background image

Page 7

Hi-E Model EPH Pool and Spa Heater

3. A minimum of 5 inches (127 mm) W.C. for

natural gas and 11 inches (279 mm) W.C. for
propane gas, when the burner is firing, is required.

4. If the supply gas pressure is less than the mini-

mum, check for under-sized pipe between the
meter and the heater, a restrictive fitting, an under-
sized gas meter.

IMPORTANT: Any gas supply problem must be
corrected. The source of the incorrect supply pressure
must be found and corrected. If you cannot clear up
the supply pressure problem, contact a qualified
service technician or your local gas company.

3A-3. Checking the Metering Orifice

Gas flow is controlled by the orifice in the fitting

between the gas valve and the venturi throat. The
orifice must be the correct size for the fuel being used
(see Table 2).

To inspect the gas orifice:

1. Disconnect the venturi pressure tube (see Fig. 6).
2. Carefully remove the fitting between the gas valve

and the venturi throat.

3. Remove the orifice and inspect it.

4. Reassemble all parts properly after making sure the

orifice size is correct.

3A-4. Checking the Venturi Pressure Switch

The venturi pressure switch is calibrated to open

when the pressure falls below the minimum values,
shutting off the heater. If a dull blue lazy flame is
detected or it takes a long time for the heater to heat
up, the cause may be:

1. A restriction in the combustion system flow by a

partially blocked combustion air inlet or vent
terminal.

2. Excessive vent pipe length or too many 90 degree

elbows (see Document 3090B, Installation and
Operation Manual).

3. Worn or dirty combustion air filter.

4. Internal blockage in the condensate trap or drain

system.

To check the venturi pressure difference perform

the following stack test:

1. Remove upper inlet pressure tap from the top of

the venturi (see Fig. 6).

2. Attach the hose from the manometer to the upper

tap on the venturi.

NOTE: The manometer must be able to read a
negative pressure.

3. Start the heater and let the unit fire.

4. Take a reading. Readings should be:

a.

-2.2 to -3.2 inches (-56 to -81 mm) W.C. for
outdoor units with standard stack extensions.

b. - 1.4 to -3.2 inches (-36 to -81 mm) W.C. for

indoor units with proper venting.

3A-5. Checking the Air Flow (Filter)

The amount of gas that flows to the burner is

regulated by the amount of air through the venturi.
Testing pressure readings at the gas valve pressure tap
can determine if there is an air flow problem.

If the heater is heating slowly or cycling on and

off, perform the following filter test:

1. Attach a manometer or a negative pressure gauge

to the press tap opening on the gas valve.

2. Turn on the heater.

NOTE: The fan will come on and the heater will fire
about 20 to 30 seconds later.

3. Take a reading. Reading should be -0.3 to -0.5

inches (-7.6 to -12.7 mm) W.C.

4. If the reading is less than -0.3 inches (-7.6 mm)

W.C., check the tubing between the gas valve
regulator and the venturi port for blockage.

5. If the reading is greater than -0.5 inches (-12.7

mm) W.C., there is a restriction of air through the
heater. This will not harm the heater, only reduce
its output British Thermal Unit (BTU) rating.

To correct the reduced air flow check the following:

Содержание Hi-E EPH 300

Страница 1: ...closed allowing the heater to fire even if the filter pump is off Therefore the height difference between the heater and the pool or spa water surface level must fall within the correct range 2A 2 Hig...

Страница 2: ...by the touch panel pads or when the 120 volt alternating current VAC power to the heater is interrupted 2A 7 Gas Valve The Hi E heater has a negative pressure gas valve that regulates the gas to the...

Страница 3: ...wiring connections solid 8 Is the ignition control in lockout mode Turn the heater off and then back on at the touch panel to restart the ignition sequence If all of these items have been checked look...

Страница 4: ...water flow 2E 2 Temperature Rise Test Case 2 The main reason for a temperature rise value greater than 22 F 12 2 C is a low water flow through the heater Check the installation for the following 1 In...

Страница 5: ...gas Figure 5 Typical Manual Bypass Valve Installation Notes 1 When using metal pipe as heat sink join metal and PVC CPVC using metal male and PVC CPVC female connection 2 A manual bypass valve is used...

Страница 6: ...mm 7 49 mm Color Code Brass Silver 5 The pressure at the gas valve outlet will be 0 2 inch 5 08 mm water column W C less than the pressure at the venturi lower inlet 6 Take a reading The ideal range s...

Страница 7: ...or too many 90 degree elbows see Document 3090B Installation and Operation Manual 3 Worn or dirty combustion air filter 4 Internal blockage in the condensate trap or drain system To check the venturi...

Страница 8: ...preset to work at an optimum elevation of 3 feet 0 91 m above or below the water surface level of the pool spa to be heated see Fig 9 However the switch can be adjusted to operate correctly in heaters...

Страница 9: ...Wiring Diagram LEGEND P PURPLE BL BLUE BK BLACK O ORANGE W WHITE G Y GREEN W YELLOW TRACER BR BROWN W BK WHITE W BLACK TRACER Y YELLOW W R WHITE W RED TRACER R RED BL O BLUE W ORANGE TRACER GY GRAY FA...

Страница 10: ...le Link Blue Wire 24VAC at Fusible Link Red Wire Is Combustion Fan Operating Table 3 Temp Control Sensor Resistance Water Temperature Sensor Resistance F C Ohms 50 10 19 906 60 16 15 314 70 21 11 884...

Страница 11: ...sure 3B 3 Adjusting the Pressure Switch When the heater is installed between 3 and 10 feet 0 91 and 3 05 m below the water surface of the pool or spa the pressure switch senses the increased weight of...

Страница 12: ...sistance in the range of 50 to 400 ohms 3 If the reading is above or below the range of 50 to 400 ohms replace the igniter Figure 10 Adjusting the Pressure Switch 6 Turn pump ON If pressure switch doe...

Страница 13: ...rom the flow control valve see Fig 13 3 Inspect the disk to make sure it is properly seated 4 If the disc is not properly seated disassemble the valve and overhaul it Replace any corroded parts 3B 6 T...

Страница 14: ...aching the combustion air fan to the venturi 10 Hold the combustion air fan with one hand and separate from the venturi 11 Reverse the previous steps to install a new fan Figure 12 Filter Removal Figu...

Страница 15: ...nel assembly by remov ing the three screws along the base of the heater and the four screws on the sides see Fig 15 Two of these screws are inside the heater compartment 7 Remove the hex bolts that fa...

Страница 16: ...al Strip Assembly R0209700 66 Fuse Assembly R0212600 67 Fuse 1 1 4 Amp R0021300 68 Panel Upper Front R0205100 69 Label Upper Front Panel R0209800 70 Bezel Temperature Control R0209900 71 Panel Lower F...

Страница 17: ...Page 17 Hi E Model EPH Pool and Spa Heater...

Страница 18: ...H 03867 603 335 6300 480 S Service Road West Oakville Ontario Canada L6K 2H4 905 844 8233 The above warranty applies only if the installa tion and operating instructions applicable to the model purch...

Отзывы: