background image

Page 3 of 4

Wiring Precautions:

• Before  wiring,  verify  the  correct  model  number  and

options  on  the  label.  Switch  off  the  power  while
checking.

• Care must be taken to ensure that the maximum voltage

rating specified on the label is not exceeded.

• It  is  recommended  that  the  power  for  these  units  be

protected  by  fuses  or  circuit  breakers  rated  at  the
minimum value possible.

• All  units  should  be  installed  in  a  suitable  enclosure  to

prevent live parts from being accessible to human hands
and  metal  tools.  Metal  enclosures  and/or  subpanels
should  be  grounded  in  accordance  with  national  and
local codes.

• All  wiring  must  conform  to  appropriate  standards  of

good  practice  and  local  codes  and  regulations.  Wiring
must  be  suitable  for  the  voltage,  current,  and
temperature rating of the system.

• Beware  not  to  over-tighten  the  terminal  screws.  The

torque should not exceed 1 N-m (8.9 lb-in or 10 KgF-cm).

• Unused control terminals should not be used as jumper

points  as  they  may  be  internally  connected,  causing
damage to the unit.

• Verify  that  the  ratings  of  the  output  devices  and  the

inputs as specified are not exceeded.

• Except  for  thermocouple  wiring,  all  wiring  should  use

stranded copper conductor with a maximum gage of 14
AWG.

• Electrical  power  in  industrial  environments  contains  a

certain amount of noise in the form of transient voltage
and spikes. This electrical noise can adversely affect the
operation  of  microprocessor-based  controls.  For  this
reason the use of shielded thermocouple extension wire
which  connects  the  sensor  to  the  controller  is  strongly
recommended.  This  wire  is  a  twisted-pair  construction
with  foil  wrap  and  drain  wire.  The  drain  wire  is  to  be
attached to ground in the control panel only.

General Operation

Adjust the digital set point to the temperature desired. The
“OUT”  lamp  will  glow  red,  indicating  that  the  control  is
calling  for  heat,  and  the  relay  is  closed.  As  the  process
temperature  approaches  the  set  point,  the  control  will
begin to cycle the heaters on and off. When the heater load
is  turned  off,  the  “OUT”  lamp  will  not  be  lit.  The  actual
process temperature measured by the sensor is indicated
on the digital LED display.

Calibration Instructions

Calibration  is  performed  using  the  four  potentiometers
located on the bottom of the left-hand circuit board. Open
the  control  by  unlatching  the  clamps  on  the  top  and
bottom  of  the  front  of  the  control.  Allow  the  control  to
warm  up  for  at  least  half  an  hour  before  checking  the
calibration.  The  functions  of  the  potentiometers  is  as
follows:      VR1 Low scale calibration

                 VR2 Low scale switching point
                 VR3 High scale switching point
                 VR4 High scale calibration

You must set the “reset” adjustment to zero before
calibration. VR1 and VR4 affect each other, so you should
calibrate low scale and high scale at least three times each.

Alarm Operation (Optional)

The  TEC-805  has  the  option  of  coming  equipped  with  a
form-A  relay  that  can  be  used  as  a  deviation  alarm.  It  is
called  a  deviation  alarm  because  the  alarm  set  point
maintains the same deviation from the control set point, so
if the control set point is changed, the alarm set point will
change with it. The relay is rated for a maximum load of 2
amps, 240 volts. On units that have been ordered with the
alarm  option,  there  will  be  an  alarm  set  point  adjustment
on the front of the control. The alarm can be adjusted from
0–10%  of  the  range  of  the  control  from  the  set  point,  in
either  direction.  If  the  alarm  adjustment  is  set  to  the
positive side, it will act as a deviation high alarm, if it is set
to the negative side, it will act as a deviation low alarm. If
it is set at 0, the alarm will energize at the control set point.

WARNING:

Failure  of  the  thermocouple-RTD  sensor,  heater  output
relay,  temperature  control,  or  other  devices  can  result  in
severe  damage  to  a  product  while  in  process,  melting  of
the  heater,  or  a  damaging  fire.  An  over-temperature
protection  device  must  be  included  in  your  process  that
will  remove  all  power  from  the  heater  circuit  if  any  of  the
above failures occur. It is recommended that this device be
classified  as  a  safety  control.  Failure  to  install  such  a
device  where  a  potential  hazard  exists  could  result  in
damage  to  equipment  and  property,  and  injury  to
personnel.

Troubleshooting

Common causes of failures:
• Line wires improperly connected

• Incorrect voltage between line terminals

• No voltage between line terminals

• Connections to terminals are loose, open, or missing

• Short across terminals

• Shorted thermocouple leads

• Thermocouple is open at tip

• Thermocouple lead is broken

• Open or shorted heater circuit

• Open coil in external contactor

• Burned out contactor

• Burned out line fuses

• Defective line switches

• Defective circuit breakers.

If the control still does not function after these points have
been  checked,  the  instrument  should  be  returned  to
Tempco  for  inspection.  Make  sure  to  use  adequate
packing materials to prevent damage during shipment.

Note that no products returned can be accepted without a
completed Return Material Authorization (RMA) form.

Отзывы: