GT-FIRE
PORTABLE GAS DETECTOR
67816
Revision D
37
6.3.2. Hydrophobic Filter
Note: When replacing the hydrophobic filter, you must also replace the dust filter.
Caution: The monitor must be OFF when replacing the hydrophobic
filter. Ensure any dust / dirt falls away from the monitor.
1. Remove and discard the dust filter, as detailed in
2. Unscrew the probe adaptor, as illustrated in
Figure 44: Hydrophobic Filter Bulb Removal
.
3. Turn the hydrophobic filter bulb in an anticlockwise direction to release the bayonet connection.
Note: The hydrophobic filter is permanently attached to the hydrophobic filter bulb.
4. Inspect the hydrophobic filter for contamination or damage.
5. Fit a new Hydrophobic Filter Bulb (Part No. 67213), if required.
6. Check the probe washer and replace if damaged (part no. 12379).
Note: Do not overtighten the hydrophobic filter bulb or probe adaptor filter assembly.
7. Switch ON the monitor and check that a ‘FLOW FAULT’ is displayed when the probe inlet is
blocked (while pump is running).
8. If ‘FLOW FAULT’ is not displayed, check tightness of all fittings.
Figure 44: Hydrophobic Filter Bulb Removal