background image

15

76683

Managing Heat Output

The heat output from the appliance can be controlled by the
position of the flue damper on vented fireplaces.

The damper setting should be fully closed for maximum heat
output, partially closed for less heat output and fully open for
minimum heat output.

The appliance may be used in a working solid fuel burning
fireplace with the fuel damper closed only if unvented appli-
ances are permitted by local state and city codes.  It may also
be operated as a decorative appliance whose prime function
lies in the aesthetic effect of the flames when installed in a solid
fuel burning fireplace with the flue damper open.  If unvented
heaters are not permitted, the fireplace vent damper must be
locked at a minimum free (vent) area of 15 sq. ins.

Whenever the appliance is operated with the fireplace's
flue damper closed, glass doors - if present - must be open
and the outside air damper and the ash dump (if the
fireplace is equipped with either one) must be closed.

The heat output from the appliance when operated as a vent-
free heater may be controlled by adjusting the main gas valve
and by turning the front (blue flame) burner on or off. Reference
lighting instructions on Page 11 and chart on Page 3 which
shows inputs at all settings.

The main gas valve may be adjusted anywhere between high
and low to give the desired combination of flame aesthetics and
heat output. The blue flame front burner control must be turned
fully to either the “ON” or “OFF” position.

Maintenance

Cleaning

CAUTION:  Before cleaning or moving logs or other parts of the
unit, be sure to read the section on important safeguards.

Cleaning should be done before the logs are used each year
and after long periods of non-use.  Professional servicing is
recommended.

All cleaning should be carried out when the appliance is cold.

Only limited cleaning will be required under normal use.
Dusting the front grate or the control knob panel may be
required occasionally.  Do not use any cleaning fluids to clean
the logs or any other part of the appliance.

If the flames show any unusual shapes or behavior, or if the
burner(s) fail to ignite properly, then the burner holes may
require cleaning.  If this occurs contact your nearest dealer to
get the appliance serviced.

Alternatively, the appliance can be cleaned by removing the
logs.  Handle the logs gently so as not to damage them.
Always lift each log by holding it carefully at each end.

After the logs are removed allowing access to the burner area,
use the brush attachment from your vacuum cleaner to carefully
remove dust and loose particles from the base, logs and from
around the burner.  Gloves are recommended when handling
the logs.  Use extreme caution when cleaning around the pilot
(ODS).  The pilot should not be moved or altered from the
original factory setting (Pilot to burner preset location).  To clean
the pilot, take an Air Duster can (computer cleaner compressed
air) and insert the nozzle into the primary air inlet.  Shoot a
short blast of air into the inlet to clear dust. (Fig. 26)  The burner
should not be removed or taken out of it’s locked and secure
position (proper location of burners are critical).

Logs must be carefully replaced in their orignial, preset posi-
tions, as shown in Figure 27, to prevent the rear flames from
touching any log.  No other arrangement is permitted.  Incorrect
placement can diminish combustion efficiency and cause
sooting.

A qualified gas professional should periodically check and clean
the orifices and burners per National Fuel Gas Code, Appendix
B.

Lack of proper maintenance may void warranty.

Gas
Outlet

Primary Air
Inlet

T135

Fig. 26  Use a short burst of air into the primary air inlet to clean
pilot.

Fig. 27  Correct log placement, top view.

TL110

Содержание PS24RN

Страница 1: ...from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Section Provisions For Adequate Combustion and Ventilation Air Page 4 FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any e...

Страница 2: ...nt Safeguards 14 Flame Check 14 Managing Heat Output 15 Maintenance Cleaning 15 Troubleshooting 16 Servicing 16 Repair Parts 16 Warranty Information 19 Installation and Startup Checklist 20 Warranty Registration 22 Table of Contents Minimum Dimensions for Existing Solid Fuel Burning Fireplaces This appliance may be installed in an aftermarket permanently located manufactured mobile home where not ...

Страница 3: ...ional vehicles bedrooms or bathrooms If this is the ONLY gas appliance we recommend a minimum 200 pound cylinder with a fill gauge Use of a 100 pound cylinder is not recommended Other household gas appliances may require the tank size to be larger Do not operate the vent free heater if the fuel level in the propane tank is below 1 4 full DO NOT use this heater if any part of it has been submerged ...

Страница 4: ...e Example Space size 25 length x 25 width x 8 ceiling height 5 000 cu ft volume of space If additional ventilation from adjoining room s is supplied with grills or doorless openings add the volume of these rooms to compute the total volume of the applicable space 2 Divide the space volume by 50 cubic feet to determine the maximum BTU Hr the space can support ________ volume of space 50 cu ft Maxim...

Страница 5: ...onal Fuel Gas Code NFPA 54 ANSI Z223 1 Section 5 3 Air for Combustion and Ventilation for required size of ventilation grills or ducts IMPORTANT Do not provide openings for inlet or outlet air into attic if attic has a thermostat controlled power vent Heated air entering the attic will activate the power vent L W D Flue Damper Closed for Unvented Operation and Maximum Heat Output Flue Damper Locke...

Страница 6: ...d cause gas leaks Holes are provided just behind the front grate legs and should be used for securing the log set After locating the chassis correctly in the fireplace mark the hole positions on the fireplace floor Drill two 1 8 diameter holes approximately 1 2 deep Use the two screws to secure the chassis to the fireplace floor Fig 3 Clearances NOTE The following instructions regarding installati...

Страница 7: ...plies Gas Line Connection If installation is for L P gas have L P installer use two stage regulation and make all connections from storage tank to heater Refer to the National Fuel Gas Code for the proper supply tank size with the Btu s Hr requirements If this is the ONLY gas appliance we recommend a minimum 200 pound cylinder with a fill gauge Use of a 100 pound cylinder is not recommended Other ...

Страница 8: ...e Ground Joint Union Tee Fitting Nipple 3 Min Cap 1 8 N P T Plugged Hole for Test Gauge Gas Valve Riser Horizontal Piped Gas Supply Piped Gas Supply 1 All bends in metallic tubing should be smooth elbows are recommended 2 CAUTION Shut off the main gas supply before removing end cap to prevent gas from filling the work area Test for gas leakage when installation is complete T130 Under no circumstan...

Страница 9: ... 7 0 w c 11 0 w c Min 5 0 w c 10 8 w c Regulator Pressure 3 5 w c 10 0 w c Minimum inlet supply pressure for the purpose of input adjustment Gas Pressure Check The gas inlet pressure specified in Table 1 is the pressure where the field installed gas line connects to the gas control This is measured at the inlet test port on the gas valve in the appliance Ensure that pressure is as shown in Table 1...

Страница 10: ...must be positioned as illustrated The top twig may be positioned as shown in either Figure 7 or Figure 8 The top twig must be placed in the notches provided on top of the rear and center logs The front of the top twig is to rest of the large knot on the front log CAUTION Proper location is critical When positioning the log set make sure that the logs do not interfere with the sides of the fireplac...

Страница 11: ...d in a location suitable to you The thermostat wire should be routed from the wall box to the log set and should be routed underneath the log set and pulled up to the valve s wiring terminal as shown in Fig 9 The two wires letter A should not be removed or changed Remove switch wires Letter B The two female ends of your wire can be connected to the two outer connections just below the screw termin...

Страница 12: ...me control knob T155 T147 Fig 14 Terminal connection side view T148a Fig 15 Existing valve wiring B B A T148 Fig 16 Attach remote receiver terminals to out two connec tors A Existing valve wiring Do not tamper with B Remote receiver wires red or white on either side Side View Top View T156 Fig 17 Terminal ends ...

Страница 13: ...o turn off the gas supply depress the knob slightly and turn clockwise to the OFF position 3 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety information above If you don t smell gas go to the next step 4 Refer to Figure 19 Locate the pilot It is at the right side of the burner 5 Refer to Figure 20 Push in the control...

Страница 14: ...umes etc can cause burner damage and or produce strong odors If the fireplace is equipped with glass doors the doors must be fully open when the gas appliance is operating WARNING The glowing ember base and all the logs are manufactured from bonded ceramic fiber This is a commonly used material in industry worldwide In the event of the logs and base being removed care should be taken not to damage...

Страница 15: ... cleaning should be carried out when the appliance is cold Only limited cleaning will be required under normal use Dusting the front grate or the control knob panel may be required occasionally Do not use any cleaning fluids to clean the logs or any other part of the appliance If the flames show any unusual shapes or behavior or if the burner s fail to ignite properly then the burner holes may req...

Страница 16: ...in while Press in control knob while in pilot position in pilot position Ignitor did not spark Ignitor electrode positioned wrong Correct electrode position Ignitor electrode broken Replace assembly Ignitor cable pinched or broken Free ignitor cable if damaged replace it Ignitor cable not connected to ignitor Connect cable to ignitor 2 Pilot will not stay lit Partially clogged ODS pilot orifice Co...

Страница 17: ...8 Tube Pilot 78329 78329 1 9 Valve Bracket 76388 76388 2 10 Gas Valve 55463 55462 1 11 Ignitor w Nut Piezo 65180 65180 1 12 Wire Ignitor AD Common 74017 74017 1 13 Mini Rocker Switch PCOA049 PCOA049 1 Wire Assy Rocker Switch 75435 75435 1 14 Manifold Tube Split Nut 76519 76519 1 15 Manifold Tube Split Nut 76520 76520 1 16 Injector 41 Natural 76773 1 17 Injector 49 Natural 76771 1 18 Injector 1 45 ...

Страница 18: ...71867 71867 1 Lava Gravel Assy 20000198 20000198 1 Ember Coals 74511 74511 1 24 Log Kit PL24 PL24 1 27 Front Log 24 75974 75974 1 28 Middle Log 24 75973 75973 1 29 Rear Log 24 75972 75972 1 30 Twig 24 or 28 76398 76398 1 28 Log Kit PL28 PL28 Front Log 28 76839 76839 1 Middle Log 28 76840 76840 1 Rear Log 28 76894 76894 1 30 Twig 24 or 28 76398 76398 1 ...

Страница 19: ...allation instructions and in compliance with local codes and ordinances The logs must be placed strictly in accor dance with the arrangement described in the installation instructions The Product must be operated and maintained according to the instructions furnished Alteration of the Product in any way is prohibited and voids any and all war ranties Removal of the data plate alters the Products a...

Страница 20: ...rners as well as proper appearance of flames Verify that ceramic fiber and refractory components are properly positioned and secure Rear burner must not contact logs Verify adequate clearance to mantels and other combustibles Demonstrate correct operation of the product to the consumer NOTE LP models must not be operated if fuel tank is less than 1 4 full Observe the consumer operating the product...

Страница 21: ...burners as well as proper appearance of flames Verify that ceramic fiber and refractory components are properly positioned and secure Rear burner must not contact logs Verify adequate clearance to mantels and other combustibles Demonstrate correct operation of the product to the consumer NOTE LP models must not be operated if fuel tank is less than 1 4 full Observe the consumer operating the produ...

Страница 22: ...er your warranty please provide the information indicated on this form and mail it to TEMCO Fireplace Products Attn Warranty Registration 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 Model ______________________________________ I certify that I have followed all codes and regulations and adhered to the TEMCO installation instructions I have completed the proper installation and startup chec...

Отзывы: