29
Temco DV5200, DV6400DSN/DSP Series
77794
1
2
3
4
Regulator
Fitting
T210
Fig. 41 White-Rodgers 25M18A-706PI gas control.
6. With the main burner burning, read the pressure on
the manometer or pressure gauge. The pressure on
the gauge should read between 9.8” and 10.2” w.c.
7. Turn off the gas supply. Turn off the electrical
supply to the appliance.
8. Remove the manometer or pressure gauge. Tighten
the screw in the pressure tap.
9. Turn on the gas supply. Turn on the electrical
supply to the appliance.
10. Immediately test all gas line connections and the
control valve for gas leaks using a soap and water
solution or other gas detection solution. Bubbles
indicate a leak that MUST be corrected. Do not use
an open flame to test for gas leaks.
11. Using a ball point pen, fill out the conversion label
that is supplied with the conversion kit. Place the
conversion label adjacent to the rating plate.
A
Air Shutter Settings
Model
Opening A
DV5200DSP
7/16” (11mm)
DV6400DSP
7/16” (11mm)
Fig. 42 Correct air shutter settings.
NOTE: These are minimum settings. Air shutter open-
ings may be increased to prevent flame sooting.
Conversion Parts Included with Fireplace
Description
DV5200
DV6400
Orifice 1.45mm
PCOAO70H37
PCOAO70H37
Label, Conversion
77549
77549