5 Settings 

The module settings can be configured by PC software through USB, and the main 
parameters can also be configured remotely by SMS commands. 

5.1 Configuring through USB connection 

The programming software is available on the module’s USB drive. After connecting the 
module to USB, it will be recognized as a USB drive and also creates a USB HID device. 
Since it is a HID device, the USB connection requires no special drivers.  
 
The programming software runs on the following operating systems: 
 

 

Windows XP SP2 (32/64 bit) 

 

Windows 7 (32/64 bit) 

The language of the program interface can be selected using the language icons found 
in the lower right corner of the program window.

 

Programming: 

  Copy the programming software from the module to a suitable place on the PC. 

The software is available in the following folder: 
”Drive letter”

:\Software\Remoter\Remoter.exe

 

 Start 

the 

Remoter.exe

 programming software 

  Power up the module from external power supply. (If the module is powered only 

from USB, it establishes the connection with the software after 25 seconds and 
then it accepts programming for 2 minutes only!) 

  Connect the module to USB 

  As soon as the program connects to the module, it requests the module password, 

then a green tick icon appears next to the USB icon in the upper right corner of the 
main window: 

  Thereafter the “

Read

” and “

Write

” function buttons become available on the 

Settings

” page as well as status information on the “

Status

” page of the software. 

Configure the settings, then write them to the module using the “

Write

” button. 

Содержание DUALCOM SIA IP

Страница 1: ...DUALCOMSIA IP INSTALLATION AND APPLICATION MANUAL for module version V1 20 1837 and up Document version 1 61 12 08 2013...

Страница 2: ...he programming software 6 5 1 3 Phone numbers 6 5 1 4 SIM A SIM B GPRS settings 7 5 1 5 Input settings 8 5 1 6 Relay outputs 10 5 2 Configuring by SMS commands 11 5 3 Module status monitoring 13 5 3 1...

Страница 3: ...IA DC 09 2007 standard No need for a central server only an IP receiver with internet connection is necessary The module works with the following receiver types TELLMon AMR 08 and ENIGMA II 2 Function...

Страница 4: ...ferent networks and to the different remote monitoring stations in parallel Due to the parallel operation ideally each receiver receives the event roughly at the same time this is an average of 5 seco...

Страница 5: ...ram window Programming Copy the programming software from the module to a suitable place on the PC The software is available in the following folder Drive letter Software Remoter Remoter exe Start the...

Страница 6: ...nction buttons of the programming software Read read settings from the connected module Write write settings to the connected module Open load settings from file Save save settings to file 5 1 3 Phone...

Страница 7: ...gure the IP addresses in pairs which means if IP A is set B must also be set and vice versa Primary 1A 2A the primary receivers belonging to SIM A network Primary 1B 2B the primary receivers belonging...

Страница 8: ...ow battery voltage threshold the module is able to monitor the supply voltage This function is useful when the module is powered from uninterrupted power supply provided with a backup battery recommen...

Страница 9: ...The restoration event is sent automatically upon restore for inputs according to the input sensitivity settings For inputs and tamper event the module sends the zone number 001 006 automatically accor...

Страница 10: ...f the 6 inputs is activated and remains activated as long as any input is active Indicates battery trouble the output is activated upon battery trouble and remains activated as long as the battery tro...

Страница 11: ...Command Value Superuser registration SUPERUSER registers the sender s phone number Modifying deleting the Superuser SU phone number APN assigned to SIM A APNA APN name e g internet APN user name assi...

Страница 12: ...hreshold BATH e g 12500 9000 30000 mV Restart module after 30sec RESET 1 The module sends response message about the modifications e g IP1A OK except for the superuser registration Examples Registerin...

Страница 13: ...ersion the module s hardware version Firmware version the module s firmware version System timer Date time the date and time setting of the module s internal clock Uptime the time elapsed from last mo...

Страница 14: ...ection ok ready Online ACK error IP connection ok but no acknowledgement signal is received alarm monitoring software serial connection error Offline No response no response is received from the confi...

Страница 15: ...wet places or places with high degree of humidity Connecting the GSM antenna the GSM antennas can be fixed in the FME M connectors found on the panel The antennas supplied with the module provide good...

Страница 16: ...security lock downwards towards USB connector until it clicks Check the SIM cards to be inserted properly Check the antennas to be fixed properly in the FME M connectors The device can be powered up...

Отзывы: