Telefire
ADR-3000 – System Introduction
Revision 1.10 4 November 2004
4 Accessories
4.1 Introduction
Telefire's ADR-3000 Analog Addressable Fire Alarm Control Panel is easily expandable
with a variety of analog addressable I/O modules. These modules allow the interfacing
of non-addressable devices such as conventional detectors, horns, relays, extinguishers,
etc., in order to take advantage of the ADR-3000’s flexibility and advanced capabilities.
All the ADR-81X and ADR-82X I/O modules are connected to the SLC analog line and
are powered from an external 24 V
DC
power source that can be supplied either from the
main control panel or a remote power supply such as Telefire’s TPS-34A Analog
Addressable Remote Power Supply. The ADR-805 connects to the SLC loop and does
not require 24 V
DC
input.
4.2 Analog Addressable Modules
4.2.1 Input
Modules
ADR-805
Flow Switch Interface
ADR-810
Single-Channel Input Module
ADR-812
Two-Channel Input Module
ADR-818
Eight-Channel Input Module
4.2.2 Output
Modules
ADR-820
Single-Channel Output Module
ADR-828
Eight-Channel Output Module
4.2.3 Multifunction
Modules
ADR-823
Three-Channel Input/Output Module
ADR-833
Automatic Extinguishing Control Unit (multi I/O)
4.2.4 Other
Accessories
LI-3000
Line Isolation Module
TIP-224A
Analog Addressable Alarm Notification Sounder – Indoor
TPS-34A
Analog Addressable Remote Power Supply
4.2.5 ADR-805 Flow Switch Interface Module
100K
EOL
ADR-805
PROG
SLC
SW. In
+L -L
+
-
The ADR-805 interfaces flow-switches or other non-powered
initiating devices.
The two-wire input connection is fully supervised and is terminated
by a 100 K
Ω
end-of-line resistor.
The ADR-805 includes an onboard indicating LED that flickers when
addressed by the control panel and latches on upon alarm.
Any device connected to the ADR-805 must be installed adjacent to
it (no further than 50 cm).
Figure 15 ADR-805 Flow Switch Interface Module
– Page 12 –