background image

ST

ART

-UP

 PROCEDURE

UNIT PROTECTION

WIRING

- 3 -

installation details; model search 'SAT-3'.

  A separate instruction booklet comes with the  

SAT-3 for installation and operation.

  Remote temperature sensors are available 

separately and can be installed to enhance the 

systems functionality. 

Note: Ensure the remote sensor wires are run 

separately and away from main power supply wires, 

including the interconnecting cable.

c. BMS Control via dry contact and analog inputs:   

the unit controller (UC8) offers facilities to connect a 

BMS system via a set of of no-voltage contacts and 

0-10V dc analog signals.

d. BMS control via Modbus over RS485. For a full list 

of the Modbus control setup, settings and read/write 

parameters. Contact Temperzone for details, or visit 

www.temperzone.biz; model search 'BMS'.

5  UNIT PROTECTION

5.1 General

Unit protection is incorporated in the UC8 Controller 

board. A high pressure lockout protects the unit in the 

event of either water flow failure in cooling mode, fan 

failure in heating mode, or a loss of refrigerant. Units 

include an anti rapid cycle timer for compressor on/off 

protection. 
On CWP

S

R units the unit's controller (UC8) protects 

against freezing of the water within the unit on heating 

mode. There are relay boards supplied for both common 

fault output and run status indication (refer 7.5).
Refer to UC8 Controller label on the unit for operation & 

fault diagnostics information, or visit www.temperzone.biz
Note:  Lockout protection can be reset by switching 

the unit's power supply off and on. Lockout protection 

can also be reset by Modbus connection. For detailed 

information about control via Modbus RTU refer to 

document UC8 Modbus communications available at 

www.temperzone.biz; model search 'UC8'.

5.2  Electric Heating

Electric element/s are totally enclosed within the unit 

and are supplied with auto (90°C) and manual (120°C) 

high temp. safety thermostats required to meet AS/

NZS 60335.2.40 2006. A fan run-on timer for rapid heat 

dissipation is incorporated into the UC8 as well as a 70° 

fast acting temperature sensor to ensure overall safety. 

5.3  UC8 Controller Options

For more information on the functions, operation and 

options provided by the UC8 Controller (eg thermostat 

options, remote on/off, BACnet

 

BMS control via 

modbus over RS485, DRED, data logging), refer 

www.temperzone.biz; model search 'UC8'. 

6. START-UP PROCEDURE

6.1 Power

a.  Check the unit is electrically connected in accordance 

with the wiring diagrams.

b.  Check all wiring connection and terminal tightness.

c.  Switch ON the Main distribution board circuit breaker 

and the local isolator.

d.  Ensure the thermostat is OFF. 

e.  Check the supply voltage.

6.2 Fan

Various options are available if either High speed or Low 

speed need adjusting:
a.   The UC8 in the unit can be used to adjust the fan 

speed (applies only when the TZT-100 is used, or 

other compatible alternative):-

i. Ensure the compressor is off and the thermostat or 

BMS does not request for the compressor to start.

ii. Press and hold down the SW3 push button on the 

UC8 circuit board until the display shows the letter 

'H', then release the push button.

iii. The fan will start and run at the 'High' speed setting 

(factory default setting is 5.0V). The display will 

show the value ('5.0') and the indoor fan will run at 

the selected speed.

iv. Each following press on the SW3 push button 

increases the indoor fan control voltage in steps of 

0.5V, up to a maximum of 10.0V. Pressing the push 

button again when value 10.0 is shown returns the 

fan control voltage down to the minimum value for 

'High' fan speed (3.0V).

v. When the desired setting for high fan speed is 

selected then wait for 30 seconds. The controller 

will save the selected value in its memory and 

return to normal operation.

vi. To adjust the fan 'Low' speed repeat the above 

procedure but wait until the display shows the letter 

'L' before releasing the push button. The factory 

default value for low speed is 3.0V.

c.  Check if the High speed airflow fits the requirements 

of the installation. Beware, in tropical (high humidity) 

conditions care must be taken to select an air flow 

which does not create water carry-over problems. 

d.  Check if the Low speed satisfies the application in 

respect to noise yet without risk of frost on the coil.

6.3 Water 

a.  Check water connections to the unit have been made, 

valves are open and there are no leaks.

b.  Set the water flow rate as per the Specification Sheet.

6.4 Starting the Compressor 

a.  On the unit's UC8 controller, press and hold the SW3 

push button until the display shows a letter 'c' for 

Commissioning, then release. This reduces the waiting 

times at start-up and between cycles.

b.  Refrigerant pressures can be viewed on the UC8 

display, making it unnecessary to connect gauges. 

Refer Table 1, p.8.

Содержание CWP Series

Страница 1: ...e of isolation valves and barrel unions on waterlines easily accessible electrical isolations on all external including control circuit power supply and easily detached flexible duct connection Ensure...

Страница 2: ...Temperature EWT and the reduced flow rate Water flow needs to be balanced to suit the system design Refer Technical Data for acceptable water flow rates and pressure drop data 3 4 Air Water Flow Refer...

Страница 3: ...us over RS485 DRED data logging refer www temperzone biz model search UC8 6 START UP PROCEDURE 6 1 Power a Check the unit is electrically connected in accordance with the wiring diagrams b Check all w...

Страница 4: ...rd compressor and total run amps during stable operation e Check the readings against the specified values on Specification Sheet and record these values on the Commissioning Check List on page 11 f U...

Страница 5: ...or the procedure Example For detailed information about monitoring and control via Modbus RTU refer to document UC8 Modbus communications available at www temperzone biz model search UC8 7 4 Setting t...

Страница 6: ...e kept open Location of wall controller or remote temperature sensor is wrong Check for leaks in supply or return air ductwork Unit may be undersized for the current room size or operating under extre...

Страница 7: ...normally open remove link if used IN 1 link D1 SC UC8 Optional Condensate Drain Tray float switch normally closed remove link if used Optional Communicating BMS Controller Modbus RTU B1 A1 0V B A REF...

Страница 8: ...C Ct Condensing temperature 42 C Compressor discharge line temperature C dLt Discharge line temperature 70 C Compressor discharge side superheat K dSH Discharge side superheat 28K De ice sensor temper...

Страница 9: ...acting sensor for the electric heater elements has been triggered The display shows the message Hi t when protection is active 5 High discharge superheat protection Discharge superheat is defined as...

Страница 10: ...ting when a serious fault exists that requires the attention of a service technician The display shows the code of the fault that caused the lock out condition A unit that is locked out can be unlocke...

Страница 11: ...st Cool Cycle Low Pressure SLP kPa Return air temperature C Evap temperature Et C Supply air temperature C Suction Line temperature SLt C Entering Water temperature C Suction Superheat SSH K Leaving W...

Страница 12: ...ydney Australian Head Office and Manufacturing Wellington Christchurch Brisbane Melbourne Adelaide Singapore Shanghai Perth Hobart Newcastle Singapore Shanghai Beijing Jakarta Hong Kong Sri Lanka Maur...

Отзывы: