background image

6

76683

Installation

Unpacking

Open both cartons and remove the logs and the chassis.
Remove each of the logs by gripping at either end of the log
while avoiding any undue pressure.  Please note that the logs
have been marked for positive identification.

The cartons for all models contain the following:  grate/burner
assembly, front, middle and rear logs, top twig, 2 screws, 2
brackets  and a bag of volcanic ash.

Fireplace Preparation

The fireplace needs to be prepared before installing the unit:

A. Turn off the gas supply if the gas line has been run to the

fireplace.

B. WARNING:  Before installing logs in fireplace, the

chimney flue and firebox must be cleaned of soot,
creosote, ashes and loose paint by a qualified chimney
cleaner or sooting will occur.

Note:  If your fireplace has been cleaned using chemicals or
solvents, these products may have been absorbed into the
fireplace hearth and walls and will be burned off during the
initial break-in period.

C. Any outside air ducts and/or ash dumps in the fireplace shall

be permanently closed and sealed at the time of appliance
installation.  This will prevent drafts from disturbing the
flames and interfering with complete combustion of the gas
fuel.

Location

When gas logs are to be installed in a fireplace, inspect the
area surrounding it for possible air drafts that may affect the
flames and possibly cause sooting.  Such drafts may be caused
by a ceiling fan near the fireplace, a hot air furnace register or
an open door.  When burning the logs, carefully observe the
effect of possible drafts on the flames and take appropriate
measures to eliminate them.  For example, the ceiling fan may
be cut off, the hot air register closed, etc.

Centrally locate the gas logs in the fireplace deep enough into
the firepit to accomplish an adequate draft (if use as a vented
appliance is planned).  Ensure that the front feet of the grate sit
inside the front edge of the fireplace.  Be sure fireplace meets
minimum fireplace dimensions.

To avoid any movement of the unit during operation, screw
the chassis to the floor of the fireplace using the screws
provided.  Failure to do so could cause gas leaks.

Holes are provided just behind the front grate legs and should
be used for securing the log set. After locating the chassis
correctly in the fireplace, mark the hole positions on the
fireplace floor. Drill two 1/8” diameter holes approximately 1/2”
deep.

Use the two screws to secure the chassis to the fireplace floor.
(Fig. 3)

Clearances

NOTE: The following instructions regarding installation clear-
ances and the use and installation of a canopy apply to use of
the appliances as an unvented space heater in permitting
jurisdictions
.  When installed as a vented decorative gas
appliance, the clearances noted below and the use of a heat-
deflecting canopy are not required.

However, it is recommended that these instructions be followed
even when the appliance will be used as a vented decorative
appliance in case local codes change to allow unvented space
heaters or in the event that the flue damper is inadvertently
closed.

Clearances for unvented installation in existing fireplaces,
(jurisdiction permitting)

1. Sidewall Clearances:  Clearances from the side of the

fireplace opening to any combustible wall should not be less
than 2”.  (Fig. 4A and 4B)

2. Ceiling Clearances:  The ceiling height should not be less

than 62" from the top of the fireplace opening.  (Fig. 4A)

3. Mantel Clearances:  The use of a canopy* is optional

depending on mantel clearances to the fireplace opening
and projection profile.

NOTE:  Mantel clearances may differ for each vent-free
firebox.  Refer to the firebox installation instructions for
clearances.

A. Mantel profile:  The minimum distance above the

fireplace opening to combustible material projecting 1

¹⁄₂

"

(tile moldings, breast boards, etc.) is 12

¹⁄₂

".

Combustible material projecting 6" (a mantel shelf, for
example) requires a minimum clearance of 19" above the
fireplace opening.  Required clearance varies with the
amount of projection. (Fig. 4C)

The mantel profile must fall within the cross-section
shown in Figures 4C or 4D.

B. Heat resistant material:  Any heat resistant material

suitable for a continuous operating temperature of 120

°

C

(248

°

F) must cover the wall surface directly above the

fireplace opening and extend the full width of the
fireplace opening for a distance of 10" above the
opening.  (Fig. 4C)

Fig. 3  Use two (2) screws to secure the chassis to the fireplace
floor.

Chassis Hole
Location

T152

Содержание PS24RN

Страница 1: ...from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Section Provisions For Adequate Combustion and Ventilation Air Page 4 FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any e...

Страница 2: ...nt Safeguards 14 Flame Check 14 Managing Heat Output 15 Maintenance Cleaning 15 Troubleshooting 16 Servicing 16 Repair Parts 16 Warranty Information 19 Installation and Startup Checklist 20 Warranty Registration 22 Table of Contents Minimum Dimensions for Existing Solid Fuel Burning Fireplaces This appliance may be installed in an aftermarket permanently located manufactured mobile home where not ...

Страница 3: ...ional vehicles bedrooms or bathrooms If this is the ONLY gas appliance we recommend a minimum 200 pound cylinder with a fill gauge Use of a 100 pound cylinder is not recommended Other household gas appliances may require the tank size to be larger Do not operate the vent free heater if the fuel level in the propane tank is below 1 4 full DO NOT use this heater if any part of it has been submerged ...

Страница 4: ...e Example Space size 25 length x 25 width x 8 ceiling height 5 000 cu ft volume of space If additional ventilation from adjoining room s is supplied with grills or doorless openings add the volume of these rooms to compute the total volume of the applicable space 2 Divide the space volume by 50 cubic feet to determine the maximum BTU Hr the space can support ________ volume of space 50 cu ft Maxim...

Страница 5: ...onal Fuel Gas Code NFPA 54 ANSI Z223 1 Section 5 3 Air for Combustion and Ventilation for required size of ventilation grills or ducts IMPORTANT Do not provide openings for inlet or outlet air into attic if attic has a thermostat controlled power vent Heated air entering the attic will activate the power vent L W D Flue Damper Closed for Unvented Operation and Maximum Heat Output Flue Damper Locke...

Страница 6: ...d cause gas leaks Holes are provided just behind the front grate legs and should be used for securing the log set After locating the chassis correctly in the fireplace mark the hole positions on the fireplace floor Drill two 1 8 diameter holes approximately 1 2 deep Use the two screws to secure the chassis to the fireplace floor Fig 3 Clearances NOTE The following instructions regarding installati...

Страница 7: ...plies Gas Line Connection If installation is for L P gas have L P installer use two stage regulation and make all connections from storage tank to heater Refer to the National Fuel Gas Code for the proper supply tank size with the Btu s Hr requirements If this is the ONLY gas appliance we recommend a minimum 200 pound cylinder with a fill gauge Use of a 100 pound cylinder is not recommended Other ...

Страница 8: ...e Ground Joint Union Tee Fitting Nipple 3 Min Cap 1 8 N P T Plugged Hole for Test Gauge Gas Valve Riser Horizontal Piped Gas Supply Piped Gas Supply 1 All bends in metallic tubing should be smooth elbows are recommended 2 CAUTION Shut off the main gas supply before removing end cap to prevent gas from filling the work area Test for gas leakage when installation is complete T130 Under no circumstan...

Страница 9: ... 7 0 w c 11 0 w c Min 5 0 w c 10 8 w c Regulator Pressure 3 5 w c 10 0 w c Minimum inlet supply pressure for the purpose of input adjustment Gas Pressure Check The gas inlet pressure specified in Table 1 is the pressure where the field installed gas line connects to the gas control This is measured at the inlet test port on the gas valve in the appliance Ensure that pressure is as shown in Table 1...

Страница 10: ...must be positioned as illustrated The top twig may be positioned as shown in either Figure 7 or Figure 8 The top twig must be placed in the notches provided on top of the rear and center logs The front of the top twig is to rest of the large knot on the front log CAUTION Proper location is critical When positioning the log set make sure that the logs do not interfere with the sides of the fireplac...

Страница 11: ...d in a location suitable to you The thermostat wire should be routed from the wall box to the log set and should be routed underneath the log set and pulled up to the valve s wiring terminal as shown in Fig 9 The two wires letter A should not be removed or changed Remove switch wires Letter B The two female ends of your wire can be connected to the two outer connections just below the screw termin...

Страница 12: ...me control knob T155 T147 Fig 14 Terminal connection side view T148a Fig 15 Existing valve wiring B B A T148 Fig 16 Attach remote receiver terminals to out two connec tors A Existing valve wiring Do not tamper with B Remote receiver wires red or white on either side Side View Top View T156 Fig 17 Terminal ends ...

Страница 13: ...o turn off the gas supply depress the knob slightly and turn clockwise to the OFF position 3 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety information above If you don t smell gas go to the next step 4 Refer to Figure 19 Locate the pilot It is at the right side of the burner 5 Refer to Figure 20 Push in the control...

Страница 14: ...umes etc can cause burner damage and or produce strong odors If the fireplace is equipped with glass doors the doors must be fully open when the gas appliance is operating WARNING The glowing ember base and all the logs are manufactured from bonded ceramic fiber This is a commonly used material in industry worldwide In the event of the logs and base being removed care should be taken not to damage...

Страница 15: ... cleaning should be carried out when the appliance is cold Only limited cleaning will be required under normal use Dusting the front grate or the control knob panel may be required occasionally Do not use any cleaning fluids to clean the logs or any other part of the appliance If the flames show any unusual shapes or behavior or if the burner s fail to ignite properly then the burner holes may req...

Страница 16: ...in while Press in control knob while in pilot position in pilot position Ignitor did not spark Ignitor electrode positioned wrong Correct electrode position Ignitor electrode broken Replace assembly Ignitor cable pinched or broken Free ignitor cable if damaged replace it Ignitor cable not connected to ignitor Connect cable to ignitor 2 Pilot will not stay lit Partially clogged ODS pilot orifice Co...

Страница 17: ...8 Tube Pilot 78329 78329 1 9 Valve Bracket 76388 76388 2 10 Gas Valve 55463 55462 1 11 Ignitor w Nut Piezo 65180 65180 1 12 Wire Ignitor AD Common 74017 74017 1 13 Mini Rocker Switch PCOA049 PCOA049 1 Wire Assy Rocker Switch 75435 75435 1 14 Manifold Tube Split Nut 76519 76519 1 15 Manifold Tube Split Nut 76520 76520 1 16 Injector 41 Natural 76773 1 17 Injector 49 Natural 76771 1 18 Injector 1 45 ...

Страница 18: ...71867 71867 1 Lava Gravel Assy 20000198 20000198 1 Ember Coals 74511 74511 1 24 Log Kit PL24 PL24 1 27 Front Log 24 75974 75974 1 28 Middle Log 24 75973 75973 1 29 Rear Log 24 75972 75972 1 30 Twig 24 or 28 76398 76398 1 28 Log Kit PL28 PL28 Front Log 28 76839 76839 1 Middle Log 28 76840 76840 1 Rear Log 28 76894 76894 1 30 Twig 24 or 28 76398 76398 1 ...

Страница 19: ...allation instructions and in compliance with local codes and ordinances The logs must be placed strictly in accor dance with the arrangement described in the installation instructions The Product must be operated and maintained according to the instructions furnished Alteration of the Product in any way is prohibited and voids any and all war ranties Removal of the data plate alters the Products a...

Страница 20: ...rners as well as proper appearance of flames Verify that ceramic fiber and refractory components are properly positioned and secure Rear burner must not contact logs Verify adequate clearance to mantels and other combustibles Demonstrate correct operation of the product to the consumer NOTE LP models must not be operated if fuel tank is less than 1 4 full Observe the consumer operating the product...

Страница 21: ...burners as well as proper appearance of flames Verify that ceramic fiber and refractory components are properly positioned and secure Rear burner must not contact logs Verify adequate clearance to mantels and other combustibles Demonstrate correct operation of the product to the consumer NOTE LP models must not be operated if fuel tank is less than 1 4 full Observe the consumer operating the produ...

Страница 22: ...er your warranty please provide the information indicated on this form and mail it to TEMCO Fireplace Products Attn Warranty Registration 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 Model ______________________________________ I certify that I have followed all codes and regulations and adhered to the TEMCO installation instructions I have completed the proper installation and startup chec...

Отзывы: