background image

6

78570

Installation

Unpacking

Open the carton and remove the logs and the chassis.  Re-
move each of the logs by gripping at either end of the log while
avoiding any undue pressure.  Please note that the logs have
been marked for positive identification.

The carton for all models contains the following:  grate/burner
assembly, front and rear logs, 2 top twigs, 2 screws, a bag of
volcanic ash and a bag of embers.

Fireplace Preparation

The fireplace needs to be prepared before installing the unit:

A. Turn off the gas supply if the gas line has been run to the

fireplace.

B. WARNING:  Before installing logs in fireplace, the

chimney flue and firebox must be cleaned of soot,
creosote, ashes and loose paint by a qualified chimney
cleaner or sooting will occur.

Note:  If your fireplace has been cleaned using chemicals or
solvents, these products may have been absorbed into the
fireplace hearth and walls and will be burned off during the
initial break-in period.

C. Any outside air ducts and/or ash dumps in the fireplace shall

be permanently closed and sealed at the time of appliance
installation.  This will prevent drafts from disturbing the
flames and interfering with complete combustion of the gas
fuel.

Location

When gas logs are to be installed in a fireplace, inspect the
area surrounding it for possible air drafts that may affect the
flames and possibly cause sooting.  Such drafts may be caused
by a ceiling fan near the fireplace, a hot air furnace register or
an open door.  When burning the logs, carefully observe the
effect of possible drafts on the flames and take appropriate
measures to eliminate them.  For example, the ceiling fan may
be cut off, the hot air register closed, etc.

Centrally locate the gas logs in the fireplace deep enough into
the firepit to accomplish an adequate draft (if use as a vented
appliance is planned).  Ensure that the front feet of the grate sit
inside the front edge of the fireplace.  Be sure fireplace meets
minimum fireplace dimensions.

To avoid any movement of the unit during operation, screw
the chassis to the floor of the fireplace using the screws
provided.  Failure to do so could cause gas leaks.

Holes are provided in the sheet metal chassis (Fig. 3) and
should be used for securing the log set. After locating the
chassis correctly in the fireplace, mark the hole positions on the
fireplace floor. Drill two 1/8” diameter holes approximately 1/2”
deep.

Use the two screws to secure the chassis to the fireplace floor.
(Fig. 3)

Clearances

NOTE: The following instructions regarding installation clear-
ances and the use and installation of a canopy apply to use of
the appliances as an unvented space heater in permitting
jurisdictions
.  When installed as a vented decorative gas
appliance, the clearances noted below and the use of a heat-
deflecting canopy are not required.

However, it is recommended that these instructions be followed
even when the appliance will be used as a vented decorative
appliance in case local codes change to allow unvented space
heaters or in the event that the flue damper is inadvertently
closed.

Clearances for unvented installation in existing fireplaces,
(jurisdiction permitting)

1. Sidewall Clearances:  Clearances from the side of the

fireplace opening to any combustible wall should not be less
than 2”.  (Fig. 4A and 4B)

2. Ceiling Clearances:  The ceiling height should not be less

than 62" from the top of the fireplace opening.  (Fig. 4A)

3. Mantel Clearances:  The use of a canopy* is optional

depending on mantel clearances to the fireplace opening
and projection profile.

NOTE:  Mantel clearances may differ for each vent-free
firebox.  Refer to the firebox installation instructions for
clearances.

A. Mantel profile:  The minimum distance above the

fireplace opening to combustible material projecting 1

¹⁄₂

"

(tile moldings, breast boards, etc.) is 12

¹⁄₂

".

Combustible material projecting 6" (a mantel shelf, for
example) requires a minimum clearance of 19" above the
fireplace opening.  Required clearance varies with the
amount of projection. (Fig. 4C)

The mantel profile must fall within the cross-section
shown in Figures 4C or 4D.

B. Heat resistant material:  Any heat resistant material

suitable for a continuous operating temperature of 120

°

C

(248

°

F) must cover the wall surface directly above the

fireplace opening and extend the full width of the
fireplace opening for a distance of 10" above the
opening.  (Fig. 4C)

Fig. 3  Use two (2) screws to secure the chassis to the fireplace
floor.

T131a

Содержание VFL34MN

Страница 1: ...es air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Section Provisions For Adequate Combustion and Ventilation Air Page 4 FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do n...

Страница 2: ...ighting 13 Flame Check 13 Managing Heat Output 14 Maintenance Cleaning 14 Troubleshooting 15 Servicing 15 Repair Parts 16 Warranty Information 17 Installation and Startup Checklist 18 Warranty Registration 20 Table of Contents Minimum Dimensions for Existing Solid Fuel Burning Fireplaces This appliance may be installed in an aftermarket permanently located manufactured mobile home where not prohib...

Страница 3: ...DO NOT use this heater in recreational vehicles bedrooms or bathrooms If this is the ONLY gas appliance we recommend a minimum 200 pound cylinder with a fill gauge Use of a 100 pound cylinder is not recommended Other household gas appliances may require the tank size to be larger Do not operate the vent free heater if the fuel level in the propane tank is below 1 4 full DO NOT use this heater if a...

Страница 4: ...e Example Space size 25 length x 25 width x 8 ceiling height 5 000 cu ft volume of space If additional ventilation from adjoining room s is supplied with grills or doorless openings add the volume of these rooms to compute the total volume of the applicable space 2 Divide the space volume by 50 cubic feet to determine the maximum BTU Hr the space can support ________ volume of space 50 cu ft Maxim...

Страница 5: ...onal Fuel Gas Code NFPA 54 ANSI Z223 1 Section 5 3 Air for Combustion and Ventilation for required size of ventilation grills or ducts IMPORTANT Do not provide openings for inlet or outlet air into attic if attic has a thermostat controlled power vent Heated air entering the attic will activate the power vent L W D Flue Damper Closed for Unvented Operation and Maximum Heat Output Flue Damper Locke...

Страница 6: ... do so could cause gas leaks Holes are provided in the sheet metal chassis Fig 3 and should be used for securing the log set After locating the chassis correctly in the fireplace mark the hole positions on the fireplace floor Drill two 1 8 diameter holes approximately 1 2 deep Use the two screws to secure the chassis to the fireplace floor Fig 3 Clearances NOTE The following instructions regarding...

Страница 7: ...ol valve gas line inlet The inlet to these units is 1 2 NPT If installation is for L P gas have L P installer use two stage regulation and make all connections from storage tank to heater Refer to the National Fuel Gas Code for the proper supply tank size with the Btu s Hr requirements If this is the ONLY gas appliance we recommend a minimum 200 pound cylinder with a fill gauge Use of a 100 pound ...

Страница 8: ... for specific requirements Piped Gas Supply Drop Manual Shut Off Valve Horizontal Ground Joint Union Tee Fitting Nipple 3 Min Cap 1 8 N P T Plugged Hole for Test Gauge Gas Valve Drop Manual Shut Off Valve Ground Joint Union Tee Fitting Nipple 3 Min Cap 1 8 N P T Plugged Hole for Test Gauge Gas Valve Tubing Gas Supply Riser Manual Shut Off Valve Ground Joint Union Tee Fitting Nipple 3 Min Cap 1 8 N...

Страница 9: ... 7 0 w c 11 0 w c Min 5 0 w c 10 8 w c Regulator Pressure 3 5 w c 10 0 w c Minimum inlet supply pressure for the purpose of input adjustment Gas Pressure Check The gas inlet pressure specified in Table 1 is the pressure where the field installed gas line connects to the gas control This is measured at the inlet test port on the gas valve in the appliance Ensure that pressure is as shown in Table 1...

Страница 10: ...c ash on burner pilot or logs 6 Platinum embers are to be placed only on top of the front burner port area Equally space emblers one layer thick Do not pile ember material over one layer thick as this does not enhance the ember appearance or improve the log set performance Fig 8 7 Flames must not impinge touch on logs WARNING Do not use more embers than those supplied with your unit Do not use emb...

Страница 11: ... connecting a wall switch thermostat or remote control use only the top and bottom control valve terminals for attachment of the wire leads do not use center terminal of terminal block Figs 9 and 10 Remote Control Information The remote receiver does not need to be secured to the VFL34R N P base but can be placed along side of the log base assembly larger fireboxes only in a wall mounted switch bo...

Страница 12: ...en smell for gas including near the floor If you smell gas STOP Follow B in the safety information above If you don t smell gas go to the next step 4 Refer to Figure 13 Locate the pilot It is positioned on the burner behind the front log and below the right twig times This will cause a spark at the pilot which will ignite the pilot gas 7 Hold the control knob for 20 seconds to prevent the flame fa...

Страница 13: ...pliance is operating WARNING The glowing ember base and all the logs are manufactured from bonded ceramic fiber This is a commonly used material in industry worldwide In the event of the logs and base being removed care should be taken not to damage the bonded material Intentional misuse of or deliberately fragmenting the material could lead to inhaling fibers and be injurious to health Insure the...

Страница 14: ...e required under normal use Dusting the front grate or the control knob panel may be required occasionally Do not use any cleaning fluids to clean the logs or any other part of the appliance If the flames show any unusual shapes or behavior or if the burner s fail to ignite properly then the burner holes may require cleaning If this occurs contact your nearest dealer to get the appliance serviced ...

Страница 15: ...lace assembly Ignitor cable pinched or broken Free ignitor cable if damaged replace it Ignitor cable not connected to ignitor Connect cable to ignitor 2 Pilot will not stay lit Partially clogged ODS pilot orifice Contact qualified service person or your gas company Corrosion of thermocouple contact Clean thermocouple contact Bad gas valve Replace gas valve Control knob not pressed in long After pi...

Страница 16: ...78439 1 Air Scoop 78445 78445 1 Valve Natural 55463 1 Valve LP Propane 55462 1 Burner Natural 78474 1 Burner LP Propane 78473 1 Pilot Natural OP 78167 1 Pilot LP Propane OP 78169 1 Manifold Tube Split Nut 78456 78456 1 Orifice 31 Natural 78458 1 Orifice 50 LP Propane 78451 1 Tube Flexible Gas Inlet 71598 71598 1 Tube Pilot 3 16 78583 78583 1 Ignitor w Nut Piezo 65180 65180 1 Wire Assembly Rocker S...

Страница 17: ...allation instructions and in compliance with local codes and ordinances The logs must be placed strictly in accor dance with the arrangement described in the installation instructions The Product must be operated and maintained according to the instructions furnished Alteration of the Product in any way is prohibited and voids any and all war ranties Removal of the data plate alters the Products a...

Страница 18: ...rners as well as proper appearance of flames Verify that ceramic fiber and refractory components are properly positioned and secure Rear burner must not contact logs Verify adequate clearance to mantels and other combustibles Demonstrate correct operation of the product to the consumer NOTE LP models must not be operated if fuel tank is less than 1 4 full Observe the consumer operating the product...

Страница 19: ...burners as well as proper appearance of flames Verify that ceramic fiber and refractory components are properly positioned and secure Rear burner must not contact logs Verify adequate clearance to mantels and other combustibles Demonstrate correct operation of the product to the consumer NOTE LP models must not be operated if fuel tank is less than 1 4 full Observe the consumer operating the produ...

Страница 20: ...er your warranty please provide the information indicated on this form and mail it to TEMCO Fireplace Products Attn Warranty Registration 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 Model ______________________________________ I certify that I have followed all codes and regulations and adhered to the TEMCO installation instructions I have completed the proper installation and startup chec...

Отзывы: