Tempco TEC-9200 Скачать руководство пользователя страница 8

Power Wiring

The controller is supplied to operate on 24V (20–32VAC/VDC) or 90–264VAC. Verify that the voltage of the power
supply corresponds to that indicated on the product label before connecting power to the controller.

This equipment is designed for installation in an enclosure which provides adequate protection against electrical

shock. The enclosure must be connected to earth ground.

Local requirements regarding electrical installation should be rigidly observed. Consideration should be given to prevent
unauthorized personnel from gaining access to the power terminals.

Input Wiring

Connect the appropriate sensor to terminals 12, 13, 14, 15, or 16 as indicated in figure 4.3. Make sure that the correct
sensor type is selected on the controller, and that the correct polarity is observed at both ends of the cable.
For thermocouple wiring, the correct type of extension wire must be used for the entire distance between the controller
and the thermocouple. The extension wires must be the same alloy and polarity as the thermocouple, and joints in the
cable should be avoided, if possible. The color codes used on the thermocouple extension wires are shown in table 4.1.
For wiring three-wire RTD, the two common wires should be connected to terminals 13 and 14, compensating lead
connected to terminal 13. When using a two-wire RTD, install a jumper between terminals 13 and 14. A three-wire RTD
offers the capability of lead resistance compensation, provided that all three leads are the same gauge and material, and
of equal length.

Table 4.1 International Thermocouple Cable Color Codes

* Color of overall sheath

Output Wiring

There are several types of output modules (see section 2) that can be selected for output 1 when ordering the TEC-
9200, depending on the control application. Make sure the output device you selected is appropriate for your application
requirements. The external connections will depend on the type of output installed. If pulsed voltage is selected, note
that pulsed voltage output is non-isolated.

Sensor Placement

Proper sensor installation can eliminate many problems in a control system. The probe should be placed so that it can
detect any temperature change with minimal thermal lag. In a process that requires fairly constant heat output, the probe
should be placed close to the heater. In a process where the heat demand is variable, the probe should be close to the
work area. Some experiments with probe location are often required to find the optimum position.

In a liquid process, the addition of a stirrer will help eliminate thermal lag. Since a thermocouple is basically a point
measuring device, placing more than one thermocouple in parallel can provide an average temperature readout and
produce better results in most air-heated processes.

Thermocouple

Type

Cable

Material

American

ANSI

British

BS

German

DIN

French

NFE

J

Iron/Constantan

+ white
- red
* black

+ yellow
- blue
* black

+ red
- blue
* blue

+ yellow
- black
* black

K

Chromel/Alumel

+ yellow
- red
* yellow

+ brown
- black
* red

+ red
- green
* green

+ yellow
- purple
* yellow

T

Copper/
Constantan

+ blue
- red
* blue

+ white
- blue
* blue

+ red
- brown
* brown

+ yellow
- black
* black

R

S

Platinum/Rhodium

+ black
- red
* green

+ white
- blue
* green

+ red
- white
* white

+ yellow
- green
* green

B

Platinum/Rhodium

+ grey
- red
* grey

+ red
- grey
* grey

8

Содержание TEC-9200

Страница 1: ...ure Controller TEMPCO Electric Heater Corporation 607 N Central Avenue Wood Dale IL 60191 1452 USA Tel 630 350 2252 800 323 6859 Fax 630 350 0232 website http www tempco com Copyright 2003 Tempco Elec...

Страница 2: ...nderstood and met CONTENTS 1 Introduction 2 Numbering System 3 Specifications 4 Installation 5 Operation 6 Recalibration 7 Error Messages and Diagnosis Information in this user s manual is subject to...

Страница 3: ...lling method by many industries yet PID has difficulty dealing with some sophisticated systems such as second and higher order systems long time lag systems during set point changes and or load distur...

Страница 4: ...gurable 9 Other 4 Control Mode 3 Field configurable 9 Other 5 Output 1 0 None 1 Relay 3A 240VAC 2 Pulse DC for SSR drive 24VDC 20mA max 3 4 20mA linear max load 500 ohms 4 0 20mA linear max load 500 o...

Страница 5: ...rotection NEMA 4X IP65 EMC emission EN50081 1 EN55011 EMC immunity IEC801 2 IEC801 3 IEC801 4 Sensor Input Type Range F Accuracy F Range C Accuracy C J Iron Constantan 58 to 1832 F 3 6 F 50 to 1000 C...

