Tempco TEC-9400 Скачать руководство пользователя страница 8

 

Page 7 of 18 

 

1.1.2

 

Manual Mode Menu – (Use for Temporary Operation if Sensor Fails) 
Press and hold the “ ” key for approx. 6sec until the “HAND” parameter is shown in the upper display. 

Then, press and hold the “ ” key for an additional 5 sec. until an “MANU” led starts to flash in the lower left 

of the display.  Then, use the “ ” key to cycle through the available options. 

User is able to manually set the out output to be energized from 0-100% of the cycle time.   

“Hx.xx” is used to adjust output 1. 

“Cx.xx” is used to adjust output 2. 
You are able to exit manual mode by pressing and holding the 

 

key. 

 

 

1.1.3

 

Auto-Tuning Mode – (Tunes PID Parameters to Your Application) 

 

Press and hold the “ ” key for approx. 7sec until the “A-T” parameter is shown in the upper display. 

Press and hold the “ ” key for 5 seconds to activate Auto-Tuning Mode.  Continue to hold the “ ” key for 

an additional 3 seconds, else the display will revert to a “User Menu” parameter. 

 

Auto-tuning allows the controller to find its own optimal control parameters (PID) by measuring the speed of 

your thermal process.  

 

 

 

 

 

 

 

 

 

 

 

 

HANd

5 Sec

MV1
MV2

FILE

Press

 key 5 Sec To execute the selected default  program

Содержание TEC-9400

Страница 1: ...TPC 1000 2000 3000 4000 12 Amp with TEC 9400 PID Fuzzy Logic Process Controller D1306 TE 401 402 404 405 Revision 2 22 2019 USER MANUAL Manual TPC 1000 2000 3000 4000 12 Amp Revision 7 19 D1340...

Страница 2: ...uipment must be disconnected before installation or beginning any troubleshooting procedures Heater output wiring and component replacement must be made by qualified personnel only 3 To minimize the p...

Страница 3: ...4 290 for 4 zone units Fuse 1 rated 1 5 Amp 250V x 1 slow acting BUSS ABC 1 5 R Used for TEC 9400 Controller located inside rear panel mounted fuseholder EHD 124 300 for 2 zone units Fuses 2 rated 8 a...

Страница 4: ...Page 3 of 18 2 1 TEC 9400 Front Panel Keys and Display...

Страница 5: ...cess a parameter In the User Menu Refer to Section 1 1 1 1 page 5 To access a parameter in the Setup Menu Refer to Section 1 1 1 Starting on Page 5 8 Sub menu options are available for the setup menu...

Страница 6: ...ransformer Menu 4 Event Input Menu 8 Profile Menu Ramp and Soak 1 1 1 1 Basic Menu bASE In the setup menu when the upper display says SET Use the or keys to get bASE in the lower display Then use the...

Страница 7: ...menu when the upper display says SET use the or key to get oUT in the lower display Then use the key to cycle through the oUT menu parameters Note Chart on pg 9 or SET OUT OUT1 O1TY O1FT O1HY CYC1 OF...

Страница 8: ...o adjust output 1 Cx xx is used to adjust output 2 You are able to exit manual mode by pressing and holding the key 1 1 3 Auto Tuning Mode Tunes PID Parameters to Your Application Press and hold the k...

Страница 9: ...near current input 16 0 20 0 20mA linear current input 17 0 5V 0 5VDC linear voltage input 18 1 5V 1 5VDC linear voltage input 19 0 10 0 10VDC linear voltage input 0 1 or 13 Depends on Model Ordered 9...

Страница 10: ...Direct cooling control action 0 21 O1TY FACTORY SET DO NOT CHANGE Output 1 signal type 0 RELY Relay output 1 SSrd Solid state relay drive output 2 4 20 4 20mA linear current 3 0 20 0 20mA linear curr...

Страница 11: ...Parameter Notation Parameter Description Range Default Value 27 RR Ramp rate See Pg 13 Low 0 0 High 900 0 F 0 61 PL1L Output 1 Low Power limit Low 0 High PL1H or 50 0 62 PL1H Output 1 High Power limi...

Страница 12: ...ccess Rights 0 Any Value All parameters are changeable 1000 1000 All parameters are changeable 1000 Only user menu parameters changeable 9999 9999 All parameters are changeable 9999 Only SP1 to SP7 ar...

Страница 13: ...3 2 Heat only P or PD Control Used for Electric Heaters Select REVR for OUT1 set TI 0 OFST is used to adjust the control offset manual reset If PB 0 then O1HY will be hidden OFST Function OFST is meas...

Страница 14: ...en selecting parameters all of the above parameters may not be available The number of visible parameters depends on the configuration of the controller 2 4 Ramp The ramping function is performed duri...

Страница 15: ...ection 1 7 for the operation flowchart Press and hold the key until the setup Menu page is obtained Then press and release the key to navigate to the calibration low parameter OFTL Send your low signa...

Страница 16: ...m a Bumpless transfer After that the previous average value of of the output will be used for controlling output 1 2 If output 1 is configured as proportional control PB 0 and a value of 0 to 100 0 is...

Страница 17: ...until the process value falls below the setpoint This will occur at least two times while the controller learns how to control your process Procedures Auto Tuning can be applied either as the process...

Страница 18: ...uning is still unsatisfactory the following guidelines can be applied for further adjustment of PID values ADJUSTMENT SEQUENCE SYMPTOM SOLUTION Proportional Band PB Slow Response Decrease PB High over...

Страница 19: ...output will be on for 10seconds then turn off for 10 seconds The controller performs open loop control and ignores the input sensor as long as it stays in manual control mode 2 10 1 Exit Manual Contr...

Страница 20: ...exible Heaters Process Heaters Temperature Control Cartridge Heaters Coil Cable Heaters Strip Heaters Tubular Heaters Instrumentation Temperature Sensors HEAT THINGS UP With Thousands of Design Variat...