32
*1 The scale high/low values are defined in the following table for the parameters HSP1, LSP1, SP2, PV.HI, PV.HO, IN.LO, IN.HI,
SHIF, HSP.L, HSP.H, LSP.L, LSP.H, PV, SV, AOLO and AOHI:
Conditions
Non-linear
Linear input
Linear input
Linear input
Linear input
input
RESO = 0
RESO = 1
RESO = 2
RESO = 3
Scale low
-1999.9
-19999
-1999.9
-199.99
-19.999
Scale High
4553.6
45536
4553.6
455.36
45.536
*2 The scale high/low values are defined in the following table for O1.HY, and AL.HY:
Conditions
Non-linear
Linear input
Linear input
Linear input
Linear input
input
RESO = 0
RESO = 1
RESO = 2
RESO = 3
Scale low
0.0
0
0.0
0.00
0.000
Scale High
6553.5
65535
6553.5
655.35
65.535
7-4 Data Conversion
The word data are regarded as unsigned (positive) data in the Modbus message. However, the actual value of the parameter may be a
negative value with decimal point. The high/low scale values for each parameter are used for the purpose of such conversion.
Let
M = Value of Modbus message
A = Actual value of the parameter
SL = Scale low value of the parameter
SH = Scale high value of the parameter
M =
65535
×
(A – SL)
SH – SL
)
(
A =
SH – SL
×
(M + SL)
65535
(
)
*3: The PROG code is defined by 5.XX, where XX denotes the software version number.
For example : PROG=5.10 means the product is TEC-410 with software version 10.
*4: The least significant bit (LSB) of ALM shows the status of output 1.LSB=1 if output