Страница 6: ...ure Do not use this instrument in areas under hazardous conditions such as excessive shock vibration dirt moisture corrosive gases or oil The ambient temperature of the areas should not exceed the max...

Страница 7: ...minals should not be used as jumper points as they may be internally connected causing damage to the unit Verify that the ratings of the output devices and the inputs are not exceeded Electrical power...

Страница 8: ...length Table 4 1 International Thermocouple Cable Color Codes Color of overall sheath Output Wiring There are several types of output modules see section 2 that can be selected for output 1 when order...

Страница 9: ...the value of the selected digit or to change the selection for an index parameter Selects the parameter in a direct sequence Also used to select the tool program parameters Selects the parameters in h...

Страница 10: ...UE SET POINT VALUE SHIF PB TI TD AhY1 AhY2 hYST ADDR LO SC hI SC PL 1 PL 2 INPT UNIT RESO CON A A1 MD A1 SF A2 MD A2 SF CYC CCYC C PB D B Security Level 1 Security Level 2 Short scroll advances forwar...

Страница 11: ...e selected input 999 F PL 1 Power limit of Output 1 0 100 100 PL 2 Power limit of Output 2 0 100 100 INPT Input type selection J K T E B R S or N TC J K T E B R S or N type T C PT100 DIN PTDN PT100 JI...

Страница 12: ...the Drift compensation code FAIL SAFE Fail Safe Defines the status of the outputs if the sensor fails OUT 1 ALM 1 ALM 2 or or or OUT 2 or Select the status for Output 1 ON or OFF Select the status fo...

Страница 13: ...minutes The dwell timer starts counting when the process value reaches the set point value See sections 5 10 and 5 13 for more details RAMP Ramp Rate This controls the heating or cooling rate of the...

Страница 14: ...cimal points Note that 2 dP can only be used for linear process input when Pu is selected for UNIT CON A Control Action of Output 1 This selects reverse heating action or direct cooling action for out...

Страница 15: ...e lower display For example if you select LOCK for LEV 2 and press the scroll key for 3 2 seconds to enter the selection the all parameters in level 2 can no longer be changed A LOCK message will appe...

Страница 16: ...values for the process which are then automatically entered into the nonvolatile memory During the second period of the auto tune program the controller performs PID control to verify the results and...

Страница 17: ...Sequence Symptom Solution Proportional Band P PB Slow response Decrease PB High overshoot or oscillations Increase PB Integral Time I TI Slow response Decrease TI Instability or oscillations Increase...

Страница 18: ...ble value When using on off control the parameters TI TD and CYC will have no effect on the system and both manual mode and the auto tune program will be disabled 5 9 Cooling Control Cooling control o...

Страница 19: ...d Hold Alarm A1SF LT HO When selected in any alarm mode prevents an alarm on power up The alarm is enabled when the process value reaches the set point value Thereafter the alarm acts as a latch alarm...

Страница 20: ...the controller fails Manual control mode is an open loop control The process may rise to a dangerous temperature Special attention must be paid to the process in order to prevent damage to the system...

Страница 21: ...being open on initial start up The timer begins to count down once the set point temperature has been reached After the amount of time set in ASP1 has elapsed the alarm 1 relay will close This functi...

Страница 22: ...libration data will be lost Do not attempt recalibration unless you have the appropriate calibration equipment available If the calibration data is lost you will need to return the controller to your...

Страница 23: ...e display Now the display will indicate process value with respect to the INPT type selected Feed a standard signal to the appropriate input terminals and examine the accuracy of the display 4 Press t...

Страница 24: ...en or shorted heater circuit Open coil in external contactor Burned out line fuses Burned out relay inside control Defective solid state relays Defective line switches Burned out contactor Defective c...

Страница 25: ...d into EEPROM Replace EEPROM 11 Process display shows OVER Overflow error data out of range during execution of software program Check for electrical noise 12 Process display shows LOCK Attempt to cha...

Страница 26: ...ic Heater Corporation 607 N Central Avenue Wood Dale IL 60191 1452 USA Tel 630 350 2252 800 323 6859 Fax 630 350 0232 website http www tempco com Copyright 2003 Tempco Electric Heater Corporation all...

Отзывы: