background image

70

 -

TBD

 

 

 

                                 

©

2007-2020

 

A

LL RIGHTS RESERVED TO 

T

ELE

F

IRE 

F

IRE AND 

G

AS 

D

ETECTORS 

L

TD

.

                                            

R

EVISION 

1.11

 

F

EBRUARY 

2020

 

     

Page 

16 of 19 

Connection to the TeleFire panels   

 

Note 

    

24VDC supply to the detector will be provided from 24R input in

 TSA-200 / 

TSA-240 and TSA-1000 panels, and from 24V input for ADR-712 assembly.  

Make sure that the ADR-712 assembly is of software version 6 and higher. 

Do not use ADR-812A assembly to connect to addressable panels

 . 

Usually smoke that goes up starts spreading sideways at a certain distance below the 
ceiling, because of a layer of hot air that is found next to the ceiling. Therefore the 
detector has to be installed on the building wall, at least 50-cm and no more than 1-m 
below the ceiling, to meet the requirements of NFPA 72/ UL 268 and Israeli Standard IS 
1220-3, 2014 revision.  

4.1  Connection to addressable panels  

 

Drawing 1: Connection of FireBeam detector to addressable panels  

 

 

Note! 

In software version 6 and higher of the 
ADR-712, TBR-5100 reset circuit is not 
necessary. Do not use assemblies of 
software revision 5 and lower.  

Zone 

Zone 

24V supply to zones 

 

24VR supply 

 

Fire beam detector 

 

Continued 24V line to the next device 

 

Communication line to the next device 

 

Communication line to devices 
from the panel or previous 

device 

 

Connect 5.1k end-of-line resistor to 
each zone 

 

Continued 24V line to the next device 

 

Shielding 

 

Содержание FireBeam Xtra

Страница 1: ...Detector for Automatic Alignment Displacement Compensation Technical instructions TELEFIRE FIRE AND GAS DETECTORS LTD P O Box 7036 Petach Tikwa 49250 Tel 03 970 0400 Fax 03 921 1816 Email info telefir...

Страница 2: ...i Please Note Do not install operate or conduct maintenance operations in the device before reading this manual thoroughly 2007 2020 ALL RIGHTS RESERVED TO TELEFIRE FIRE AND GAS DETECTORS LTD...

Страница 3: ...ND GAS DETECTORS LTD REVISION 1 11 FEBRUARY 2020 Page 1 of 19 1 Operation range and location 1 1 Operation range FIREBEAM Xtra detectors can be installed at three distance ranges 7 70 m detector prims...

Страница 4: ...ctor on a solid and stable structure Install the detector at a level of 2 7 m minimum from the floor to prevent the passage of people and equipment through the beam Also take into account the traffic...

Страница 5: ...cting the connector and tightening it to the base with the Allen key supplied with the detector 2 2 Installation of the control unit Install the control unit at a suitable level taking into account ac...

Страница 6: ...70 TBD 2007 2020 ALL RIGHTS RESERVED TO TELEFIRE FIRE AND GAS DETECTORS LTD REVISION 1 11 FEBRUARY 2020 Page 4 of 19 2 3 Wiring...

Страница 7: ...to change language use the right and left buttons to select the desired language When you finish selecting the desired language press Enter 5 Press Enter The Normal Fast screen will be displayed In m...

Страница 8: ...n and Enter to enter a manual adjustment mode Caution If a free radius of 50 cm is impossible and the detector beam is obstructed by objects the IR intensity will stop increasing and the beam alignmen...

Страница 9: ...gnment 10 When the value of AQ is higher than 100 manually press Enter to exit manual mode and then press Enter to enter Auto Alignment mode Auto alignment is an automatic process that first reduces t...

Страница 10: ...R Cover the prims entirely and quickly If the beam is well aligned an error message will be displayed after 10 seconds The yellow fault lamp on the detector head and on the control unit will be flashi...

Страница 11: ...y reading the resistance on the grey and black terminals If connected 110 Ohm has to be shown and if disconnected the resistance will be 220 Ohm This screen is displayed when the beam conducts alignme...

Страница 12: ...Enter to enter the system menu Then press Down to browse the main menu options Press Enter to change the language Press Enter to align the detector Press Enter to set the detector settings sensitivity...

Страница 13: ...100 the message Pre Align Complete will be displayed Otherwise a too high output power was obtained because of reflection of light from an adjacent object Use the left right up and down arrow keys to...

Страница 14: ...conds In order for the beam to enter fault mode the beam has to be completely blocked within 1 second press Enter to return to Mode Change or the down arrow for Auto Reset The detector s default is Au...

Страница 15: ...such that if the beam is set to alarm mode at 65 threshold of 35 the beam intensity has to reach 15 80 before it returns to normal state This operation prevents fluctuations in the reflected signal c...

Страница 16: ...The relay will not be released before the Time to Fire expires This value can be between 2 30 seconds Press the left back arrows to end the test Fire Test will be displayed Press the left back arrows...

Страница 17: ...70 TBD 2007 2020 ALL RIGHTS RESERVED TO TELEFIRE FIRE AND GAS DETECTORS LTD REVISION 1 11 FEBRUARY 2020 Page 15 of 19...

Страница 18: ...ext to the ceiling Therefore the detector has to be installed on the building wall at least 50 cm and no more than 1 m below the ceiling to meet the requirements of NFPA 72 UL 268 and Israeli Standard...

Страница 19: ...ETECTORS LTD REVISION 1 11 FEBRUARY 2020 Page 17 of 19 4 2 Connection to TSA 1000 panel Drawing 2 Connection of Fire Beam detector to TSA 1000 panel Note When connecting a beam detector to TSA 1000 pa...

Страница 20: ...S LTD REVISION 1 11 FEBRUARY 2020 Page 18 of 19 4 3 Connection to TSA 200 TSA 240 panel Drawing 3 Connection of Fire Beam detector to TSA 200 TSA 240 panel Note When connecting a beam detector to TSA...

Страница 21: ...t Dimensions W x H x D 120 x 185 x 62 mm Weight 0 55 kg Mid range prism 40KIT80 Dimensions W x H x D 293 x 293 x 50mm Weight 0 8kg Long range prism 80KIT100 Dimensions W x H x D 394 x 394 x 5 mm Weigh...

Отзывы: