The proper sensor type is also a very important factor in obtaining precise measurements. The sensor must have the
correct temperature range to meet the process requirements. In special processes, the sensor might have additional
requirements such as leak-proof, anti-vibration, antiseptic, etc.
Standard sensor limits of error are ±4°F (±2°C) or 0.75% of sensed temperature (half that for special) plus drift caused
by improper protection or an over-temperature occurrence. This error is far greater than controller error and cannot be
corrected on the sensor except by proper selection and replacement.
5. Operation
5–1 Front Panel Description
5–2 Keypad Operation
*It takes 12 seconds with power on to memorize the new value of a parameter once it has been changed.
9
Alarm Outputs
Process Value
3 Silicone Rubber Buttons
for ease of control setup
and set point adjustment.
Set Point Value
Control Output
A1
A2
PV
'
C
'
F
SV
OUT
TEC
-9200
Press and release quickly to select which digit of a numerical parameter to change.
Press and hold to increase the value of the selected digit or to change the selection
for an index parameter.
Selects the parameter in a direct sequence. Also used to select the tool program
parameters.
Selects the parameters in higher security level, and actuates the selected tool
program whenever the display is showing a tool program.
Disables keypad operation to protect all the parameters from being tampered with.
Selects the tool programs in sequence.
Unlocks keypad operation and resets the front panel display to normal display mode,
exits tool program, or stops the autotuning function.
Starts the autotune program.
Press
for at least 3.2 seconds
Press
Press
Press
Press
for at least 3.2 seconds
Up Key
Down Key
(Direct) Scroll Key
Long Scroll/Enter Key
Reverse Scroll/Callibration
Verification Key
Lock Key
Tool Program Key
Reset/Exit Key
Autotune Key
TOUCHKEYS
FUNCTION
DESCRIPTION
Selects the parameters in a reverse direction during parameter scrolling, or verifies
the display accuracy for various input types during callibration.
Press
for at least 3.2 seconds
Press and release quickly to select which digit of a numerical parameter to change.
Press and hold to decrease the value of the selected digit or to change the selection
for an index parameter.