INSTALLER MENU /
MAX POWER FROM GRID
This configuration can be used in two different
ways, depending whether you enable dynamic
load balancing or not.
1.
If you have enabled dynamic load balancing,
use this value to set the maximum current per
phase that can be supplied to the whole
electrical installation. Usually this value is the
rated current of the main circuit breaker.
2.
If dynamic load balancing is disabled, use this
value to set maximum current that an EV
charger can use depending on the other site
appliances load. That means that the current
should not be higher than 16 amperes (if an 11
kW EV charger is installed) or 32 amperes (if a
7,4 or 22 kW EV charger is installed).