Telguard TG-7FP Installation & Operating Guide
7
56052401 Rev A
UL/ULC Compliance Notes:
•
In Fire installations, STC2 (normally closed) cannot be used for communicating with the
alarm panel; only STC1 (normally open) can be used.
•
In Burglary installations, when an alternate communications path is connected to another
alarm panel-Telco interface or DACT, an STC relay shall be programmed to trip on NSC
and wired to an available zone on the panel.
ULC Compliance Notes:
•
TG-7FP devices are suitable for use in Security Level 2 applications.
•
For commercial fire installations, only the Active/Sole Path communication shall be used.
Post-Installation Remote Programming
To continue to meet compliance requirements, once a communicator is installed it cannot be
remotely reprogrammed or receive updated firmware from Telguard Technical Support without
manual on-site intervention. To change the device settings or accept updated firmware, follow these
steps:
•
Locate and press either of the RSSI buttons on the TG-7FP, holding it for at least 5-7
seconds (use the provided tool or an unbent paper clip if using side button).
•
LED 5 will flash, indicating that a message has been sent to initiate a Maintenance Window.
•
The maintenance window will last for 10 minutes after receipt of the device message.
•
and make the necessary configuration
changes to the device, within the observed maintenance window (10 minutes).
•
No device configuration changes can be made outside of the maintenance window.
NOTE: All alarm functions and transmissions will continue to operate during the Maintenance
Window.
Diagnostic and Status LEDs
Seven active LEDs are provided as a useful aid during installation and give installers an immediate
visual indication of system status. The LEDs serve as indicators for activation, system trouble
conditions, power, and communication indicators. They can also provide a signal strength indication,
similar to the signal strength bars on a cellular phone. See Appendix 2 or the installation section for
details.
Complete Factory Reset Option
A special function within the TG-7FP allows you to perform a complete Factory Reset on the
communicator. This reset will change all communicator settings back to a factory default
configuration.
NOTE: Never attempt to do a Complete Factory Reset on an active account because the
communicator
will need to be re-activated.
To begin the factory reset, follow these steps:
•
Power cycle the device. For the first three seconds after power up, all LEDs will be lit solid.
•
While the communicator shows this pattern, press and hold either of the RSSI buttons (use
the provided tool or an unbent paper clip if using side button). After 15 seconds of button
press, the LEDs will begin to sequentially turn on and off in a cascading pattern, indicating
the factory reset is taking place.
•
Release the button. After the factory reset concludes, the LEDs will go back to normal
status.