56050301 – Rev B
18
© 2017 Telguard
AC T
ERMINAL
S
TRIP
P
IN
A
SSIGNMENTS
Terminal
Strip Pin
Definition
Connects To
Function
Status LED
Reference
1 AC
2 AC
AC power
input.
12 VAC,
10VA.
120 VAC 60Hz
un-switched
circuit.
Provides primary
operational power to
Telguard and battery
charging circuit.
AC Power LED
ON
when AC is
normal.
AC power LED
OFF
And
STC LED 2
Flashes 1 time
when AC is low
C
OMPATIBLE
A
LARM
P
ANELS
Any UL Listed Alarm Panels that supports one of the following formats is compatible and may be
used withTG-4:
Pulse Formats:
o
3+1 pulse; 10pps, Double Round, 1400Hz ack
o
3+1 pulse; 20pps, Double Round, 2300Hz ack
o
3+1 pulse; 40pps, Double Round, 2300Hz ack
o
4+2 pulse; 20pps, Double Round, 1400Hz ack
o
4+2 pulse; 20pps, Double Round, 2300Hz ack
o
4+2 pulse; 40pps, Double Round, 2300Hz ack
Contact ID
Modem IIe/IIIa
2
/4
SIA2 (SIA-DC-03 level 2 release at 300 baud)
DMP
The installer should verify the complete compatibility at the time installation.
A
PPENDIX
2 – T
ROUBLESHOOTING
G
UIDE
This section provides a summary of all LED indications and their meanings, as well as the
expected behavior of the TG-4 under various exception conditions.