Error Code

The description of the Error code is explained below 

Error Code 

Display Symbol 

Description & Reason 

Corrective Action 

ER04 

Illegal setup values used:

 COOL is 

used for OUT2 when DIRT (cooling 

action) is used for OUT1, 

or when PID mode is not used for 

OUT1 (PB =0 and/or TI=0) 

Check and correct setup values of OUT2, PB1, PB2, 

TI1, TI2 and OUT1. IF OUT2 is needed for cooling 

control, the controller should use PID mode (PB

 0 

and TI

 0) and OUT1 should use reverse mode 

(heating action), otherwise, OUT2 cannot be used for 

cooling control 

10 

ER10 

Communication error: 

bad function 

code 

Correct the communication software to meet the 

protocol requirements. 

11 

ER11 

Communication error: 

register 

address out of range 

Do not issue an over-range address of the register to 

the 

secondary

 

14 

ER14 

Communication error: 

attempt to 

write a read-only data 

Do not write read-only data or protected data to 

the 

secondary

15 

ER15 

Communication error: 

write a value 

which is 

out of range to a register 

Do not write an over-range data to the 

secondary

 register 

16 

EIER 

Event Input Error: 

Two or more 

event inputs are set to the same 

function

 

Do not set the same function in two or more Event 

Input Function parameters (E1FN through E6FN) 

26 

ATER 

Auto-Tuning Error:

 Failed to perform 

Auto-Tuning function 

1. The PID values obtained after Auto-Tuning

process are out of range. Retry Auto-Tuning.

2. Do not change the setpoint value during Auto-

Tuning process.

3. Use manual tuning instead of Auto-Tuning

process.

4. Do not set a zero value for TI.
5. Do not set a zero value for PB.
6. Touch RESET key

29 

EEPR 

EEPROM can't be written correctly 

Return to factory for repair. 

30 

CJER 

Cold junction compensation for 

Thermocouple malfunction 

Return to factory for repair. 

39 

SBER 

Input sensor break, or input 

current below 1 mA if 4-20 mA is 

used, or input voltage below 

0.25V if 1 - 5V is used 

Replace the input sensor. 

40 

ADER 

A to D converter or related 

component(s) malfunction 

Return to factory for repair. 

6-5.Error Code

6.5

 

Mode 

The Value of the Mode Register is as below. 

Value 

Mode 

H'000X 

Normal mode 

H'010X 

Calibration mode 

H'020X 

Auto-Tuning mode 

H'030X 

Manual control mode 

H'040X 

Failure mode 

H'0X00 

Alarm status is off 

H'0x01 

Alarm status is on 

6-6.Operation Mode

1

9

Содержание TPC10062

Страница 1: ...TPC10062 Power Control Console with TEC 9400 PID Fuzzy Logic Process Controller D1306 TE 401 402 404 405 Revision 2 22 2019 USER MANUAL Manual TPC10062 Revision 4 21 D1357 02...

Страница 2: ......

Страница 3: ...d personnel only 3 To minimize the possibility of fire or shock do not expose this console to rain or excessive moisture 4 Do not use this console in areas where hazardous conditions exist such as exc...

Страница 4: ...e following pages for complete operation and page 4 for auto tuning of the TEC 9400 temperature controller SPARE REPLACEMENT PARTS Tempco Description Part Number EHD 124 148 Fuse rated 15 Amp 250V x 1...

Страница 5: ...error message 5 Restart the dwell timer when the dwell timer has timed out 6 Enter the manual control menu if failure mode occurs ENTER KEY Press and hold for 5 seconds or longer to for 6 2 seconds t...

Страница 6: ...Sec 5 Sec 5 Sec To access parameter In the User Menu Refer to Section 1 1 1 To access parameter in the Setup Menu Refer to Section 1 1 2 Page 5 To start Manual Control Mode Refer to Section 1 1 3 Page...

Страница 7: ...ile Menu Ramp and Soak 1 1 2 1 Basic Menu bASE In the setup menu when the upper display says SET Use the or keys to get bASE in the lower display Then use the key to cycle through the bASE menu parame...

Страница 8: ...en the upper display says SET use the or key to get oUT in the lower display Then use the key to cycle through the oUT menu parameters Note Chart on pg 9 or SET OUT OUT1 O1TY O1FT O1HY CYC1 OFST OUT2...

Страница 9: ...output 1 Cx xx is used to adjust output 2 You are able to exit manual mode by pressing and holding the key 1 1 4 Auto Tuning Mode Tunes PID Parameters to Your Application Also refer to pg 15 Press an...

Страница 10: ...input 16 0 20 0 20mA linear current input 17 0 5V 0 5VDC linear voltage input 18 1 5V 1 5VDC linear voltage input 19 0 10 0 10VDC linear voltage input 0 9 UNIT Input unit selection 0 oC C unit 1 oF F...

Страница 11: ...action 0 21 O1TY FACTORY SET DO NOT CHANGE Output 1 signal type 0 RELY Relay output 1 SSrd Solid state relay drive output 2 4 20 4 20mA linear current 3 0 20 0 20mA linear current 4 0 5V 0 5VDC linear...

Страница 12: ...meter Description Range Default Value 27 RR Ramp rate See Pg 13 Low 0 0 High 900 0 F 0 61 PL1L Output 1 Low Power limit Low 0 High PL1H or 50 0 62 PL1H Output 1 High Power limit Low PL1L High 100 100...

Страница 13: ...ghts 0 Any Value All parameters are changeable 1000 1000 All parameters are changeable 1000 Only user menu parameters changeable 9999 9999 All parameters are changeable 9999 Only SP1 to SP7 are change...

Страница 14: ...only P or PD Control Used for Electric Heaters Select REVR for OUT1 set TI 0 OFST is used to adjust the control offset manual reset If PB 0 then O1HY will be hidden OFST Function OFST is measured in...

Страница 15: ...on is performed during power up or any time the set point is changed Choose MINR ramp in minutes or HRR ramp in hours for the RAMP setting and the controller will perform the ramping function The ramp...

Страница 16: ...OFTL Send your low signal to the sensor input of the controller then press and release the key If the process value the upper display is different from the input signal the user can use and keys to ch...

Страница 17: ...mpless transfer After that the previous average value of of the output will be used for controlling output 1 2 If output 1 is configured as proportional control PB 0 and a value of 0 to 100 0 is set f...

Страница 18: ...l the process value falls below the setpoint This will occur at least two times while the controller learns how to control your process Procedures Auto Tuning can be applied either as the process is w...

Страница 19: ...still unsatisfactory the following guidelines can be applied for further adjustment of PID values ADJUSTMENT SEQUENCE SYMPTOM SOLUTION Proportional Band PB Slow Response Decrease PB High overshoot or...

Страница 20: ...will be on for 10seconds then turn off for 10 seconds The controller performs open loop control and ignores the input sensor as long as it stays in manual control mode 2 10 1 Exit Manual Control Press...

Страница 21: ...the secondary register 16 EIER Event Input Error Two or more event inputs are set to the same function Do not set the same function in two or more Event Input Function parameters E1FN through E6FN 26...

Страница 22: ...give as much background information on the application or process as possible E mail techsupport tempco com Phone 630 350 2252 800 323 6859 Note Information in this manual was deemed correct at the t...

Страница 23: ......

Страница 24: ...eaters Process Heaters Temperature Control Cartridge Heaters Coil Cable Heaters Strip Heaters Tubular Heaters Instrumentation Temperature Sensors HEAT THINGS UP HEAT THINGS UP With Thousands of Design...

Отзывы: