background image

W

A

TER CONNECTION

WIRING

- 2 -

3  WATER CONNECTION

3.1 General

The CWP unit has two pair of IN/OUT water connections 

(top and front). The unused pair must be securely 

capped off. IN/OUT water connections are male BSP 

pipe threaded. The unit can be piped directly or using 

two temperzone flexible high pressure water hoses 

(recommended optional extra) which have tapered 

hydraulic female swivel union fittings at each end.
Sediment free water supply is required for correct heat 

rejection performance. Ensure water circuit is maintained 

and sediment free. Any contaminants may need to be 

pre-filtered by external means, particularly where open 

cooling towers are used. Unmaintained water quality can 

lead to nuisance tripping and premature corrosion. 
If a closed loop water system is used, with treatment, it 

may be considered unnecessary to have water filtering in 

the main supply loop.
Note: Always install isolating valves and a Stat valve 

set to ensure the correct CWP design waterflow. It is 

recommended that the water supply system be fitted with 

a water flow switch and water flow verification circuit. 

These items prevent the CWP units from going into fail 

safe lockout status due to a loss of water flow. 
Failure to install the above items could require the 

resetting of all CWP units in the system – by breaking 

the power supply to each unit or by Modbus command (if 

installed).

3.2 Water Control

A motorised water shut-off valve is supplied built-in and 

connected to the UC8 controller; refer wiring diagram. 

The valve is closed when the compressor is off. 
This valve control system ensures water does not flow 

through the unit when it is not operational for a long 

period of time, thereby reducing the overall central pump 

power usage. The UC8 controller performs a periodic 

water-flush-cycle to minimizes the risk of stagnant water 

and settling of particulate deposits when the unit is off for 

long periods.

3.3 Circuit Balancing Valve

An external circuit balancing valve must be fitted to 

maintain water flow at a constant rate. The minimum 

water flow rates in litres per second (l/s) are stated in the 

supplied Specifications Data sheet.
The CWP unit controller (UC8) will protect the 

refrigeration system of the unit under severe operating 

conditions. On heating cycle it protects to ensure the 

evaporating temperature does not drop below freezing 

for an extended period. The extreme lowest leaving water 

temperature needs to be such that the unit does not 

cut-out on protection and will be above approx. 4°C. This 

can be achieved by a combination of the Entering Water 

Temperature (EWT) and the reduced flow rate. Water 

flow needs to be balanced to suit the system design. 

Refer Technical Data for acceptable water flow rates and 

pressure drop data.

3.4  Air / Water Flow

Refer to CWP Technical Data pamphlets at  

www.temperzone.biz for detailed information on air 

handling performance and water flow rates.

3.5 Water Circulating Pump & Flow Verification Options

In order to promote efficiency and avoid running the 

water circulation pump unnecessarily, the unit's UC8 

Controller can be used to control the activation of the 

pump prior to running the compressor. After the activation 

signal is sent to the external water circulating pump, 

the UC8 waits for the flow verification contact to close 

(if present) before starting the compressor (refer wiring 

diagram, p.7). The UC8 will also de-activate the pump 

when the compressor stops. 

3.6 Heating Operation

On heating, the UC8 looks at the entering water 

temperature and if this is below 10°C it will activate 

the electric standby elements to warm the air stream 

and achieve the room thermostat setpoint. If the water 

temperature is above 10°C, the CWP will action the 

reverse cycle heating and compressor. If the evaporating 

temp. consistently stays below -10°C and/or the entering 

water temp. drops consistently below 5°C , the UC8 will 

stop the compressor and revert to standby electric heat.

4. WIRING

4.1 General

Electrical power wiring must be fitted and certified by 

persons with appropriate qualifications and certification 

and comply with local and national standards.
Where appllcable, a signed 'Certificate of Compliance' 

must be left with the unit for insurance purposes.

4.2 Power to Unit

All power wiring is to be done to the appropriate 

electrical standard of the country in which the unit is 

being installed.

The person installing the wiring is responsible for the 

correct selection of wiring size and auxiliary components.

See the Specification Sheet for supply voltage range, 

frequency, phase and maximum operating current .

Wire the unit directly from the Electrical Distribution 

Board.

The unit should have its own dedicated circuit breaker 

on the Distribution Board and a lockable isolator switch 

should be installed in accordance with the applicable 

wiring regulations.

4.3 Control 

Room Temperature Controller

The thermostat should be set within the recommended 

operating range of between 19°C and 30°C.

Various options are available to control the air 

conditioning unit operation.

a. Temperzone TZT-100 Wall Thermostat.

  Refer  to www.temperzone.biz for features and 

installation details; model search 'TZT-100'.

  Separate 'Installer' and 'User' instructions are 

supplied with the TZT-100 for installation and 

operation.

b. The Temperzone SAT-3 Wall Thermostat.

  Refer to www.temperzone.biz for features and 

Содержание CWP Series

Страница 1: ...e of isolation valves and barrel unions on waterlines easily accessible electrical isolations on all external including control circuit power supply and easily detached flexible duct connection Ensure...

Страница 2: ...Temperature EWT and the reduced flow rate Water flow needs to be balanced to suit the system design Refer Technical Data for acceptable water flow rates and pressure drop data 3 4 Air Water Flow Refer...

Страница 3: ...us over RS485 DRED data logging refer www temperzone biz model search UC8 6 START UP PROCEDURE 6 1 Power a Check the unit is electrically connected in accordance with the wiring diagrams b Check all w...

Страница 4: ...rd compressor and total run amps during stable operation e Check the readings against the specified values on Specification Sheet and record these values on the Commissioning Check List on page 11 f U...

Страница 5: ...or the procedure Example For detailed information about monitoring and control via Modbus RTU refer to document UC8 Modbus communications available at www temperzone biz model search UC8 7 4 Setting t...

Страница 6: ...e kept open Location of wall controller or remote temperature sensor is wrong Check for leaks in supply or return air ductwork Unit may be undersized for the current room size or operating under extre...

Страница 7: ...normally open remove link if used IN 1 link D1 SC UC8 Optional Condensate Drain Tray float switch normally closed remove link if used Optional Communicating BMS Controller Modbus RTU B1 A1 0V B A REF...

Страница 8: ...C Ct Condensing temperature 42 C Compressor discharge line temperature C dLt Discharge line temperature 70 C Compressor discharge side superheat K dSH Discharge side superheat 28K De ice sensor temper...

Страница 9: ...acting sensor for the electric heater elements has been triggered The display shows the message Hi t when protection is active 5 High discharge superheat protection Discharge superheat is defined as...

Страница 10: ...ting when a serious fault exists that requires the attention of a service technician The display shows the code of the fault that caused the lock out condition A unit that is locked out can be unlocke...

Страница 11: ...st Cool Cycle Low Pressure SLP kPa Return air temperature C Evap temperature Et C Supply air temperature C Suction Line temperature SLt C Entering Water temperature C Suction Superheat SSH K Leaving W...

Страница 12: ...ydney Australian Head Office and Manufacturing Wellington Christchurch Brisbane Melbourne Adelaide Singapore Shanghai Perth Hobart Newcastle Singapore Shanghai Beijing Jakarta Hong Kong Sri Lanka Maur...

Отзывы: