(*Parameters that are not applicable are not shown)
Register
Address
Parameter
Notation
Parameter Description
Range
Default
Value
16
DISP
Secondary display selection
0 None: No Display
1 MV1: Display MV1
2 MV2: Display MV2
3 tIMR: Display Dwell Time
4 PRoF: display Profile Status
0
17
PB
Proportional band value
(See Pg. 17)
Low: 0.0
High:
9
00.0°
F
(
5
00.0°
C
)
18.0° F
(10.0° C)
18
TI
Integral time value
(See Pg. 17)
Low: 0
High: 3600 sec
100
19
TD
Derivative time value
(See Pg. 17)
Low: 0.0
High: 360.0 sec
25
20
OUT1
Output 1 function
0 REVR: Reverse (heating) control
action
1 dIRt : Direct (cooling) control
action
0
21
O1TY
FACTORY
SET, DO
NOT
CHANGE
Output 1 signal type
0 RELY: Relay output
1 SSrd: Solid state relay drive
output
2 4-20: 4-20mA linear current
3 0-20: 0-20mA linear current
4 0-5V: 0-5VDC linear voltage
5 1-5V: 1-5VDC linear voltage
6 0-10: 0-10VDC linear voltage
1
22
O1FT
Output 1 failure transfer mode
(See Pg. 15)
Select BPLS (Bumpless transfer), or
0.0 ~ 100.0 % to continue output 1
control function if the sensor fails, or
select OFF (0) or ON (1) for ON-OFF
control
0
23
O1HY
Output 1 ON-OFF control
hysteresis. PB=0
Low: 0.
2
°
F
(0.
1
°
C
)
High:
9
0.0°
F
(
5
0.0°
C
)
0.2° F
(0.1° C)
24
CYC1
Output 1 cycle time
Low: 0.1
High: 90.0 sec.
1.0
26
RAMP
Ramp function selection
(See Pg. 13)
0 NoNE: No Ramp Function
1 MINR: Use
°
/minute as Ramp Rate
2 HRR: Use
°
/hour as Ramp Rate
0
Basic
Menu
Basic
Menu
Output
Menu
9