background image

Page 12

To test the ignition control:

1. Turn the heater on and observe the ignition

sequence.

2. If the igniter doesn’t glow, turn the power off and

disconnect the igniter from the ignition control.

3. Connect the leads of the voltmeter to the igniter

and igniter/120 terminals of the ignition control.

4. Set the voltmeter on the AC scale with a range of

at least 150V.

5. Turn the heater on.

6. Turn the temperature control knob all the way to

the right. After about 15 seconds, the voltmeter
should read about 120V.

7. If the voltmeter does not read voltage, replace the

ignition control.

3B-5. Testing the Igniter

If there is proper voltage, but the igniter does not

glow, the igniter may be open. To test the igniter:

1. Switch the volt-ohmmeter to read resistance or

ohms, on a range which can read from zero to
about 500 ohms.

2. With the igniter unplugged from the ignition

control, connect the leads of the ohmmeter to the
ends of the igniter wiring (see Fig. 11). A cold
igniter should have resistance in the range of 50 to
400 ohms.

3. If the reading is above or below the range of 50 to

400 ohms, replace the igniter.

Figure 10. Adjusting the Pressure Switch

6. Turn pump ON. If pressure switch does not open,

turn pump OFF and repeat step 5. When pressure
switch opens, go to step 7.

7. Slowly turn the adjustment clockwise until the

pressure switch closes.

8. Then slowly turn the adjustment counterclockwise

until the pressure switch opens again.

9. Turn the pump OFF and ON to check the adjust-

ment. Pause after each attempt. The pressure
switch should open immediately after the pump
stops.

10. Reconnect wires to the pressure switch.

11. After pressure switch is adjusted, the rise should

be taken to verify water flow.

12. Turn the heater ON following the instructions

found on the inside of the heater.

13. Set the temperature control to the desired tempera-

ture.

14. If a satisfactory adjustment cannot be made,

contact a Teledyne Laars representative for
assistance.

3B-4. Testing the Ignition Control

Caution

The ignition control and igniter operate on
120V power. Keep this in mind while
servicing the heater, and take care to avoid
electrical shock.

Figure 11. Igniter Resistance Test

Содержание Hi-E EPH 300

Страница 1: ...closed allowing the heater to fire even if the filter pump is off Therefore the height difference between the heater and the pool or spa water surface level must fall within the correct range 2A 2 Hig...

Страница 2: ...by the touch panel pads or when the 120 volt alternating current VAC power to the heater is interrupted 2A 7 Gas Valve The Hi E heater has a negative pressure gas valve that regulates the gas to the...

Страница 3: ...wiring connections solid 8 Is the ignition control in lockout mode Turn the heater off and then back on at the touch panel to restart the ignition sequence If all of these items have been checked look...

Страница 4: ...water flow 2E 2 Temperature Rise Test Case 2 The main reason for a temperature rise value greater than 22 F 12 2 C is a low water flow through the heater Check the installation for the following 1 In...

Страница 5: ...gas Figure 5 Typical Manual Bypass Valve Installation Notes 1 When using metal pipe as heat sink join metal and PVC CPVC using metal male and PVC CPVC female connection 2 A manual bypass valve is used...

Страница 6: ...mm 7 49 mm Color Code Brass Silver 5 The pressure at the gas valve outlet will be 0 2 inch 5 08 mm water column W C less than the pressure at the venturi lower inlet 6 Take a reading The ideal range s...

Страница 7: ...or too many 90 degree elbows see Document 3090B Installation and Operation Manual 3 Worn or dirty combustion air filter 4 Internal blockage in the condensate trap or drain system To check the venturi...

Страница 8: ...preset to work at an optimum elevation of 3 feet 0 91 m above or below the water surface level of the pool spa to be heated see Fig 9 However the switch can be adjusted to operate correctly in heaters...

Страница 9: ...Wiring Diagram LEGEND P PURPLE BL BLUE BK BLACK O ORANGE W WHITE G Y GREEN W YELLOW TRACER BR BROWN W BK WHITE W BLACK TRACER Y YELLOW W R WHITE W RED TRACER R RED BL O BLUE W ORANGE TRACER GY GRAY FA...

Страница 10: ...le Link Blue Wire 24VAC at Fusible Link Red Wire Is Combustion Fan Operating Table 3 Temp Control Sensor Resistance Water Temperature Sensor Resistance F C Ohms 50 10 19 906 60 16 15 314 70 21 11 884...

Страница 11: ...sure 3B 3 Adjusting the Pressure Switch When the heater is installed between 3 and 10 feet 0 91 and 3 05 m below the water surface of the pool or spa the pressure switch senses the increased weight of...

Страница 12: ...sistance in the range of 50 to 400 ohms 3 If the reading is above or below the range of 50 to 400 ohms replace the igniter Figure 10 Adjusting the Pressure Switch 6 Turn pump ON If pressure switch doe...

Страница 13: ...rom the flow control valve see Fig 13 3 Inspect the disk to make sure it is properly seated 4 If the disc is not properly seated disassemble the valve and overhaul it Replace any corroded parts 3B 6 T...

Страница 14: ...aching the combustion air fan to the venturi 10 Hold the combustion air fan with one hand and separate from the venturi 11 Reverse the previous steps to install a new fan Figure 12 Filter Removal Figu...

Страница 15: ...nel assembly by remov ing the three screws along the base of the heater and the four screws on the sides see Fig 15 Two of these screws are inside the heater compartment 7 Remove the hex bolts that fa...

Страница 16: ...al Strip Assembly R0209700 66 Fuse Assembly R0212600 67 Fuse 1 1 4 Amp R0021300 68 Panel Upper Front R0205100 69 Label Upper Front Panel R0209800 70 Bezel Temperature Control R0209900 71 Panel Lower F...

Страница 17: ...Page 17 Hi E Model EPH Pool and Spa Heater...

Страница 18: ...H 03867 603 335 6300 480 S Service Road West Oakville Ontario Canada L6K 2H4 905 844 8233 The above warranty applies only if the installa tion and operating instructions applicable to the model purch...

Отзывы: