...bol on the display flashes on and off Settings in Fan Setup Mode are as follows Setting Display Range Notes Low level fan control voltage SET Lo 2 0 to 8 0 Default 5 0 High level fan control voltage SET Hi 4 0 to 10 0 Default 8 0 Steps of 0 333 e g 2 0 2 3 2 7 3 0 etc Additional zone voltage increase SET Ad 0 to 950 Default 300 Zone 1 balance bL 10 to 100 Default 100 Zone 2 balance bL 10 to 100 De...

Страница 8: ...utes 1 minute Minimum heating to cooling change over time 10 minutes 1 minute Power on delay prior to starting compressor 2 minutes 2 minutes 2 4 Return Air Sensor option To use a return air sensor with the SAT 3 the return air sensor must be connected to the SAT 3 The SAT 3 provides a socket that accepts a 2 pin JST connector of the standard type that Temperzone uses for its optional temperature ...

Страница 9: ...ith the power disconnected Code displayed Description Remedy t1 SAT 3 internal temperature sensor error The internal temperature sensor of the SAT 3 is damaged Replace the SAT 3 t2 SAT 3 external temperature sensor error Check the external temperature sensor connected to the Sat 3 t3 No communications between SAT 3 and unit controller Check the wiring between the unit controller and the SAT 3 Chec...