Telguard TG-7FP Installation & Operating Guide
15
56052401 Rev A
Appendix 1 Connection Guide
Wiring Diagrams
The following wiring diagrams show the configurations in which the TG-7FP can be used:
•
Sole Path (TG-7FP is the only communication path connected to the panel):
Cellular-Only
transmission with Link supervision
(180-sec, 5-min, or 60-min)
•
Primary or Secondary Path (another communication path is connected to the panel):
Cellular-Only transmission with self-test (6-hr or 24-hr)
Scenario 1: Sole Path (TG-7FP is the only communication path)
Used when the communicator is working in a system that does not involve a Telco connection or a
secondary path. In this case, the alarm panel is connected directly to the TG-7FP, and there is no
other connection for communication. For commercial fire installations, a specific level of link
supervision may be required (frequencies of 180 seconds, 5 minutes, or 60 minutes).
TG-7FP
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
LED 8
FACP
(Burg Panel Similar)
TRIP
INPUT
EARTH
GROUND
SIM
LTE
ANTENNA
SEE NOTE
ABOVE
NOTE: Secondary dialer must
be disabled, or connections
spliced. See Appendix 3 for
instructions.
Tamper
Switch
STC2 NOT PERMITTED
IN UL FIRE SYSTEMS