background image

 
 

TMP

 

Oil Furnaces

 – 

Furnace Manual

 

6

 

 670-000-004/1010

 

2

 

Prepare furnace and place in position 

 

Inspect & prepare furnace 

Remove furnace from carton 

Remove the furnace from its shipping carton and inspect thoroughly. 
Remove access panels to inspect the furnace interior. 

Immediately file a claim with the transportation 
company if you discover concealed damage. 

Do not install or attempt to operate the furnace if the 
heat exchanger, burner or controls have been 
damaged. Immediately contact your furnace 
supplier. Operating a damaged furnace could result 
in severe personal injury, death or substantial 
property damage. 

 

Prepare burner 

Remove the burner from its shipping carton and inspect thoroughly. 
Read the burner manual and follow instructions for preparing and 
installing the burner. 

Install the correct nozzle for the required firing rate, using the burner 
manual shipped with the burner. Follow the burner manual 
instructions for nozzle installation. Verify the correct setting of 
electrodes after nozzle and burner oil tube assembly are in place. 
 
 

 

 
 

Openings in walls, floor & ceiling 

General 

Ensure that the finished door opening to the furnace room is large 
enough to install and remove the furnace, water heater or any other 
appliances in the room. 

Before placing furnace in a closet or small room, cut all openings 
required in floor, ceiling or walls for ducts and vent. This will simplify 
the work and prevent construction dust from entering the furnace 
heat exchanger. 

Verify that all clearances to combustible construction 
and for service accessibility will be met. The vent 
must be no closer than 18 inches to any combustible 
surface unless a type “L” double-wall vent pipe is 
used or the vent is constructed per the requirements 
of the NFPA 31. Provide a ventilated thimble per all 
applicable codes where vent pipe passes through 
wall or ceiling. Failure to comply could result in 
severe personal injury, death or substantial property 
damage. 

 

Duct locations and sizing 

Verify that the size of the supply and return duct system is sufficient 
for the application. The pressure drop through the duct system must 
not exceed 0.2” water column. The total drop through the duct 
system and air conditioning condensing coil (if used) must not 
exceed 0.5” water column. 

See suggested duct sizing in this manual. For more detailed sizing 
information, refer to ACCA Manual D. 
 

 

Openings … 

(continued)

 

Supply and return ducts 

You must install a return air duct, sealed to the furnace, even if no 
return manifold is used. Cut the required opening for the supply air 
duct in the floor of the room before placing the furnace. 

Verify that the filter will be easily accessible for 
removal after the furnace is in place. 

 
 
 
 
 

Install furnace and burner 

Place furnace 

Place the furnace in the desired location. Measure clearances and 
verify per page 3 or table 1 of this manual. 

Level the furnace using a spirit level on the front and one side. 
 

Inspect combustion chamber 

Inspect the combustion chamber. Verify that it is in good condition 
and correctly positioned inside the heat exchanger. The burner 
opening in the chamber must align with the burner heat exchanger 
opening. 

The combustion chamber is constructed of ceramic 
fiber materials. See the WARNING information on 
page 21 of this manual. Comply with these 
instructions when handling any ceramic fiber or 
fiberglass materials. Failure to adhere to these 
guidelines could result in severe personal injury or 
death. 

 

Insert burner 

Following the burner manual instructions, install the burner and its 
gasket in the burner opening. Make sure the burner passes through 
the opening in the combustion chamber and does not protrude more 
than ¼ inch into the chamber. 

Secure the burner in place with the four nuts and washers provided. 
Wire and pipe fuel to the burner as per the burner manual and this 
manual. 
 

Burner orientation 

For a horizontal installation, you must turn the burner 90

o

, to the 

normal orientation. Always keep the motor shaft in horizontal 
position. 

Содержание TMP-105

Страница 1: ...by the consignee Do not store or use gasoline or other flammable liquids or vapors near this furnace or any other appliance Ventilate house while operating furnace for the first time Odors may be emi...

Страница 2: ...ure of gasoline and oil waste fuel refuse or any other substance in the burner of furnace Installation 18 Do not block flow of combustion or ventilation air to furnace Do not block or obstruct the air...

Страница 3: ...TMP furnaces are approved for installation on non combustible floor If a combustible floor is used follow these instructions Horizontal installation on combustible floor Always keep the minimum instal...

Страница 4: ...r and fireplace When outside air is used Connect each opening directly by ducts to the outdoors or to crawl or attic space that freely connects with outdoors Size per below Through outside wall or ver...

Страница 5: ...avoid Spray cans containing chloro fluorocarbons Permanent wave solutions Chlorinated waxes cleaners Chlorine based swimming pool chemicals Calcium chloride used for thawing Sodium chloride used for w...

Страница 6: ...re personal injury death or substantial property damage Duct locations and sizing Verify that the size of the supply and return duct system is sufficient for the application The pressure drop through...

Страница 7: ...In the event that the BVSO repetitively shuts down the oil burner a qualified technician needs to evaluate the cause of this shut down Refer to the figures 3 to 5 at section 6 Wiring Diagrams and deta...

Страница 8: ...ame furnace installed with a 4 ton air conditioning evaporator coil Heating mode airflow is still 1 050 CFM Cooling mode airflow use Equation 3 4 CFM 4 x 400 1 600 CFM The larger number is 1 600 CFM c...

Страница 9: ...7 7 6 6 900 14 58 41 31 25 21 19 17 14 12 11 10 9 8 8 7 7 7 1000 16 64 45 34 28 23 20 18 15 13 11 10 9 9 8 8 7 7 1100 16 72 49 38 30 25 22 19 16 14 12 11 10 9 9 8 8 7 1200 16 54 41 33 27 24 21 17 15 1...

Страница 10: ...2 600 12 59 38 28 22 19 16 15 13 700 12 69 44 32 25 21 18 16 15 13 800 14 50 36 29 24 20 18 16 14 900 14 56 41 32 26 22 20 18 15 1000 16 63 45 35 29 24 22 19 17 15 1100 16 69 49 38 31 26 23 21 18 16 1...

Страница 11: ...t must slope upwards away from the furnace a minimum of inch per foot 2 Connection must be made above bottom of chimney to avoid blockage Vent pipe must not enter chimney far enough to cause obstructi...

Страница 12: ...use Teflon tape as an oil pipe sealant It can cause valves to fail creating hazards Use only flare fittings Do not use compression fittings Failure to comply could result in severe personal injury dea...

Страница 13: ...TMP Oil Furnaces Furnace Manual 670 000 004 1010 13 Notes...

Страница 14: ...o one red wire from BVSO 5 Connect the green ground wire to a cabinet screw Connect power wiring All wiring must conform to National Electrical Code ANSI NFPA 70 latest edition and any additional nati...

Страница 15: ...TMP Oil Furnaces Furnace Manual 670 000 004 1010 15 6 Wire furnace burner continued PLB Oil Furnaces Furnace Manual Figure 4 Wiring TMP furnaces with direct drive blowers DNS 0888 Rev E...

Страница 16: ...TMP Oil Furnaces Furnace Manual 16 670 000 004 1010 6 Wire furnace burner continued PLB Oil Furnaces Furnace Manual Figure 5 Wiring TMP furnaces with direct drive blowers DNS 0907 Rev C...

Страница 17: ...Then adjust burner for correct combustion using combustion test equipment Adjust burner for Draft 0 00 to 0 035 water column draft in furnace combustion chamber For pressure reading replace the sight...

Страница 18: ...piping and piping checked for leaks 23 Was burner sealed to furnace and nuts tightened Was burner harness securely plugged in Obtain gas tight seals at burner flange cleanout plates and or flue colle...

Страница 19: ...nozzle and electrode position Check ignition transformer output Reference burner manufacturers instructions Check tube insertion and alignment Check nozzle and electrode position Reference burner manu...

Страница 20: ...on page 21 Failure to comply could result in severe personal injury death or substantial property damage Consult with homeowner to see if there were any Check sequence of operation problems with furna...

Страница 21: ...it in a plastic bag for disposal Wash potentially contaminated clothes separately from other clothing Rinse clothes washer thoroughly NIOSH stated First Aid Eye Irrigate immediately Breathing Fresh ai...

Страница 22: ...removing the electrical wires remove the thermal switch and remove any build up from the thermal switch surface D Do not dent or scratch the surface of the thermal switch If the thermal switch is dam...

Страница 23: ...TMP Oil Furnaces Furnace Manual 670 000 004 1010 23 11 Components and replacement parts Figure 7 Model TMP furnaces Component locations B50098 Rev A...

Страница 24: ...panel insulation B30570 27A Front right baffle B30569 01 27B Front left baffle B30569 02 28 Bottom front panel assembly item 29 included B30774 01 29 Bottom front panel insulation B30773 30 Washer 3 8...

Страница 25: ...ture rise quantity load ampacity for fuse size weight o F and size amps wiring sizing amps pounds TMP 105 55 70 1 20 X 20 115 60 1 12 2 13 7 15 202 Model Volt Hertz Phase DNS 0908 Rev A BTU h BTU h GP...

Страница 26: ...0 60 Bar 0 75 0 75 CARLIN BURNER EZ 1 Tube insertion 5 3 16 TMP 105 0 4 0 3 Model Input TMP 105 BECKETT BURNER Model AFG 3450 RPM Tube insertion 5 1 8 Input Model Firing rate USGPH Nozzle Delavan Hea...

Страница 27: ...om thermostat 2 If the furnace oil burner should shut down on flame failure the burner primary control will lock out Ask your service technician to show you the correct procedure to reset the primary...

Страница 28: ...TMP Oil Furnaces Furnace Manual X40105 Rev K...

Отзывы: